GUIDE SPECIFICATIONS

HORIZONTAL DISCHARGE OUTDOOR UNITS

Size Range: 3/4 and 1 Ton Nominal Cooling and Heating Capacity

Carrier Model Number:

38GXQ

PART 1 – GENERAL

1.01 System Description

A. Outdoor air-cooled split system compressor sections suitable

for on-the-ground, rooftop, wall hung or balcony mounting.

Units shall consist of a variable speed rotary compressor, an
air-cooled coil, propeller-type draw-through outdoor fan,
reversing valve, accumulator, metering devices, and control

box. Units shall discharge horizontally as shown on the
contract drawings. Units shall function as the outdoor

component of an air-to-air heat pump system.

B. Units shall be used in a refrigeration circuit matched to

duct-free heat pump fan coil units.

1.02 Agency Listings

C. Unit construction shall comply with ANSI/ASHRAE 15, latest

revision, and with NEC.

D. Units shall be evaluated in accordance with UL standard 1995.
E. Units shall be listed in CEC directory.
F. Unit cabinet shall be capable of withstanding 500-hour salt

spray test per Federal Test Standard no. 141 (method 6061).

G. Air-cooled condenser coils shall be leak tested at 573 psig.

1.03 Delivery, Storage, And Handling

Units shall be shipped in one piece and shall be stored and handled

per manufacturer s recommendations.

1.04 Warranty (For Inclusion By Specifying

Engineer)

PART 2 – PRODUCTS

2.01 Equipment

A. General:

Factory assembled, single piece, air-cooled outdoor unit. Contained

within the enclosure shall be all factory wiring, piping, controls,

and compressor.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of galvanized steel,

bonderized and coated with baked-enamel finish on inside
and outside.

2. Unit access panel should be removable with minimal screws

and shall provide full access to the compressor, fan, and
control components.

3. Outdoor compartment shall be isolated and have an acoustic

lining to assure quiet operation.

C. Fans:

1. Outdoor fans shall be direct-drive propeller type, and shall

discharge air horizontally. Fan shall draw air through the

outdoor coil.

2. Outdoor fan motors shall be totally-enclosed, single phase

motors with class B insulation and permanently- lubricated
ball bearings. Motor shall be protected by internal thermal
overload protection.

3. Shaft shall have inherent corrosion resistance.
4. Outdoor fan openings shall be equipped with PVC

metal/mesh coated protection grille over fan.

D. Compressor

1. Compressor shall be fully hermetic variable speed rotary

type.

2. Compressor shall be Three phase, inverter driven.
3. Compressor shall be equipped with oil system, operating oil

charge, and motor.

4. Motor shall be NEMA rated class F, suitable for operation

in refrigerant atmosphere.

5. Compressor assembly shall be installed on rubber vibration

isolators.

6. The inverter and compressor shall be protected against over

temperature and over current.

E. Outdoor Coil:

Coil shall be constructed of Aluminum fins mechanically bonded

to seamless copper tubes, which are cleaned, dehydrated and

sealed.

F. Refrigerant Components:

Refrigerant circuit components shall include brass external liquid

line service valve with service gauge port connections, suction line

service valve with service gage connection port, service gage port

connections on compressor suction and discharge lines with

Schrader type fittings with brass caps, accumulator, reversing

valve.

G. Safeties:

Operating safeties shall be factory selected, assembled, and tested.

The minimum functions shall include the following:

1. Compressor discharge over temperature protection.
2. System low voltage protection.
3. Compressor overload protection.
4. Compressor over current protection.
5. IPM module protection.

H. Electrical Requirements:

1. Units shall operate on single-phase, 60 Hz power at 115 v.

for unit sizes 009-012.

2. Unit electrical power shall be a single point connection.
3. All power and control wiring must be installed per NEC

and all local electrical codes.

4. Units shall have high and low-voltage terminal block

connections.

I. Special Features (Field Installed):

1. Crankcase heater
2. Wind baffle (field fabricated)

38/

40GX

Q

Summary of Contents for 38GXQ

Page 1: ...ounted on the wall near the ceiling This selection of fan coils permits inexpensive and creative solutions to design problems such as S Add ons to current space sun room S Special space requirements S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structur...

Page 2: ... the user and the unit SECURE OPERATION If security is an issue outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings In addition since the 38GXQ can be installed close to an outside wall coils are protected from vandals and severe weather FAST INSTALLATION This compact duct free split system is simple to i...

Page 3: ...XQ 1 01 009 Air Cooled Condenser Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton INDOOR UNIT 40 GXQ 1 01 009 Fan Coil Unit Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton 38 40GXQ ...

Page 4: ...1 year for parts and 5 years for compressor INDOOR UNITS A07892 Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump accessory is recommended when adequate drain line pitch cannot be provided or when the condensate must move up to exit The pump has a lift capability of 12 ft 3 6 m on the discharge side if the pump is mounted in the fan coil or 6 ft 1 8 m on the suction side i...

Page 5: ...bs Kg 9k 30 3 770 9 8 250 7 84 1 99 18 7 8 5 12k 32 7 830 11 2 285 8 9 225 24 2 11 Fig 2 Dimensions of Indoor Unit DIMENSIONS OUTDOOR W D H A08290 Unit Size W In mm D In mm H In mm Net Operating Weight Lbs Kg 9k 12k 33 4 848 12 6 320 21 3 540 88 40 Fig 3 Dimensions of Outdoor Unit 38 40GXQ ...

Page 6: ...5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR A07891 Fig 4 Indoor unit clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 UNIT 12k in mm A 20 508 B 20 508 C 24 610 D 12 305 E 12 305 Fig 5 Outdoor Unit Clearance 38 40GXQ ...

Page 7: ...lse DC Rated Cooling Capacity Btuh 12 000 Rated Heating Capacity Btuh 11 200 Operating Weight lb kg Refrigerant Type R 410A Metering Device Capillary Tube at Outdoor Unit Moisture Removal Rate pints hr Indoor Fan RPM CFM High 1200 290 1350 315 RPM CFM Medium 1060 245 1200 268 RPM CFM Low 700 224 1100 245 Motor Watts 13 20 Blower Quantity Size in 1 3 8 x 23 1 3 6 x 24 3 Indoor Coil Face Area sq ft ...

Page 8: ... 7 Indoor Temp 80 67_F 26 7 19 4_C db wb Indoor Fan High Speed D Rating Point A09176 Fig 6 38GXQ009 40GXQ009 Cooling 0 20 40 60 80 100 120 17 15 8 3 9 4 35 33 1 7 0 6 45 43 7 2 6 1 62 57 16 7 13 9 Capacity Ratio Outdoor Temperature F C DB WB Indoor temperature 75_F 23 4_C db Indoor Fan High Speed D Rating Point A09178 Fig 7 38GXQ009 40GXQ009 Heating 0 20 40 60 80 100 120 140 Capacity Ratio Outdoor...

Page 9: ...l environmental conditions SYSTEM OPERATING CONDITIONS Cooling operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 115 46 1 55 12 78 Indoor Unit 95 35 55 12 78 Heating operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 75 23 9 14 10 Indoor Unit 80 26 7 55 12 78 METERING DEVICES These units have capillary tube metering devices in the outdoo...

Page 10: ... not take place of a dehumidifier In addition to the above modes that are selected by using the remote control the unit can run in emergency mode by using a manual button This mode is used when the remote is misplaced or the batteries in the remote died In this mode the unit will run in AUTO mode with a predetermined set point 76_F 24 4_C For more details on the sequence of operation please refer ...

Page 11: ...0 42 29 31 40GXQ012 1 55 54 44 43 51 51 40 40 48 50 37 39 NOTES 1 Sound power ratings are per ARI 270 and ARI 350 2 Sound pressure ratings are estimated sound pressure 3 feet 91 m from the unit based on sound power data ELECTRICAL DATA UNIT SIZE SYSTEM VOLTAGE OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP VOLTS PH HZ MAX MIN RLA LRA FLA HP W VOLTS FLA HP W 009 115 1 60 12...

Page 12: ... propeller type and shall discharge air horizontally Fan shall draw air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class B insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Outdoor fan openings shall be equipped with PVC metal m...

Page 13: ...stics The temperature control range shall be from 62_F to 84_F 16 7_C to 28 9_C The unit shall have the following functions as a minimum 1 Automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing control to enter set points and operating conditions 4 Wireless inf...

Page 14: ...0 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40GX 1PD Replaces New Printed in U S A Edition Date 03 09 38 40GXQ ...

Reviews: