background image

7

Step 4

Make Electrical connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Unit failure as a result of operation on improper line voltage

or excessive phase imbalance constitutes abuse and may

cause damage to electrical components. Such operation

would void any applicable Carrier warranty.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance, be sure indoor

unit main power switch is turned OFF and indoor blower

has stopped.

Control Circuit Wiring

Control voltage is 24 v (40 va minimum). See Fig. 5 and unit label

diagram for field--supplied wiring details. Route control wire
through opening in unit side panel to connection in unit control

box.

A07398

Fig. 5

---

38HDR Typical Control Circuit Connections

NOTE

:

Use No. 18 AWG color----coded, insulated (35

_

C

minimum) wire. If thermostat is located more than 100 ft (30.48
m). from unit, as measured along the control voltage wires, use No.
16 AWG color--coded wire to avoid excessive voltage drop.

NOTE

: All wiring must conform to NEC and local codes.

NOTE

: Operating unit on improper line voltage constitutes abuse

and could affect Carrier warranty. See Table 2.

Do not

install unit

in a system where voltage may fluctuate above or below
permissible limits.
See Table 2 for recommended fuse sizes. When making electrical

connections, provide clearance at the unit for refrigerant piping
connections.

NOTE

: The 38HDR units use the control transformer supplied

with the matched indoor unit.

Power Wiring

Unit is factory wired for voltage shown on nameplate. Provide

adequate, fused disconnect switch within sight from unit, readily
accessible, but out of reach of children. Provision for locking the

switch open (off) is advisable to prevent power from being turned
on while unit is being serviced.
Disconnect switch, fuses, and field wiring must comply with the

NEC and local code requirements. Use copper wire only between
the disconnect switch and unit. Use minimum 60 C wire for the

field power connection.
Route power wires through the opening in unit side panel and

connect in the unit control box as shown on the unit label diagram
and Fig. 6. Unit must be grounded.

Connections to Duct Free Fan Coil Units

The 38HDR units are designed for easy match--up to 40QA duct free
fan coils. This unit provides 24 v power for the outdoor unit from the

fan coil. Connect the Y and C terminals of the indoor unit to the Y and

C terminals.

38H

D

R

Summary of Contents for 38HDR

Page 1: ...brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes...

Page 2: ...ee Fig 2 Locate unit so that condenser airflow is unrestricted on both sides Refer to Fig 2 Unit may be mounted on a level pad directly on base legs or mounted on raised pads at support points See Fig...

Page 3: ...1 13 16 3 4 1 16 1 2 1 2 0 8 1 2 1 6 7 8 0 3 7 16 0 6 1 2 1097 1131 9 433 4 468 3 774 7 498 5 893 4 1017 9 354 2 215 9 479 4 88 165 4 UNIT SIZE M OPERATING WT in mm lb kg 38HDR 018 5 8 15 88 166 75 8...

Page 4: ...n If any section of pipe is buried there must be a 6 in 152 4 mm vertical rise to the valve connections on the outdoor unit If more than the recommended length is buried refrigerant may migrate to coo...

Page 5: ...lves are closed from the factory and are ready for brazing After wrapping the service valve with a wet cloth the tubing set can be brazed to the service valve using either silver bearing or non silver...

Page 6: ...2 3 3 FPI 20 20 20 20 20 20 HIGH PRESSURE SWITCH Cut In psig Cutout psig 420 25 650 10 LOW PRESSURE SWITCH Low Cutout psig Low Cut in psig 20 5 45 25 REFRIGERANT LINES Connection Type Sweat Liquid Lin...

Page 7: ...unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop NOTE All wiring must conform to NEC and local codes NOTE Operating unit on improper lin...

Page 8: ...al power source Copper wire must be used from service disconnect to unit 2 All motors compressors contain internal overload protection 3 In compliance with NEC U S A Standard requirements for multi mo...

Page 9: ...Heater COMP Compressor Motor EQUIP Equipment GND Ground HPS High Pressure Switch LPS Low Pressure Switch OFM Outdoor Fan Motor OL Overload TB Terminal Board Splice Field Terminal Marked Terminal Unma...

Page 10: ...isconnect switch Lock out and tag switch with a suitable warning label Outdoor Fan A reinforced wire mount holds the outdoor fan assembly in position See Fig 7 for proper mounting position 38HDR Unit...

Page 11: ...before brazing The service valve cannot be field repaired therefore only a complete valve or valve stem seal and service port caps are available for replacement Refrigerant Charging WARNING PERSONAL...

Page 12: ...9 58 7 3 13 72 160 56 2 13 44 262 86 9 30 50 364 110 0 43 33 466 128 7 53 72 596 148 4 64 67 60 8 6 13 00 162 57 0 13 89 264 87 4 30 78 366 110 4 43 56 468 129 0 53 89 600 149 0 65 00 62 10 0 12 22 16...

Page 13: ...02 62 34 60 33 58 32 56 31 54 30 52 29 208 64 36 62 34 60 33 58 32 56 31 54 30 215 66 37 64 36 62 34 60 33 58 32 56 31 222 68 38 66 37 64 36 62 34 60 33 58 32 229 70 39 68 38 66 37 64 36 62 34 60 33 2...

Page 14: ...r conditions Inspect coil monthly and clean as required Fins are not continuous through coil sections Dirt and debris may pass through first section become trapped between the row of fins and restrict...

Reviews: