background image

11

High--Pressure Switch

The high--pressure switch, located on discharge line, protects

against high discharge pressures caused by such events as
overcharge, condenser--fan motor failure, system restriction, etc. It

opens on pressure rise at about 650

±

10 psig. If system pressures

go above this setting during abnormal conditions, the switch

opens.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal

injury or death.

DO NOT

attempt to

simulate

these system

abnormalities -- high pressures pose a serious safety

hazard.

The high--pressure switch is checked with an ohmmeter. If system

pressure is below 625 psig switch shows continuity.

Crankcase Heater

The crankcase heater prevents refrigerant migration and
compressor oil dilution during shutdown when compressor is not

operating. If the crankcase heater is de--energized for more than 6

hours, both compressor service valves must be closed.

NOTE

: Crankcase heaters are only available on 38HDR030--060

units.
The crankcase heater is powered by the high--voltage power of the
unit. It is connected across the line side of the contactor and is

thermostatically controlled.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal

injury or death.
Use extreme caution when troubleshooting this device

as line voltage is continually present.

To troubleshoot:

1. Apply voltmeter across crankcase heater leads to see if heat-

er voltage is on. Do not touch heater. Carefully feel area

around crankcase heater; if warm, crankcase heater is func-
tioning.

2. With power off and heater leads disconnected, check across

leads with ohmmeter. Do not look for a specific resistance
reading. Check for resistance or an open circuit, and change

heater if an open circuit is detected.

Service Valves

The service valves in the outdoor unit come from the factory
frontseated. This means the refrigerant charge is isolated from the

line--set connection ports. To prevent damage to the valve, use a
wet cloth or other accepted heat sink material on the valve before

brazing.
The service valve cannot be field repaired, therefore, only a

complete valve or valve stem seal and service port caps are

available for replacement.

Refrigerant Charging

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal

injury and/or equipment damage.
Wear safety glasses and gloves when handling

refrigerant. Do not overcharge system -- this can cause

compressor flooding.

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal

injury and/or equipment damage.
Service valves must be fully backseated to close service

port. There is no Schrader valve at the service port, and

failure to backseat the valve could result in loss of

system charge or personal injury.

NOTE

:

Do not vent or de--pressurize unit refrigerant to

atmosphere. Remove and recover refrigerant following accepted
practices.
All units are shipped with the refrigerant charge listed on the

nameplate.
Refer to Table 3 and consider the following when working with
Puron

r

refrigerant:

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400
psig, DOT (Department of Transportation) 4BA400 or
DOT BW400.

S

Puron systems should be charged with liquid refrigerant.
Use a commercial type metering device in the manifold
hose when charging into suction line with compressor op-

erating.

S

Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low--side retard.

S

Use hoses with 700 psig service pressure rating.

S

Puron refrigerant, as with other HFCs, is only compatible
with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Polyol Ester oils absorb moisture rapidly. Do not expose
oil to atmosphere.

S

Polyol Ester oils may cause damage to certain plastics and
roofing materials.

S

Wrap all filter driers and service valves with wet cloth when
brazing.

S

Factory approved, liquid--line filter drier is required on ev-

ery unit.

S

Do not use a TXV (thermostatic expansion valve) de-
signed for use with R--22 refrigerant. Refer to separate in-
door unit installation instructions for more details.

S

If using a suction line drier, do not leave in place for more
than 72 hours.

38H

D

R

Summary of Contents for 38HDR

Page 1: ...brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes...

Page 2: ...ee Fig 2 Locate unit so that condenser airflow is unrestricted on both sides Refer to Fig 2 Unit may be mounted on a level pad directly on base legs or mounted on raised pads at support points See Fig...

Page 3: ...1 13 16 3 4 1 16 1 2 1 2 0 8 1 2 1 6 7 8 0 3 7 16 0 6 1 2 1097 1131 9 433 4 468 3 774 7 498 5 893 4 1017 9 354 2 215 9 479 4 88 165 4 UNIT SIZE M OPERATING WT in mm lb kg 38HDR 018 5 8 15 88 166 75 8...

Page 4: ...n If any section of pipe is buried there must be a 6 in 152 4 mm vertical rise to the valve connections on the outdoor unit If more than the recommended length is buried refrigerant may migrate to coo...

Page 5: ...lves are closed from the factory and are ready for brazing After wrapping the service valve with a wet cloth the tubing set can be brazed to the service valve using either silver bearing or non silver...

Page 6: ...2 3 3 FPI 20 20 20 20 20 20 HIGH PRESSURE SWITCH Cut In psig Cutout psig 420 25 650 10 LOW PRESSURE SWITCH Low Cutout psig Low Cut in psig 20 5 45 25 REFRIGERANT LINES Connection Type Sweat Liquid Lin...

Page 7: ...unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop NOTE All wiring must conform to NEC and local codes NOTE Operating unit on improper lin...

Page 8: ...al power source Copper wire must be used from service disconnect to unit 2 All motors compressors contain internal overload protection 3 In compliance with NEC U S A Standard requirements for multi mo...

Page 9: ...Heater COMP Compressor Motor EQUIP Equipment GND Ground HPS High Pressure Switch LPS Low Pressure Switch OFM Outdoor Fan Motor OL Overload TB Terminal Board Splice Field Terminal Marked Terminal Unma...

Page 10: ...isconnect switch Lock out and tag switch with a suitable warning label Outdoor Fan A reinforced wire mount holds the outdoor fan assembly in position See Fig 7 for proper mounting position 38HDR Unit...

Page 11: ...before brazing The service valve cannot be field repaired therefore only a complete valve or valve stem seal and service port caps are available for replacement Refrigerant Charging WARNING PERSONAL...

Page 12: ...9 58 7 3 13 72 160 56 2 13 44 262 86 9 30 50 364 110 0 43 33 466 128 7 53 72 596 148 4 64 67 60 8 6 13 00 162 57 0 13 89 264 87 4 30 78 366 110 4 43 56 468 129 0 53 89 600 149 0 65 00 62 10 0 12 22 16...

Page 13: ...02 62 34 60 33 58 32 56 31 54 30 52 29 208 64 36 62 34 60 33 58 32 56 31 54 30 215 66 37 64 36 62 34 60 33 58 32 56 31 222 68 38 66 37 64 36 62 34 60 33 58 32 229 70 39 68 38 66 37 64 36 62 34 60 33 2...

Page 14: ...r conditions Inspect coil monthly and clean as required Fins are not continuous through coil sections Dirt and debris may pass through first section become trapped between the row of fins and restrict...

Reviews: