6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the
hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
6.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make
the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
Electronic scale
Summary of Contents for 38HVM109303P
Page 13: ...13 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W MOF 18HFN1 MU0W...
Page 14: ...14 MOG 24HFN1 MT0W...
Page 29: ...29 If T4 5 or the compressor starts running the preheating function will stop...
Page 47: ...47 9 2 2 Indoor outdoor units communication error diagnosis and solution E1...
Page 48: ...48 9 2 3 Fan speed has been out of control diagnosis and solution E3 E7...
Page 50: ...50 9 2 4 Open circuit or short circuit of temperature sensors diagnosis and solution E5 E6...
Page 51: ...51 9 2 5 IPM malfunction or IGBT over strong current protection diagnosis and solution P0...
Page 52: ...52 9 2 6 Over voltage or over low voltage protection diagnosis and solution P1...
Page 54: ...54 9 2 9 Inverter compressor drive error diagnosis and solution P4...