13
MAINTENANCE
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
LUBRICATION
Compressor
Compressor contains factory oil charge; replace oil when lost. Use
Mobile 3MA--POE oil.
CLEANING COILS
Coil should be washed out with water or blown out with
compressor air. Note that the blow--thru design causes dirt and
debris to build up on the inside of the coils. Clean coil annually or
as required by location and outdoor air conditions. Inspect coil
monthly and clean as required. Fins are not continuous through
coil sections. Dirt and debris may pass through first section,
become trapped between the row of fins and restrict condenser
airflow. Use a flashlight to determine if dirt or debris has collected
between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Using a garden hose or other suitable equipment, flush coil
from the outside to remove dirt. Be sure to flush all dirt and
debris from drain holes in base of unit. Fan motors are wa-
terproof.