Carrier 38EYA Product Data Download Page 28

Carrier Corporation 

 Indianapolis, IN 46231

3-00

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

Page 28

Catalog No. 523-776

Printed in U.S.A.

PC 101

Form 38EYA-1PD

Tab

5a 5a

Replaces: NEW

Guide specifications

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system heat pump unit 

suitable for ground or rooftop installation. Unit consists of a 
hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil or 
coil unit.
Quality Assurance

Unit will be rated in accordance with the latest edition of 

ARI Standard 240.

Unit will be certified for capacity and efficiency, and listed 

in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have C-UL 
approval.

Unit cabinet will be capable of withstanding Federal Test 

Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.

Air-cooled condenser coils will be leak tested at 217 psig 

and pressure tested at 450 psig.
Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled heat pump unit. 

Contained within the unit enclosure will be all factory wiring, 
piping, controls, compressor, refrigerant charge (Puron®), and 
special features required prior to field start-up.
Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.
Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type 

with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire 

safety guards.
Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 

bonded to copper tubes which are then cleaned, dehydrated, 
and sealed.
Refrigeration Components

Refrigeration circuit components will include liquid tube 

shutoff valve with sweat connections, suction tube shutoff 
valves with sweat connections, system charge of Puron® 
refrigerant, POE compressor oil, accumulator, and reversing 
valve.
Operating Characteristics

The capacity of the unit will meet or exceed 

 Btuh at a 

suction temperature of 

 °F. The power consumption at 

full load will not exceed 

 kw.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of 

 Btuh or greater 

at conditions of 

 CFM entering air temperature at the 

evaporator at 

 °F wet bulb and 

 °F dry bulb, and air 

entering the unit at 

 °F.

The system will have an SEER of 

 Btuh/watt or greater 

at DOE conditions.
Electrical Requirements

Nominal unit electrical characteristics will be 

 v,

 phase, 60 hertz. The unit will be capable of satisfactory 

operation within voltage limits of 

 v to 

 v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and 

descriptions for specific features and available enhancements.

Air-Cooled, Split-System

Heat Pump

38EYA

2 to 5 Tons Nominal

Summary of Contents for 38EYA

Page 1: ...n thanks to the performance advantage of Puron the 38EYA is extremely efficient with ratings from 12 to 14 SEER Maximum performance and efficiency are made possible through the use of the FX4A and FV4...

Page 2: ...service reversing valve Thermostatic Expansion Valve TXV The 38EYA Heat Pump must be installed with a Puron TXV on the indoor coil The FX4 and FV4 indoor fan coils are factory equipped with a bi flow...

Page 3: ...8 3 8 5 8 3 4 ACR 3 4 030 3 8 3 8 3 4 7 8 1 1 8 036 3 8 3 8 3 4 7 8 1 1 8 042 048 3 8 3 8 7 8 7 8 3 4 and 1 1 8 060 3 8 3 8 1 1 8 7 8 3 4 RST Refrigeration Service Tubing standard refrigerant grade tu...

Page 4: ...Flow TXV Hard Shutoff Size 024 030 KSATX0301HSZ Bi Flow TXV Hard Shutoff Sizes 036 042 KSATX0401HSZ Bi Flow TXV Hard Shutoff Size 048 KSATX0501HSZ Bi Flow TXV Hard Shutoff Size 060 KH45LG140 RCD Filt...

Page 5: ...mp and gas or oil fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat Control is used 9 Isolation Relay An SPDT relay which switches the Low Ambient Controller out of the out...

Page 6: ...pacity of nonmetallic sheathed cable NM trade name ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Article 336 26 If other than uncoated non plated 60 or 75 C 140 or 167 F insula...

Page 7: ...Minimum outdoor operating ambient in cooling mode is 55 F 2 NOTES unless low ambient control is used max 125 F DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E...

Page 8: ...BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38EYA024 301 FX4A030 38EYA036 301 FX4ANF036 38EYA048 301 FX4A048 KW 38EYA060 301 FX4ANF060 NOTE The performance s...

Page 9: ...TDR 13 50 11 35 29 000 3 52 17 800 2 42 8 00 F A B 4AN F C 036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FC4BNF036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FG3AAA036 28 000 NONE 11...

Page 10: ...35 000 3 56 22 200 2 54 8 00 COILS 58U H X V100 20 VARIABLE SPEED FURNACE CC5A CD5AA042 33 400 TDR 13 50 11 30 35 000 3 44 21 800 2 50 7 80 CC5A CD5AA048 33 800 TDR 13 50 11 25 35 000 3 48 22 000 2 5...

Page 11: ...8 20 FC4BN F B 060 44 000 TDR 11 50 9 75 47 000 3 44 29 800 2 40 8 00 FC4BNB070 45 000 TDR 12 00 10 25 47 000 3 62 29 400 2 50 8 20 FG3AAA060 43 500 NONE 12 00 10 15 46 000 3 38 29 000 2 42 8 00 FV4A...

Page 12: ...22 TXV with Puron TXV UNIT SIZE SERIES INDOOR UNIT ARI STANDARD RATINGS Cooling Heating TC Seasonal Efficiency SEER EER High Temp Low Temp HSPF Factory Supplied Enhance ment Standard Rating Field Supp...

Page 13: ...5 2 20 22 2 21 9 2 44 20 9 20 9 2 71 19 7 19 7 3 00 18 2 18 2 3 30 57 24 1 24 1 1 97 23 1 23 1 2 20 22 1 22 1 2 44 20 9 20 9 2 71 19 6 19 6 3 00 18 2 18 2 3 30 950 72 29 7 15 7 2 04 28 1 15 1 2 27 26...

Page 14: ...2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 57 28 8 28 8 2 24 27 6 27 6 2 48 26 2 26 2 2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 1200 72 34 6 18 9 2 34 32 8 18 3 2 57 30 9 17 7 2 82 28 9...

Page 15: ...8 25 8 4 57 63 36 1 29 6 2 78 34 1 28 8 3 08 32 1 27 9 3 41 29 9 27 0 3 76 27 5 25 9 4 14 24 9 24 5 4 55 62 36 3 36 3 2 78 34 6 34 6 3 08 32 9 32 9 3 41 31 0 31 0 3 77 28 9 28 9 4 16 26 5 26 5 4 57 5...

Page 16: ...1575 72 49 7 26 3 3 24 47 1 25 5 3 60 44 5 24 6 4 00 41 7 23 6 4 44 38 6 22 6 4 93 35 0 21 5 5 44 67 45 6 34 7 3 21 43 3 33 8 3 57 40 9 32 9 3 97 38 3 31 8 4 41 35 4 30 7 4 89 32 2 29 4 5 40 63 42 6...

Page 17: ...50 40 4 40 4 4 99 37 9 37 9 5 54 35 0 35 0 6 13 1800 72 55 9 30 2 3 85 52 9 29 2 4 24 49 9 28 2 4 68 46 6 27 1 5 17 43 1 26 0 5 70 39 1 24 7 6 28 67 51 3 40 1 3 80 48 6 39 0 4 19 45 8 38 0 4 63 42 9...

Page 18: ...8 39 0 6 97 45 4 37 3 7 68 63 59 1 43 2 4 62 56 2 41 9 5 12 53 2 40 6 5 66 50 0 39 2 6 27 46 5 37 7 6 93 42 5 36 0 7 63 62 58 2 53 8 4 61 55 4 52 4 5 11 52 5 51 0 5 65 49 4 49 3 6 26 46 5 46 5 6 93 4...

Page 19: ...2 2 37 950 10 8 9 97 2 06 13 1 12 0 2 05 15 6 14 2 2 07 18 4 16 3 2 11 21 7 19 7 2 16 25 4 25 4 2 23 26 5 26 5 2 31 27 6 27 6 2 32 75 700 10 5 9 64 2 07 12 6 11 6 2 10 15 0 13 7 2 16 17 7 15 7 2 23 20...

Page 20: ...0 2 58 33 1 33 1 2 56 35 4 35 4 2 61 1200 13 2 12 2 2 37 15 9 14 6 2 38 19 0 17 3 2 40 22 4 19 9 2 45 26 2 23 8 2 51 30 4 30 4 2 58 33 6 33 6 2 54 35 5 35 5 2 55 75 900 13 1 12 1 2 35 15 3 14 1 2 40 1...

Page 21: ...4 0 3 04 31 5 28 7 3 16 36 5 36 5 3 29 35 8 35 8 3 21 34 3 34 3 3 10 1500 16 5 15 2 2 90 19 7 18 1 2 94 23 4 21 3 3 01 27 5 24 5 3 09 32 1 29 2 3 19 37 2 37 2 3 30 36 5 36 5 3 21 35 0 35 0 3 09 Indoor...

Page 22: ...19 4 17 8 3 46 23 0 21 1 3 43 26 9 24 6 3 40 31 1 27 6 3 37 35 7 32 5 3 35 40 8 40 8 3 32 44 5 44 5 4 05 42 3 42 3 3 87 1400 19 9 18 3 3 53 23 3 21 4 3 47 27 3 24 9 3 42 31 6 28 0 3 37 36 3 33 0 3 33...

Page 23: ...7 4 11 57 3 57 3 4 23 75 1400 20 4 18 8 3 46 24 3 22 3 3 53 28 8 26 2 3 64 33 7 29 9 3 78 39 3 35 8 3 94 45 6 45 6 4 13 50 2 50 2 4 35 54 2 54 2 4 51 1600 20 7 19 1 3 55 24 7 22 7 3 59 29 2 26 6 3 68...

Page 24: ...60 8 5 01 58 8 58 8 5 02 58 6 58 6 4 95 2000 26 6 24 5 4 22 32 6 29 9 4 37 38 7 35 2 4 48 45 4 40 4 4 62 53 1 48 3 4 79 61 7 61 7 4 98 59 8 59 8 4 97 59 6 59 6 4 88 2250 27 0 24 8 4 29 33 0 30 3 4 48...

Page 25: ...onnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Residential Split System Application Guideline and Servic...

Page 26: ...26...

Page 27: ...27...

Page 28: ...art up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Co...