background image

10

DRAIN CONNECTIONS

Install drains to meet the local sanitation codes. If adequate gravity

drainage cannot be provided, a field installed condensate pump

accessory should be used. The pump has a lift capability of 12 ft

(3.6 m) on the discharge side if the pump is mounted in the fan coil

or 6 ft (1.8 m) on the suction side if the pump is remote mounted.

See the Physical Data tables for drain sizes.

NOTE

: The high wall fan coils have internal condensate trap. An

external trap is not required.
Drain connections may be routed through alternate locations as

shown in Fig. 11.

Pipe holder

Pipe cover

Right piping

Left piping

Pipe cover

Right back piping

Left back piping

1

2

3

4

A09112

Fig. 11 – Piping Locations

WIRING

The main power is supplied to the outdoor unit. The field supplied

connecting cable from the outdoor unit to the indoor consists of 4

wires and provides the power for the indoor unit as well the

communication signal and ground between the outdoor unit and

indoor unit.

CONTROL SYSTEM

The 40GXQ/38GXQ unit is equipped with a microprocessor

controls to operate the system and give optimum levels of comfort

and operating efficiency.
There are microprocessor boards and thermistors located in both

the indoor and outdoor units. The thermistors monitor the system

operation and control the operating mode. The change in the

settings or the modes of operation, use the factory supplied

wireless remote control.
The 40GXQ/38GXQ unit has 5 operating modes:

S

Fan Only

S

Auto

S

Heating

S

Cooling

S

Dehumidification (Dry)

FAN ONLY

-- In Fan Only mode, the system filters and circulates

the room air without changing the room air temperature.

AUTO

-- In Auto mode, the system will automatically select one of

the following operating modes: cooling, heating or fan only based

on the difference between the room temperature and the set point

temperature.

HEATING

-- In the Heating mode, the system heats and filters

room air.

COOLING

-- When in Cooling mode, the fan runs all the time and

the system cools, dries and filters room air.

DEHUMIDIFICATION (DRY)

-- in Dehumidification (Dry)

mode, the system dries, filters and slightly cools room temperature.

This mode does not take place of a dehumidifier.
In addition to the above modes that are selected by using the

remote control, the unit can run in emergency mode by using a

manual button. This mode is used when the remote is misplaced or

the batteries in the remote died. In this mode the unit will run in

AUTO mode with a predetermined set point (76

_

F/24.4

_

C)

For more details on the sequence of operation please refer to the

service manual for those units.

WIRELESS REMOTE CONTROL

1. A wireless remote control is supplied for system operation.
2. Each battery--operated wireless remote control may be used

to control more than one unit.

3. The wireless remote control has a range of 25 ft. (7.6 m).

START--UP SEQUENCE

In both cooling and heating mode, the compressor does a soft start

from 0 Hz run speed approximately 52 Hz run speed. The event

takes about 55 seconds. This eliminates high in rush currents

associated with fixed speed compressors and also reduces the stress

on internal compressor parts typically seen with a full speed

startup.

COOLING MODE

In Cooling mode, the first step in compressor speed after the soft

start is a run speed of approximately 52 Hz for 150 seconds. The

next step is a ramp up to approximately 78 Hz.
If, within 20 minutes, the load is satisfied at 78 Hz, the compressor

will start to ramp back down in speed in an effort to track the load.

If the load is not satisfied within 20 minutes, the compressor speed

will ramp up to approximately 85 Hz. The compressor will operate

at this speed until the load is satisfied or a maximum of 20 minutes

after which the compressor will shut off for 3 minutes.
After 3 minutes the cycle repeats itself until the load is satisfied.

HEATING MODE

In Heating mode, the first step in compressor speed after the soft

start is a run speed of approximately 52 Hz for 150 seconds. The

next step is a ramp up to approximately 72 Hz.
If, within 25 minutes, the load is satisfied at 72 Hz, the compressor

will start to ramp back down in speed in an effort to track the load.

If the load is not satisfied within 25 minutes, the compressor speed

will ramp up to approximately 82 Hz.
The compressor will operate at this speed until the load is satisfied

or a maximum of 18 minutes after which the compressor will shut

off for 3 minutes.
After 3 minutes the cycle repeats itself until the load is satisfied.

38/

40GX

Q

Summary of Contents for 38GXQ

Page 1: ...ounted on the wall near the ceiling This selection of fan coils permits inexpensive and creative solutions to design problems such as S Add ons to current space sun room S Special space requirements S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structur...

Page 2: ... the user and the unit SECURE OPERATION If security is an issue outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings In addition since the 38GXQ can be installed close to an outside wall coils are protected from vandals and severe weather FAST INSTALLATION This compact duct free split system is simple to i...

Page 3: ...XQ 1 01 009 Air Cooled Condenser Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton INDOOR UNIT 40 GXQ 1 01 009 Fan Coil Unit Unit Type GXQ Heat Pump Voltage 1 115 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton 38 40GXQ ...

Page 4: ...1 year for parts and 5 years for compressor INDOOR UNITS A07892 Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump accessory is recommended when adequate drain line pitch cannot be provided or when the condensate must move up to exit The pump has a lift capability of 12 ft 3 6 m on the discharge side if the pump is mounted in the fan coil or 6 ft 1 8 m on the suction side i...

Page 5: ...bs Kg 9k 30 3 770 9 8 250 7 84 1 99 18 7 8 5 12k 32 7 830 11 2 285 8 9 225 24 2 11 Fig 2 Dimensions of Indoor Unit DIMENSIONS OUTDOOR W D H A08290 Unit Size W In mm D In mm H In mm Net Operating Weight Lbs Kg 9k 12k 33 4 848 12 6 320 21 3 540 88 40 Fig 3 Dimensions of Outdoor Unit 38 40GXQ ...

Page 6: ...5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR A07891 Fig 4 Indoor unit clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 UNIT 12k in mm A 20 508 B 20 508 C 24 610 D 12 305 E 12 305 Fig 5 Outdoor Unit Clearance 38 40GXQ ...

Page 7: ...lse DC Rated Cooling Capacity Btuh 12 000 Rated Heating Capacity Btuh 11 200 Operating Weight lb kg Refrigerant Type R 410A Metering Device Capillary Tube at Outdoor Unit Moisture Removal Rate pints hr Indoor Fan RPM CFM High 1200 290 1350 315 RPM CFM Medium 1060 245 1200 268 RPM CFM Low 700 224 1100 245 Motor Watts 13 20 Blower Quantity Size in 1 3 8 x 23 1 3 6 x 24 3 Indoor Coil Face Area sq ft ...

Page 8: ... 7 Indoor Temp 80 67_F 26 7 19 4_C db wb Indoor Fan High Speed D Rating Point A09176 Fig 6 38GXQ009 40GXQ009 Cooling 0 20 40 60 80 100 120 17 15 8 3 9 4 35 33 1 7 0 6 45 43 7 2 6 1 62 57 16 7 13 9 Capacity Ratio Outdoor Temperature F C DB WB Indoor temperature 75_F 23 4_C db Indoor Fan High Speed D Rating Point A09178 Fig 7 38GXQ009 40GXQ009 Heating 0 20 40 60 80 100 120 140 Capacity Ratio Outdoor...

Page 9: ...l environmental conditions SYSTEM OPERATING CONDITIONS Cooling operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 115 46 1 55 12 78 Indoor Unit 95 35 55 12 78 Heating operating range Maximum Minimum DB _F _C WB _F _C DB _F _C WB _F _C Outdoor Unit 75 23 9 14 10 Indoor Unit 80 26 7 55 12 78 METERING DEVICES These units have capillary tube metering devices in the outdoo...

Page 10: ... not take place of a dehumidifier In addition to the above modes that are selected by using the remote control the unit can run in emergency mode by using a manual button This mode is used when the remote is misplaced or the batteries in the remote died In this mode the unit will run in AUTO mode with a predetermined set point 76_F 24 4_C For more details on the sequence of operation please refer ...

Page 11: ...0 42 29 31 40GXQ012 1 55 54 44 43 51 51 40 40 48 50 37 39 NOTES 1 Sound power ratings are per ARI 270 and ARI 350 2 Sound pressure ratings are estimated sound pressure 3 feet 91 m from the unit based on sound power data ELECTRICAL DATA UNIT SIZE SYSTEM VOLTAGE OPERATING VOLTAGE COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP VOLTS PH HZ MAX MIN RLA LRA FLA HP W VOLTS FLA HP W 009 115 1 60 12...

Page 12: ... propeller type and shall discharge air horizontally Fan shall draw air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class B insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Outdoor fan openings shall be equipped with PVC metal m...

Page 13: ...stics The temperature control range shall be from 62_F to 84_F 16 7_C to 28 9_C The unit shall have the following functions as a minimum 1 Automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing control to enter set points and operating conditions 4 Wireless inf...

Page 14: ...0 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40GX 1PD Replaces New Printed in U S A Edition Date 03 09 38 40GXQ ...

Reviews: