Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the
machine will turn to auto mode as 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24
℃
setting temperature.
8.4.6.4 When there
’s indoor unit running in forced cooling, it is the master forced cooling unit. Other indoor
units will run at forced cooling mode too and they will be the slave forced cooling units. The slave forced
cooling units can not quit forced cooling mode until the master forced cooling unit quit, and turn to cooling
mode at low speed with 24
℃
setting temperature.
7.4.6.5 The slave forced cooling units will not be controlled by other signals.
8.4.7 Timer Function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on automatically when reaching the setting time.
8.4.7.3 Timer off. The machine will turn off automatically when reaching the setting time.
8.4.
7.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
8.4.7.5 Timer off/on. The ma
chine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
8.4.7.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start u
p firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
8.4.7.7 The setting time is relative time.
8.4.8 Sleep mode
8.4.8.1 The sleep function is available in cooling, heating or auto mode.
8.4.8.2. Operation process in sleep mode is as follow.
After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode.
When cooling, The set temperature rise 1
℃
per hour(be lower than 30
℃
). Two hours later, the set
temperature will maintain as a constant and the fan speed is kept at low speed.
When heating, The set temperature decrease 1
℃
per hour(be higher than 17
℃
). Two hours later, the set
temperature will maintain as a constant and the fan speed is kept at low speed (Anti-cold function takes
precedence over all).
When auto, After an hour running under economic mode ,if it is under cooling mode the set temp will rise 1
℃
,
if it is under heating mode the set temp will decrease 1
℃
, if it is under fan-only mode the set temp will be
changeless; the condition will be the same after the air conditioner running under economic mode after 2
hours, and during the next time the set temp do not change.
8.4.8.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and the AC will turn off.
Summary of Contents for 38QUS014DS2 series
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual 2018...
Page 14: ...11 5 Easy operation 6 Remote control and optional wired control method...
Page 17: ...14 3 3 Console 1 6 D ra in p ip e 1 9 5 H a n g in g a rm 7 0 0 6 0 0 2 1 0...
Page 20: ...17 3 6 Ducted A5...
Page 21: ...18 A6...
Page 25: ...22 4 5 Ceiling Floor Type 4 6 Hi wall...
Page 26: ...23 5 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 2 38QUS018DS2...
Page 27: ...24 38QUS021DS3 38QUS027DS3...
Page 28: ...25 38QUS028DS4 38QUS036DS4...
Page 29: ...26 38QUS042DS5 42QHC007D8S 42QHC009D8S 42QHC012D8S 42QHC018D8S 42QHC024D8S 16022000A83297...
Page 30: ...27 42QTD007D8S 42QTD009D8S 42QTD012D8S 42QTD018D8S 42QTD009DS 42QTD012DS 42QTD018DS 42QTD024DS...
Page 31: ...28 42QSS012DS 42QSS007D8S 42QSS009D8S 42QSS012D8S...
Page 32: ...29 42QSS018DS 42QSS024DS 42QZA009DS 42QZA012D8S 42QZA018DS...
Page 33: ...30 6 Static Pressure A5 Ducted...
Page 50: ...47 13 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 38QUS018DS2 2...
Page 52: ...49 38QUS027DS3 38QUS036DS4...
Page 53: ...50 38QUS042DS5...