5

How to remove the drain cap

Clip the drain cap by needle-nose 
pliers and pull out.

How to 

fi

 x the drain cap

1) Insert hexagon 
 

wrench (4 mm) 

 

in a center head.

4 mm

2)  Firmly insert the drain cap.

Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. Application
causes deterioration and drain
leakage of the plug.

Insert a hexagon
wrench (4 mm).

No gap

Firmly insert the drain hose and drain cap; otherwise, water may leak.

In case of right or left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool.

 

In case of bottom right or bottom left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool.

 

Slit

Slit

Left-hand connection with piping

•  Bend the connecting pipe so that it is laid within 43 mm above the wall sur-

face. If the connecting pipe is laid exceeding 43 mm above the wall surface, 
the indoor unit may unstably be set on the wall.

  When bending the connecting pipe, make sure to use a spring bender so as 

not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (

fi

 gure)

42NQ009

42NQ012

A

270

270

B

170

230

CAUTION

80

A mm

B mm

m

3

4

Liquid side

Gas side

(To the forefront of 

fl

 are)

Outward form of indoor unit

R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)

Use the handle of screwdriver, etc.

 

NOTE

If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the 
connecting pipes to the auxiliary pipes and wrap the facing tape around 
them.

•  Bind the auxiliary pipes (two) and connecting cable with facing tape 

tightly. In case of leftward piping and rear-leftward piping, bind the 
auxiliary pipes (two) only with facing tape.

Auxiliary pipes

Indoor unit

Connecting cable

Installation plate

 

CAUTION

Indoor Unit Fixing

• For detaching the indoor unit from the 

installation plate, pull the indoor unit toward 
you while pushing its bottom up at the 
speci

fi

 ed parts.

Push

Push

Press

(unhook)

Hook

Hook here.

1

2

 Installation plate

1

1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 

installation plate at the upper hook.

2.  Swing the indoor unit to right and left to con

fi

 rm that it is 

fi

 rmly hooked up on 

the installation plate.

3.  While pressing the indoor unit onto the wall, hook it at the lower part on the 

installation plate. Pull the indoor unit toward you to con

fi

 rm that it is 

fi

 rmly 

hooked up on the installation plate.

Drainage

1.  Run the drain hose sloped downwards.

2.  Put water in the drain pan and make sure that the water is drained out of 

doors.

3. When connecting extension drain hose, insulate the connecting part of 

extension drain hose with shield pipe.

 NOTE

•  The hole should be made at a slight downward slant on the outdoor side.

50 mm
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

Do not form the
drain hose into
a wavy shape.

Do not rise the
drain hose.

Extension drain hose

Inside the room

Drain hose

Shield pipe

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

CAUTION

•  Carefully arrange pipes so that any pipe does not stick out of the rear 

plate of the indoor unit.

• Carefully connect the auxiliary pipes and connecting pipes to one 

another and cut off the insulating tape wound on the connecting pipe to 
avoid double-taping at the joint; moreover, seal the joint with the vinyl 
tape, etc.

•  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

•  When bending a pipe, carefully do it, not to crush it. 

Wall

Drain
guide

Space for pipes

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

1110251161-EN.indd   5

1110251161-EN.indd   5

12/28/07   6:10:52 PM

12/28/07   6:10:52 PM

Summary of Contents for 38NY009-012 Series

Page 1: ...012 Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR TÜRKÇE NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA ...

Page 2: ... 7 n Definição do interruptor do telecomando 7 n Selecção A B do telecomando 7 n Execução do Teste 7 n Definindo de Reiniciação Automática 7 PT SPIS TREŚCI ZASADY BEZPIECZEŃSTWA 1 SCHEMAT INSTALACYJNY URZĄDZENIA WEWNĘTRZNEGO I ZEWNĘTRZNEGO 2 n Dodatkowe Części Instalacyjne 2 URZĄDZENIE WEWNĘTRZNE 3 n Miejsce Instalacji 3 n Wycinanie Otworu oraz Montaż Płyty Instalacyjnej 3 n Prace Elektryczne 3 n ...

Page 3: ...IR INTO THE ROOM IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE IT CAUSES GENERATION OF POISONOUS GAS Exposure of unit to water or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install in a place that can increase the vibration of the...

Page 4: ...frigerant pipes separately with insulation not together 2 3 8 4 Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Bat...

Page 5: ... installation plate A D B C 1 7 Anchor bolt holes Hook Hook Hook Pipe hole Pipe hole Installation plate Mounting screw Weight Indoor unit Thread 2 m or more from fl oor 42NQ009 42NQ012 A 35 mm 62 mm B 55 5 mm 82 5 mm C 120 mm 170 mm D 65 mm 85 mm When the installation plate is directly mounted on the wall 1 Securely fit the installation plate onto the wall by screwing it in the upper and lower par...

Page 6: ...he indoor unit When attaching the air inlet grille the contrary of the removed operation is performed NOTE Use stranded wire only Wire type H07RN F or more Rear right Rear left g n i t t u c e i D t i l s l e n a p t n o r f g n i g n a h C e s o h n i a r d n o i t a r a p e r p g n i p i P Bottom left Left Bottom right Right Piping and Drain Hose Installation Since dewing results in a machine tr...

Page 7: ...ing cable Installation plate CAUTION Indoor Unit Fixing For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts Push Push Press unhook Hook Hook here 1 2 Installation plate 1 1 Pass the pipe through the hole in the wall and hook the indoor unit on the installation plate at the upper hook 2 Swing the indoor unit to...

Page 8: ...30 to 42 3 0 to 4 2 kgf m Ø12 70 mm 50 to 62 5 0 to 6 2 kgf m Evacuating After the piping has been connected to the indoor unit you can perform the air purge together at once Tightening torque of flare pipe connections Flare at indoor unit side Flare at outdoor unit side The operating pressure of R410A is higher than that of R22 approx 1 6 times It is therefore necessary to firmly tighten the flar...

Page 9: ...ctory is A To separate using of remote control for each indoor unit in case of 2 air conditioner are installed nearly Remote Control B Setup 1 Press RESET button on the indoor unit to turn the air conditioner ON 2 Point the remote control at the indoor unit When two indoor units are installed in the same room or adjacent two rooms if operating a unit two units may receive the remote control signal...

Reviews: