background image

11

Reversing Valve

In heat pumps, changeover between heating and cooling modes is

accomplished with a valve that reverses flow of refrigerant in the
system. The reversing valve solenoid can be checked with the

power off using an ohmmeter. Check for continuity and shorting to
ground. With control circuit (24 v) power on, check for correct

voltage at solenoid coil, and for burned or overheated solenoid.
With unit operating, other items can be checked, such as frost or

condensate on refrigerant lines.
Using a remote measuring device, check inlet and outlet line
temperatures. Do not touch lines. If reversing valve is operating

normally, inlet and outlet temperatures on appropriate lines should
be similar. Any temperature difference would be due to heat loss or

gain across valve body. Temperatures are best checked with a
remote reading electronic--type thermometer with multiple probes.
Figures 9 and 10 show test points on reversing valve for recording
temperatures. Insulate points for more accurate reading. If valve is

defective:

1. Shut off all power to unit.
2. Remove all charge from system.
3. Remove valve using a tubing cutter.
4. Install new valve (wrap valve with a wet rag to prevent

overheating while brazing).

5. After valve is brazed in, check for leaks.
6. Evacuate and charge system. Operate system in both modes

several times to be sure valve functions properly.

LEGEND

TP —

Test Point

A07433

Fig. 9 -- Reversing Valve

(Cooling Mode or Defrost Mode, Solenoid Energized)

LEGEND

TP —

Test Point

A07434

Fig. 10 -- Reversing Valve

(Heating Mode, Solenoid De--energized)

38Q

RF

Summary of Contents for 38QRF018 --- --- ---3

Page 1: ...rations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and Nationa...

Page 2: ...r airflow clearance wiring refrigerant piping and servicing unit See Fig 3 Locate unit so that condenser airflow is unrestricted on both sides Refer to Fig 3 Unit may be mounted on a level pad directl...

Page 3: ...468 3 774 7 498 5 741 865 5 347 7 206 4 403 2 88 165 4 UNIT SIZE M OPERATING WT in mm lb kg 38QRF HEAT PUMPS 018 5 8 15 88 166 75 3 024 5 8 15 88 176 79 8 030 3 4 19 05 187 84 8 035 3 4 19 05 221 100...

Page 4: ...1720 850 3900 850 3900 850 3900 Diameter in 18 18 24 24 24 No Blades 3 3 3 3 3 Motor hp 1 8 1 8 1 4 1 4 1 4 OUTDOOR COIL Face Area sq ft 5 8 7 3 12 1 12 1 12 1 No Rows 2 3 2 2 2 FPI 20 20 20 20 20 HI...

Page 5: ...ll mounting kit A07396 Fig 4 Lifting Unit with Sling COMPLETE REFRIGERANT PIPING CONNECTIONS Outdoor units may be connected to indoor units using field supplied tubing of refrigerant grade and conditi...

Page 6: ...Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Power Wiring Unit is factory wired for voltage shown on nameplate Provide ad...

Page 7: ...utdoor unit through O on outdoor unit terminal board 5 24 v from the microprocessor control Y energizes the contactor coil in the outdoor unit The com pressor will run 6 If the HPS internal protector...

Page 8: ...2 All motors compressors contain internal overload protection 3 In compliance with NEC U S A Standard requirements for multi motor and combination load equipment refer to NEC Articles 430 and 440 the...

Page 9: ...ure rating must be 400 psig DOT Department of Transportation 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose wh...

Page 10: ...utdown when compressor is not operating If the crankcase heater is de energized for more than 6 hours both compressor service valves must be closed The crankcase heater is powered by the high voltage...

Page 11: ...lines should be similar Any temperature difference would be due to heat loss or gain across valve body Temperatures are best checked with a remote reading electronic type thermometer with multiple pro...

Page 12: ...9 58 7 3 13 72 160 56 2 13 44 262 86 9 30 50 364 110 0 43 33 466 128 7 53 72 596 148 4 64 67 60 8 6 13 00 162 57 0 13 89 264 87 4 30 78 366 110 4 43 56 468 129 0 53 89 600 149 0 65 00 62 10 0 12 22 16...

Page 13: ...ompressor air Note that the blow thru design causes dirt and debris to build up on the inside of the coils Clean coil annually or as required by location and outdoor air conditions Inspect coil monthl...

Page 14: ...END NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07435 Fig 11 Troubleshoo...

Page 15: ...EGEND NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07436 Fig 12 Troublesh...

Page 16: ...310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 05 08 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Cata...

Reviews: