While A,B,C…means different fan speed of outdoor unit.
8.4.2.2 Indoor fan running rules
For all models:
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
When the compressor is running, the indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H+(H+=H+G)
A
H(=H)
B
C
M+(M+=M+Z)
D
M(M=M)
E
F
L+(L+=L+D)
G
L(L=L)
H
I
T1-Td
℃
(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
a
b
c
d
T 1 - T d
e
H
( H - L ) * 0 . 7 5 + L
( H - L ) * 0 . 5 + L
( H - L ) * 0 . 2 5 + L
L
8.4.2.3 Evaporator low temperature T2 protection
For all models: When T2<4
℃
for 250s or T2<0
℃
, the indoor has no capacity demand and resume till
T2>8
℃
Summary of Contents for 38QUS014DS2 series
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual 2018...
Page 14: ...11 5 Easy operation 6 Remote control and optional wired control method...
Page 17: ...14 3 3 Console 1 6 D ra in p ip e 1 9 5 H a n g in g a rm 7 0 0 6 0 0 2 1 0...
Page 20: ...17 3 6 Ducted A5...
Page 21: ...18 A6...
Page 25: ...22 4 5 Ceiling Floor Type 4 6 Hi wall...
Page 26: ...23 5 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 2 38QUS018DS2...
Page 27: ...24 38QUS021DS3 38QUS027DS3...
Page 28: ...25 38QUS028DS4 38QUS036DS4...
Page 29: ...26 38QUS042DS5 42QHC007D8S 42QHC009D8S 42QHC012D8S 42QHC018D8S 42QHC024D8S 16022000A83297...
Page 30: ...27 42QTD007D8S 42QTD009D8S 42QTD012D8S 42QTD018D8S 42QTD009DS 42QTD012DS 42QTD018DS 42QTD024DS...
Page 31: ...28 42QSS012DS 42QSS007D8S 42QSS009D8S 42QSS012D8S...
Page 32: ...29 42QSS018DS 42QSS024DS 42QZA009DS 42QZA012D8S 42QZA018DS...
Page 33: ...30 6 Static Pressure A5 Ducted...
Page 50: ...47 13 Wiring diagram 38QUS014DS2 38QUS014DS2 2 38QUS018DS2 38QUS018DS2 2...
Page 52: ...49 38QUS027DS3 38QUS036DS4...
Page 53: ...50 38QUS042DS5...