85
18.3.3.9
High temperature protection of condenser (ODU P5)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temperature less than 52°C.
High temperature protection of
condenser
High temperature protection of
condenser
Check whether the
condenser temperature is
Higher than 65°C
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the
resistance of condenser
temp. sensor is normal
refer to the
Appendix
1
Check whether the
resistance of condenser
temp. sensor is normal
refer to the
Appendix
1
Replace the temperature sensor
Replace the temperature sensor
No
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop the unit
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Check whether the refrigerant
system is ok
Replace outdoor main
board
Replace outdoor main
board
No
Refrigerant is not enough add the
refrigerant
Refrigerant is not enough add the
refrigerant
No
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Correct the connection
Correct the connection
No
Yes
Check the connection
between temperature
sensor and PCB.
Check the connection
between temperature
sensor and PCB.
Yes
Summary of Contents for 38QUS014DS2 series
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual 2018...
Page 14: ...11 5 Easy operation 6 Remote control and optional wired control method...
Page 17: ...14 3 3 Console 1 6 D ra in p ip e 1 9 5 H a n g in g a rm 7 0 0 6 0 0 2 1 0...
Page 20: ...17 3 6 Ducted A5...
Page 21: ...18 A6...
Page 25: ...22 4 5 Ceiling Floor Type 4 6 Hi wall...
Page 26: ...23 5 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 2 38QUS018DS2...
Page 27: ...24 38QUS021DS3 38QUS027DS3...
Page 28: ...25 38QUS028DS4 38QUS036DS4...
Page 29: ...26 38QUS042DS5 42QHC007D8S 42QHC009D8S 42QHC012D8S 42QHC018D8S 42QHC024D8S 16022000A83297...
Page 30: ...27 42QTD007D8S 42QTD009D8S 42QTD012D8S 42QTD018D8S 42QTD009DS 42QTD012DS 42QTD018DS 42QTD024DS...
Page 31: ...28 42QSS012DS 42QSS007D8S 42QSS009D8S 42QSS012D8S...
Page 32: ...29 42QSS018DS 42QSS024DS 42QZA009DS 42QZA012D8S 42QZA018DS...
Page 33: ...30 6 Static Pressure A5 Ducted...
Page 50: ...47 13 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 38QUS018DS2 2...
Page 52: ...49 38QUS027DS3 38QUS036DS4...
Page 53: ...50 38QUS042DS5...