28
8.3 Main Protection
8.3.1 Three Minutes Delay at restart for compressor
1 minute delay for the 1
st
time start-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
8.3.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
---Compressor discharge temp. T5>115
for 5s, compressor stops.
℃
---108<T5<115
, decrease the frequency to the lower level every 3 minutes.
℃
---90<T5<105
, keep running a
℃
t the current frequency.
----T5<90
, no limit for frequency.
℃
8.3.4 Fan Speed is out of control
When Indoor Fan Speed keeps too low (300RPM) for certain time, the unit will stop and the LED will
display the failure
8.3.5 Inverter module Protection
The Inverter module has a protection function about current, voltage and temperature. If these
protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
8.3.7 Compressor preheating functions
Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3
and the machine connects to power supply newly or if T4
℃
<
3
and compre
℃
ssor has stopped for over 3 hours, the compressor heating cable will work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of the compressor, then the
compressor is heated without operation.
Preheating release condition:
Summary of Contents for 38HVM109303P
Page 13: ...13 5 2 Outdoor Unit MOC 09HFN1 MW0W MOC 12HFN1 MV0W MOF 18HFN1 MU0W...
Page 14: ...14 MOG 24HFN1 MT0W...
Page 29: ...29 If T4 5 or the compressor starts running the preheating function will stop...
Page 47: ...47 9 2 2 Indoor outdoor units communication error diagnosis and solution E1...
Page 48: ...48 9 2 3 Fan speed has been out of control diagnosis and solution E3 E7...
Page 50: ...50 9 2 4 Open circuit or short circuit of temperature sensors diagnosis and solution E5 E6...
Page 51: ...51 9 2 5 IPM malfunction or IGBT over strong current protection diagnosis and solution P0...
Page 52: ...52 9 2 6 Over voltage or over low voltage protection diagnosis and solution P1...
Page 54: ...54 9 2 9 Inverter compressor drive error diagnosis and solution P4...