GUIDE SPECIFICATIONS

INDOOR WALL--MOUNTED DUCT--FREE UNITS

Size Range: 3/4 and 1 Ton Nominal Cooling and Heating Capacity

Carrier Model Number:

40GXQ

PART 1 – GENERAL

1.01 System Description

Indoor, wall-mounted, direct expansion fan coils are matched with

heat pump outdoor units.

1.02 Agency Listings

Unit shall be rated per ARI Standards 210/240 and listed in the

ARI directory as a matched system.

1.03 Delivery, Storage, And Handling

Units shall be shipped in one piece and shall be stored and handled

per manufacturer s recommendations.

1.04 Warranty (For Inclusion By Specifying

Engineer)

PART 2 – PRODUCTS

2.01 Equipment

A. General:

Indoor, direct-expansion, wall-mounted fan coil. Unit shall be

complete with cooling/heating coil, fan, fan motor, piping

connectors, electrical controls, microprocessor control system, and

integral temperature sensing. Unit shall be furnished with integral

wall mounting bracket and mounting hardware.

B. Unit Cabinet:

Cabinet discharge and inlet grilles shall be attractively styled,

high-impact polystyrene. Cabinet shall be fully insulated for

improved thermal acoustic performance.

C. Fans:

1. Fan shall be tangential direct-drive blower type with air

intake at the top of the unit and discharge at the bottom
front. Automatic, motor-driven vertical air sweep shall be

provided standard.

2. Air sweep operation shall be useable selectable. The vertical

sweep may be adjusted (using the remote control) and the

horizontal air direction maybe be set manually.

D. Coil:

Coil shall be copper tube with aluminum fins and galvanized steel

tube sheets. Fins shall be bonded to the tubes by mechanical

expansion. A drip pan under the coil shall have a drain connection

for hose attachment to remove condensate. Condensate pan shall

have internal trap.

E. Motors:

Motors shall be open drip-proof, permanently lubricated ball

bearing with inherent overload protection. Fan motors shall be

3-speed.

F. Controls:

Controls shall consist of a microprocessor-based control system

which shall control space temperature, determine optimum fan

speed, and run self diagnostics. The temperature control range shall

be from 62

_

F to 84

_

F (16.7

_

C to 28.9

_

C).

The unit shall have the following functions as a minimum:

1. Automatic restart after power failure at the same operating

conditions as at failure.

2. A timer function to provide a minimum 24-hour timer cycle

for system Auto Start/Stop.

3. Temperature sensing control to enter set points and

operating conditions.

4. Wireless infrared remote control to enter set points and

operating conditions.

5. Automatic air sweep control to provide on or off activation

of air sweep louvers.

6. Dehumidification mode shall provide increased latent

removal capability by modulating system operation and set
point temperature.

7. Fan-only operation to provide room air circulation when no

cooling is required.

8. Diagnostics shall provide continuous checks of unit

operation and warn of possible malfunctions. Error
messages shall be displayed at the unit.

9. Fan speed control shall be user-selectable: high, medium,

low or microprocessor controlled automatic operation

during all operating modes.

The unit shall be protected against the following:

1. Indoor coil freeze up
2. Indoor coil high temperature protection shall be provided to

detect excessive indoor discharge temperature when unit is
in heat pump mode.

G. Filters:

Units shall have filter track with factory-supplied cleanable filters.

H. Electrical Requirements:

Indoor fan motor to operate 115 volts on sizes 009-012. Power is

supplied from the indoor unit.

I. Operating Characteristics:

The 40GXQ system shall have a minimum listed SEER (seasonal

energy efficiency ratio) of 16 SEER at ARI conditions, and a

minimum HSPF of 7.7.

J. Refrigerant Lines:

All units should have refrigerant line connections that can be

oriented to connect from the left, right, or back of unit. Both

refrigerant lines need to be insulated.

K. Special Features (Field Installed):

1. Condensate Pump: The condensate pump shall remove

condensate from the drain pan when gravity drainage

cannot be used. Pump shall be designed for quiet operation.
Pump shall consist of two parts: an internal reservoir/sensor
assembly, and a remote sound-shielded pump assembly. A

liquid level sensor in the reservoir shall stop cooling
operation if the liquid level in the reservoir is unacceptable.

38/

40GX

Q

Summary of Contents for 38GXQ

Page 1: ...ounted on the wall near the ceiling This selection of fan coils permits inexpensive and creative solutions to design problems such as S Add ons to current space sun room S Special space requirements S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structur...

Page 2: ... the user and the unit SECURE OPERATION If security is an issue outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings In addition since the 38GXQ can be installed close to an outside wall coils are protected from vandals and severe weather FAST INSTALLATION This compact duct free split system is simple to i...

Page 3: ...XQ 1 01 009 Air Cooled Condenser Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton INDOOR UNIT 40 GXQ 1 01 009 Fan Coil Unit Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton 38 40GXQ ...

Page 4: ...1 year for parts and 5 years for compressor INDOOR UNITS A07892 Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump accessory is recommended when adequate drain line pitch cannot be provided or when the condensate must move up to exit The pump has a lift capability of 12 ft 3 6 m on the discharge side if the pump is mounted in the fan coil or 6 ft 1 8 m on the suction side i...

Page 5: ...bs Kg 9k 30 3 770 9 8 250 7 84 1 99 18 7 8 5 12k 32 7 830 11 2 285 8 9 225 24 2 11 Fig 2 Dimensions of Indoor Unit DIMENSIONS OUTDOOR W D H A08290 Unit Size W In mm D In mm H In mm Net Operating Weight Lbs Kg 9k 12k 33 4 848 12 6 320 21 3 540 88 40 Fig 3 Dimensions of Outdoor Unit 38 40GXQ ...

Page 6: ...5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR A07891 Fig 4 Indoor unit clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 UNIT 12k in mm A 20 508 B 20 508 C 24 610 D 12 305 E 12 305 Fig 5 Outdoor Unit Clearance 38 40GXQ ...

Page 7: ...lse DC Rated Cooling Capacity Btuh 12 000 Rated Heating Capacity Btuh 11 200 Operating Weight lb kg Refrigerant Type R 410A Metering Device Capillary Tube at Outdoor Unit Moisture Removal Rate pints hr Indoor Fan RPM CFM High 1200 290 1350 315 RPM CFM Medium 1060 245 1200 268 RPM CFM Low 700 224 1100 245 Motor Watts 13 20 Blower Quantity Size in 1 3 8 x 23 1 3 6 x 24 3 Indoor Coil Face Area sq ft ...

Page 8: ... 7 Indoor Temp 80 67_F 26 7 19 4_C db wb Indoor Fan High Speed D Rating Point A09176 Fig 6 38GXQ009 40GXQ009 Cooling 0 20 40 60 80 100 120 17 15 8 3 9 4 35 33 1 7 0 6 45 43 7 2 6 1 62 57 16 7 13 9 Capacity Ratio Outdoor Temperature F C DB WB Indoor temperature 75_F 23 4_C db Indoor Fan High Speed D Rating Point A09178 Fig 7 38GXQ009 40GXQ009 Heating 0 20 40 60 80 100 120 140 Capacity Ratio Outdoor...

Page 9: ...l environmental conditions SYSTEM OPERATING CONDITIONS Cooling operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 115 46 1 55 12 78 Indoor Unit 95 35 55 12 78 Heating operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 75 23 9 14 10 Indoor Unit 80 26 7 55 12 78 METERING DEVICES These units have capillary tube metering devices in the outdoo...

Page 10: ... not take place of a dehumidifier In addition to the above modes that are selected by using the remote control the unit can run in emergency mode by using a manual button This mode is used when the remote is misplaced or the batteries in the remote died In this mode the unit will run in AUTO mode with a predetermined set point 76_F 24 4_C For more details on the sequence of operation please refer ...

Page 11: ...0 42 29 31 40GXQ012 1 55 54 44 43 51 51 40 40 48 50 37 39 NOTES 1 Sound power ratings are per ARI 270 and ARI 350 2 Sound pressure ratings are estimated sound pressure 3 feet 91 m from the unit based on sound power data ELECTRICAL DATA UNIT SIZE SYSTEM VOLTAGE OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP VOLTS PH HZ MAX MIN RLA LRA FLA HP W VOLTS FLA HP W 009 115 1 60 12...

Page 12: ... propeller type and shall discharge air horizontally Fan shall draw air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class B insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Outdoor fan openings shall be equipped with PVC metal m...

Page 13: ...stics The temperature control range shall be from 62_F to 84_F 16 7_C to 28 9_C The unit shall have the following functions as a minimum 1 Automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing control to enter set points and operating conditions 4 Wireless inf...