14
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve
counterclockwise approximately 90’, wait 10
seconds, and then set it to closed position.
Be sure to use a hexagonal wrench to operate the
valve stem.
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2-way valve to the open position and
remove the cap from the 3-
way valve’s service port.
Using the hexagonal wrench to press the valve core
pin, discharge for three seconds and then wait for
one minute.
5. Use torque wrench to tighten the service port
cap to a torque of 1.8 kgf.m. (18N.m)
6. Set the 3-way valve to the opened position.
7. Mounted the valve stem nuts to the 2-way
and 3-way valves.
8. Check for gas leakage.
At this time, especially check for gas leakage
from the 2-way and 3-way stem nuts, and from the
service port.
Caution:
If gas leakage is discovered in step (3) above, take
the following measures.
If the leaks stop when the piping connections are
tightened further, continue working from step (4).
If the gas leaks do not stop when the connections
are retightened, repair the location of the leak,
discharge all of the gas through the service port,
and then recharge with the specified amount of gas
from a gas cylinder.
Summary of Contents for 38LUVH025N
Page 8: ...6 3 Dimension 3 1 Indoor Unit 42LUVH025N 42LUVH035N 42LUVH045N...
Page 9: ...7 3 2 Outdoor Unit 38LUVH025N 38LUVH035N 38LUVH045N...
Page 10: ...8 4 Refrigerant cycle diagram...
Page 11: ...9 5 Wiring diagram 5 1 Indoor Unit 42LUVH025N 42LUVH035N...
Page 12: ...10 42LUVH045N 5 2 Outdoor Unit 38LUVH025N 38LUVH035N...
Page 13: ...11 38LUVH045N...
Page 42: ...40...