background image

5

RIG AND MOUNT UNIT

Mounting on Ground

Mount unit on a solid, level concrete pad. Position unit so water or

ice from roof does not fall directly onto unit. Accessory stacking
kits can be used when units are to be stacked. See installation

instructions provided with the accessory kit. Use field--provided
snow stand or ice rack where prolonged subfreezing temperatures

or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6

field--supplied tiedown bolts should be used and fastened through

slots provided in unit mounting feet.
For hurricane tie downs -- contact your local distributor for details

and PE (Professional Certification), if required by local authorities.

Mounting on Roof

Mount unit on a level platform or frame at least 6 in. (152.4 mm)
above roof surface. Isolate unit and tubing from structure.

Rigging

PERSONAL

INJURY

AND/OR

EQUIPMENT

DAMAGE HAZARD

Failure to follow this caution may result in personal injury

and/or equipment damage.

Be sure unit panels are securely in place prior to rigging.

CAUTION

!

Keep the unit upright and lift unit using a sling. Use cardboard or
padding under the sling, and spreader bars to prevent sling damage

to the unit. See Fig. 4. See Fig. 3 for center of gravity reference.
Install the unit so that the coil does not face into prevailing winds.

If this is not possible and constant winds above 25 mph are

expected, use accessory wind baffle. See installation instructions
provided with the accessory kit.

NOTE

: Accessory wind baffles should be used on all units with

accessory low ambient temperature control.
Field--fabricated snow or ice stands may be used to raise unit when

operation will be required during winter months. Units may also be

wall mounted using the accessory wall mounting kit.

A07396

Fig. 4 -- Lifting Unit with Sling

COMPLETE REFRIGERANT PIPING

CONNECTIONS

Outdoor units may be connected to indoor units using
field--supplied tubing of refrigerant grade and condition. See Table

1 for correct line sizes. Do not use less than 10 ft (3.05 m) of

interconnecting tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4

mm) vertical rise to the valve connections on the outdoor

unit. If more than the recommended length is buried,

refrigerant may migrate to cooler, buried section during

extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start--up.

When more than 80 ft (24.4 m) of interconnecting tubing is used,
consult the Duct--Free Split System Long Line Application Guide

for required accessories. If either refrigerant tubing or indoor coil

is exposed to the atmosphere, the system must be evacuated
following good refrigeration practices.
Run refrigerant tubes as directly as possible. Insulate both tubes,
avoiding unnecessary turns and bends. Suspend refrigerant tubes to

avoid damage to insulation or tubes so that they do not transmit

vibration to structure. Also, when passing refrigerant tubes through
a wall, seal the opening so rain or insects do not enter structure.

Leave some slack in refrigerant tubes between structure and
outdoor unit to absorb vibration. Refer to separate indoor unit

installation instructions for additional information.

Filter Drier

Refer to Fig. 2 and install filter drier as follows:

1. Assemble all parts as shown in Fig. 2
2. The filter drier must be replaced whenever the refrigeration

system is exposed to the atmosphere.

3. Only use factory specified liquid--line filter driers with rated

working pressures less than 600 psig.

NOTE

: Do not install a suction--line filter drier in liquid line.

38Q

RF

Summary of Contents for 38QRF018 --- --- ---3

Page 1: ...rations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and Nationa...

Page 2: ...r airflow clearance wiring refrigerant piping and servicing unit See Fig 3 Locate unit so that condenser airflow is unrestricted on both sides Refer to Fig 3 Unit may be mounted on a level pad directl...

Page 3: ...468 3 774 7 498 5 741 865 5 347 7 206 4 403 2 88 165 4 UNIT SIZE M OPERATING WT in mm lb kg 38QRF HEAT PUMPS 018 5 8 15 88 166 75 3 024 5 8 15 88 176 79 8 030 3 4 19 05 187 84 8 035 3 4 19 05 221 100...

Page 4: ...1720 850 3900 850 3900 850 3900 Diameter in 18 18 24 24 24 No Blades 3 3 3 3 3 Motor hp 1 8 1 8 1 4 1 4 1 4 OUTDOOR COIL Face Area sq ft 5 8 7 3 12 1 12 1 12 1 No Rows 2 3 2 2 2 FPI 20 20 20 20 20 HI...

Page 5: ...ll mounting kit A07396 Fig 4 Lifting Unit with Sling COMPLETE REFRIGERANT PIPING CONNECTIONS Outdoor units may be connected to indoor units using field supplied tubing of refrigerant grade and conditi...

Page 6: ...Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Power Wiring Unit is factory wired for voltage shown on nameplate Provide ad...

Page 7: ...utdoor unit through O on outdoor unit terminal board 5 24 v from the microprocessor control Y energizes the contactor coil in the outdoor unit The com pressor will run 6 If the HPS internal protector...

Page 8: ...2 All motors compressors contain internal overload protection 3 In compliance with NEC U S A Standard requirements for multi motor and combination load equipment refer to NEC Articles 430 and 440 the...

Page 9: ...ure rating must be 400 psig DOT Department of Transportation 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose wh...

Page 10: ...utdown when compressor is not operating If the crankcase heater is de energized for more than 6 hours both compressor service valves must be closed The crankcase heater is powered by the high voltage...

Page 11: ...lines should be similar Any temperature difference would be due to heat loss or gain across valve body Temperatures are best checked with a remote reading electronic type thermometer with multiple pro...

Page 12: ...9 58 7 3 13 72 160 56 2 13 44 262 86 9 30 50 364 110 0 43 33 466 128 7 53 72 596 148 4 64 67 60 8 6 13 00 162 57 0 13 89 264 87 4 30 78 366 110 4 43 56 468 129 0 53 89 600 149 0 65 00 62 10 0 12 22 16...

Page 13: ...ompressor air Note that the blow thru design causes dirt and debris to build up on the inside of the coils Clean coil annually or as required by location and outdoor air conditions Inspect coil monthl...

Page 14: ...END NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07435 Fig 11 Troubleshoo...

Page 15: ...EGEND NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07436 Fig 12 Troublesh...

Page 16: ...310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 05 08 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Cata...

Reviews: