System Design

1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).
4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).
5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft/indoor coil below = 150 ft (see items 8 and 9 following).
8. For interconnecting refrigerant tube lengths greater than 50 ft and/or elevation differences between indoor and outdoor units greater than 20 ft, consult Residential Split-

System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron refrigerant.

9. If ANY refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be buried without 

further considerations. Buried refrigerant tubing lengths greater than 36 in. are not recommended.

10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity (unless so specified) may result in inadequate indoor comfort.
12. Do not apply capillary tube indoor coils to these units.
13. Factory-supplied filter drier must be installed.

Summary of Contents for 38EYA

Page 1: ...n thanks to the performance advantage of Puron the 38EYA is extremely efficient with ratings from 12 to 14 SEER Maximum performance and efficiency are made possible through the use of the FX4A and FV4...

Page 2: ...service reversing valve Thermostatic Expansion Valve TXV The 38EYA Heat Pump must be installed with a Puron TXV on the indoor coil The FX4 and FV4 indoor fan coils are factory equipped with a bi flow...

Page 3: ...8 3 8 5 8 3 4 ACR 3 4 030 3 8 3 8 3 4 7 8 1 1 8 036 3 8 3 8 3 4 7 8 1 1 8 042 048 3 8 3 8 7 8 7 8 3 4 and 1 1 8 060 3 8 3 8 1 1 8 7 8 3 4 RST Refrigeration Service Tubing standard refrigerant grade tu...

Page 4: ...Flow TXV Hard Shutoff Size 024 030 KSATX0301HSZ Bi Flow TXV Hard Shutoff Sizes 036 042 KSATX0401HSZ Bi Flow TXV Hard Shutoff Size 048 KSATX0501HSZ Bi Flow TXV Hard Shutoff Size 060 KH45LG140 RCD Filt...

Page 5: ...mp and gas or oil fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat Control is used 9 Isolation Relay An SPDT relay which switches the Low Ambient Controller out of the out...

Page 6: ...pacity of nonmetallic sheathed cable NM trade name ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Article 336 26 If other than uncoated non plated 60 or 75 C 140 or 167 F insula...

Page 7: ...Minimum outdoor operating ambient in cooling mode is 55 F 2 NOTES unless low ambient control is used max 125 F DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E...

Page 8: ...BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38EYA024 301 FX4A030 38EYA036 301 FX4ANF036 38EYA048 301 FX4A048 KW 38EYA060 301 FX4ANF060 NOTE The performance s...

Page 9: ...TDR 13 50 11 35 29 000 3 52 17 800 2 42 8 00 F A B 4AN F C 036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FC4BNF036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FG3AAA036 28 000 NONE 11...

Page 10: ...35 000 3 56 22 200 2 54 8 00 COILS 58U H X V100 20 VARIABLE SPEED FURNACE CC5A CD5AA042 33 400 TDR 13 50 11 30 35 000 3 44 21 800 2 50 7 80 CC5A CD5AA048 33 800 TDR 13 50 11 25 35 000 3 48 22 000 2 5...

Page 11: ...8 20 FC4BN F B 060 44 000 TDR 11 50 9 75 47 000 3 44 29 800 2 40 8 00 FC4BNB070 45 000 TDR 12 00 10 25 47 000 3 62 29 400 2 50 8 20 FG3AAA060 43 500 NONE 12 00 10 15 46 000 3 38 29 000 2 42 8 00 FV4A...

Page 12: ...22 TXV with Puron TXV UNIT SIZE SERIES INDOOR UNIT ARI STANDARD RATINGS Cooling Heating TC Seasonal Efficiency SEER EER High Temp Low Temp HSPF Factory Supplied Enhance ment Standard Rating Field Supp...

Page 13: ...5 2 20 22 2 21 9 2 44 20 9 20 9 2 71 19 7 19 7 3 00 18 2 18 2 3 30 57 24 1 24 1 1 97 23 1 23 1 2 20 22 1 22 1 2 44 20 9 20 9 2 71 19 6 19 6 3 00 18 2 18 2 3 30 950 72 29 7 15 7 2 04 28 1 15 1 2 27 26...

Page 14: ...2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 57 28 8 28 8 2 24 27 6 27 6 2 48 26 2 26 2 2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 1200 72 34 6 18 9 2 34 32 8 18 3 2 57 30 9 17 7 2 82 28 9...

Page 15: ...8 25 8 4 57 63 36 1 29 6 2 78 34 1 28 8 3 08 32 1 27 9 3 41 29 9 27 0 3 76 27 5 25 9 4 14 24 9 24 5 4 55 62 36 3 36 3 2 78 34 6 34 6 3 08 32 9 32 9 3 41 31 0 31 0 3 77 28 9 28 9 4 16 26 5 26 5 4 57 5...

Page 16: ...1575 72 49 7 26 3 3 24 47 1 25 5 3 60 44 5 24 6 4 00 41 7 23 6 4 44 38 6 22 6 4 93 35 0 21 5 5 44 67 45 6 34 7 3 21 43 3 33 8 3 57 40 9 32 9 3 97 38 3 31 8 4 41 35 4 30 7 4 89 32 2 29 4 5 40 63 42 6...

Page 17: ...50 40 4 40 4 4 99 37 9 37 9 5 54 35 0 35 0 6 13 1800 72 55 9 30 2 3 85 52 9 29 2 4 24 49 9 28 2 4 68 46 6 27 1 5 17 43 1 26 0 5 70 39 1 24 7 6 28 67 51 3 40 1 3 80 48 6 39 0 4 19 45 8 38 0 4 63 42 9...

Page 18: ...8 39 0 6 97 45 4 37 3 7 68 63 59 1 43 2 4 62 56 2 41 9 5 12 53 2 40 6 5 66 50 0 39 2 6 27 46 5 37 7 6 93 42 5 36 0 7 63 62 58 2 53 8 4 61 55 4 52 4 5 11 52 5 51 0 5 65 49 4 49 3 6 26 46 5 46 5 6 93 4...

Page 19: ...2 2 37 950 10 8 9 97 2 06 13 1 12 0 2 05 15 6 14 2 2 07 18 4 16 3 2 11 21 7 19 7 2 16 25 4 25 4 2 23 26 5 26 5 2 31 27 6 27 6 2 32 75 700 10 5 9 64 2 07 12 6 11 6 2 10 15 0 13 7 2 16 17 7 15 7 2 23 20...

Page 20: ...0 2 58 33 1 33 1 2 56 35 4 35 4 2 61 1200 13 2 12 2 2 37 15 9 14 6 2 38 19 0 17 3 2 40 22 4 19 9 2 45 26 2 23 8 2 51 30 4 30 4 2 58 33 6 33 6 2 54 35 5 35 5 2 55 75 900 13 1 12 1 2 35 15 3 14 1 2 40 1...

Page 21: ...4 0 3 04 31 5 28 7 3 16 36 5 36 5 3 29 35 8 35 8 3 21 34 3 34 3 3 10 1500 16 5 15 2 2 90 19 7 18 1 2 94 23 4 21 3 3 01 27 5 24 5 3 09 32 1 29 2 3 19 37 2 37 2 3 30 36 5 36 5 3 21 35 0 35 0 3 09 Indoor...

Page 22: ...19 4 17 8 3 46 23 0 21 1 3 43 26 9 24 6 3 40 31 1 27 6 3 37 35 7 32 5 3 35 40 8 40 8 3 32 44 5 44 5 4 05 42 3 42 3 3 87 1400 19 9 18 3 3 53 23 3 21 4 3 47 27 3 24 9 3 42 31 6 28 0 3 37 36 3 33 0 3 33...

Page 23: ...7 4 11 57 3 57 3 4 23 75 1400 20 4 18 8 3 46 24 3 22 3 3 53 28 8 26 2 3 64 33 7 29 9 3 78 39 3 35 8 3 94 45 6 45 6 4 13 50 2 50 2 4 35 54 2 54 2 4 51 1600 20 7 19 1 3 55 24 7 22 7 3 59 29 2 26 6 3 68...

Page 24: ...60 8 5 01 58 8 58 8 5 02 58 6 58 6 4 95 2000 26 6 24 5 4 22 32 6 29 9 4 37 38 7 35 2 4 48 45 4 40 4 4 62 53 1 48 3 4 79 61 7 61 7 4 98 59 8 59 8 4 97 59 6 59 6 4 88 2250 27 0 24 8 4 29 33 0 30 3 4 48...

Page 25: ...onnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Residential Split System Application Guideline and Servic...

Page 26: ...26...

Page 27: ...27...

Page 28: ...art up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Co...