64
36
AD value of voltage
For example ,the digital display tube show “Cd”, it means AD value is
205.
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show single
digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV
open angle is 120×4=480p.)
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
Bit7
Frequency limit caused by IGBT
radiator
The display value
is hex number. For
example, the
digital display tube
show 2A,then
Bit5=1, Bit3=1,
Bit1=1.
It means
frequency limit
caused by T4,T3
and current.
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
43
Average value of T2
(Sum T2 value of all indoor units)/( number of indoor units in good
connection)(cooling:T2B, heating:T2)
44
Outdoor unit fan motor state
Fan off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super
breeze:5
45
The last error or protection code
00 means no malfunction and protection
17.5 Protection
17.5.1 Three minutes delay at restart for compressor.
17.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
T 5
C o m p r e s s o r o f f
F r e q u e n c y lim it
N o r m a l
F r e q u e n c y h o l d in g
17.5.3 Low voltage protection
V O L T A G E
N o li m it
V O L T _ L T M _ F R E Q 1 _ A D D
V O L T _ L T M _ F R E Q 2 _ A D D
Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always
after restart the machine.
Summary of Contents for 38QUS014DS2 series
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual 2018...
Page 14: ...11 5 Easy operation 6 Remote control and optional wired control method...
Page 17: ...14 3 3 Console 1 6 D ra in p ip e 1 9 5 H a n g in g a rm 7 0 0 6 0 0 2 1 0...
Page 20: ...17 3 6 Ducted A5...
Page 21: ...18 A6...
Page 25: ...22 4 5 Ceiling Floor Type 4 6 Hi wall...
Page 26: ...23 5 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 2 38QUS018DS2...
Page 27: ...24 38QUS021DS3 38QUS027DS3...
Page 28: ...25 38QUS028DS4 38QUS036DS4...
Page 29: ...26 38QUS042DS5 42QHC007D8S 42QHC009D8S 42QHC012D8S 42QHC018D8S 42QHC024D8S 16022000A83297...
Page 30: ...27 42QTD007D8S 42QTD009D8S 42QTD012D8S 42QTD018D8S 42QTD009DS 42QTD012DS 42QTD018DS 42QTD024DS...
Page 31: ...28 42QSS012DS 42QSS007D8S 42QSS009D8S 42QSS012D8S...
Page 32: ...29 42QSS018DS 42QSS024DS 42QZA009DS 42QZA012D8S 42QZA018DS...
Page 33: ...30 6 Static Pressure A5 Ducted...
Page 50: ...47 13 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 38QUS018DS2 2...
Page 52: ...49 38QUS027DS3 38QUS036DS4...
Page 53: ...50 38QUS042DS5...