Carrier 38EYA Product Data Download Page 5

 

5

 

Accessory usage guideline

 

* For tubing line sets between 50 and 175 ft and/or 20 ft elevation difference between indoor and outdoor units, refer to the Application Guideline and Service Man-

ual for Residential Split-System Air Conditioners and Heat Pumps using Puron Refrigerant.

† Required for all applications.

 

Accessory description and usage (Listed alphabetically)

 

1. Coastal Filter

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

SUGGESTED USE: In geographic areas where salt damage could occur.

 

2. Compressor Start Assist — Capacitor and Relay

 

Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.

SUGGESTED USE:

Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Units installed with Low-Ambient Pressure Switch.

 

3. Compressor Start Assist — PTC Type

 

Solid state electrical device which gives a “soft” boost to the reciprocating compressor at each start-up.

SUGGESTED USE:

Installations with marginal power supply.

 

4. Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance 
of refrigerant slugging. May or may not include a thermostat control.

SUGGESTED USE:

When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Pressure Switch.)
All commercial installations.

 

5. Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE:

All units to which Low-Ambient Pressure Switch has been added.

 

6. Filter Drier— Suction Line

 

A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps.

SUGGESTED USE:

Split-system heat pumps.

 

7. Inlet Grille Kit

 

A field-installed enhanced inlet grille to replace the standard inlet grille on residential air conditioners and heat pumps.

SUGGESTED USE:

For greater protection against inclement weather, incidental damage, and vandalism.

 

8. Interface Control (Optimizer II®)

 

An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance 
point temperature, then switches to allow furnace operation only below that temperature. KHAIC0101AAA requires outdoor thermostat (Item 11) to be adjusted for economic balance 
point temperature.

SUGGESTED USE:

For heat pump and gas- or oil-fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat™ Control is used.

 

9. Isolation Relay

 

An SPDT relay which switches the Low-Ambient Controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

SUGGESTED USE: All heat pumps where Low-Ambient Pressure Switch has been added.

 

10. Liquid-Line Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of 
refrigerant liquid ready for action at next compressor operation cycle.

SUGGESTED USE:

In long-line applications. (Refer to the Residential Split-System Long-Line Application Guideline and Service Manual.)

 

11. Low-Ambient Pressure Switch

 

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating 
limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed.

SUGGESTED USE:

Cooling operation at outdoor temperatures below 55°F (12.8°C).

 

12. Outdoor Air Temperature Sensor

 

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE:

All Carrier programmable thermostats.

 

13. Outdoor Thermostat

 

An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.

SUGGESTED USE:

Heat pump installations with multiple-stage supplemental heaters.

 

14. Secondary Outdoor Thermostat

 

An SPDT temperature actuated switch which turns on third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point.

SUGGESTED USE:

Heat pump installations where 3-stage operation of supplemental heaters is desired.

 

15. Service Alarm

 

A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper room thermostat, a 
thermostat signal is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental heaters only.

SUGGESTED USE:

As a feature to notify owner immediately when the system is not operating most efficiently.

 

ACCESSORY

REQUIRED FOR LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR LONG-LINE

APPLICATIONS*

(OVER 50 FT)

Crankcase Heater

 

Yes

Yes

Evaporator Freeze Thermostat

Yes

No

Compressor Start Assist — Capacitor and Relay

Yes

Yes

Puron Low Ambient Pressure Switch

Yes

No

Wind Baffle

See Low-Ambient

Pressure Switch Instructions

No

Support Feet

Recommended

No

Puron Hard Shutoff TXV

Yes†

Yes†

Puron Liquid-Line Solenoid Valve for Heating

No

See Long-Line

Application Guideline

Summary of Contents for 38EYA

Page 1: ...n thanks to the performance advantage of Puron the 38EYA is extremely efficient with ratings from 12 to 14 SEER Maximum performance and efficiency are made possible through the use of the FX4A and FV4...

Page 2: ...service reversing valve Thermostatic Expansion Valve TXV The 38EYA Heat Pump must be installed with a Puron TXV on the indoor coil The FX4 and FV4 indoor fan coils are factory equipped with a bi flow...

Page 3: ...8 3 8 5 8 3 4 ACR 3 4 030 3 8 3 8 3 4 7 8 1 1 8 036 3 8 3 8 3 4 7 8 1 1 8 042 048 3 8 3 8 7 8 7 8 3 4 and 1 1 8 060 3 8 3 8 1 1 8 7 8 3 4 RST Refrigeration Service Tubing standard refrigerant grade tu...

Page 4: ...Flow TXV Hard Shutoff Size 024 030 KSATX0301HSZ Bi Flow TXV Hard Shutoff Sizes 036 042 KSATX0401HSZ Bi Flow TXV Hard Shutoff Size 048 KSATX0501HSZ Bi Flow TXV Hard Shutoff Size 060 KH45LG140 RCD Filt...

Page 5: ...mp and gas or oil fired furnace combination systems unless Duel Fuel Thermostat or Thermidistat Control is used 9 Isolation Relay An SPDT relay which switches the Low Ambient Controller out of the out...

Page 6: ...pacity of nonmetallic sheathed cable NM trade name ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Article 336 26 If other than uncoated non plated 60 or 75 C 140 or 167 F insula...

Page 7: ...Minimum outdoor operating ambient in cooling mode is 55 F 2 NOTES unless low ambient control is used max 125 F DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E...

Page 8: ...BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38EYA024 301 FX4A030 38EYA036 301 FX4ANF036 38EYA048 301 FX4A048 KW 38EYA060 301 FX4ANF060 NOTE The performance s...

Page 9: ...TDR 13 50 11 35 29 000 3 52 17 800 2 42 8 00 F A B 4AN F C 036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FC4BNF036 28 000 TDR 11 50 9 90 30 000 3 30 18 900 2 26 7 50 FG3AAA036 28 000 NONE 11...

Page 10: ...35 000 3 56 22 200 2 54 8 00 COILS 58U H X V100 20 VARIABLE SPEED FURNACE CC5A CD5AA042 33 400 TDR 13 50 11 30 35 000 3 44 21 800 2 50 7 80 CC5A CD5AA048 33 800 TDR 13 50 11 25 35 000 3 48 22 000 2 5...

Page 11: ...8 20 FC4BN F B 060 44 000 TDR 11 50 9 75 47 000 3 44 29 800 2 40 8 00 FC4BNB070 45 000 TDR 12 00 10 25 47 000 3 62 29 400 2 50 8 20 FG3AAA060 43 500 NONE 12 00 10 15 46 000 3 38 29 000 2 42 8 00 FV4A...

Page 12: ...22 TXV with Puron TXV UNIT SIZE SERIES INDOOR UNIT ARI STANDARD RATINGS Cooling Heating TC Seasonal Efficiency SEER EER High Temp Low Temp HSPF Factory Supplied Enhance ment Standard Rating Field Supp...

Page 13: ...5 2 20 22 2 21 9 2 44 20 9 20 9 2 71 19 7 19 7 3 00 18 2 18 2 3 30 57 24 1 24 1 1 97 23 1 23 1 2 20 22 1 22 1 2 44 20 9 20 9 2 71 19 6 19 6 3 00 18 2 18 2 3 30 950 72 29 7 15 7 2 04 28 1 15 1 2 27 26...

Page 14: ...2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 57 28 8 28 8 2 24 27 6 27 6 2 48 26 2 26 2 2 73 24 9 24 9 3 02 23 3 23 3 3 34 21 6 21 6 3 69 1200 72 34 6 18 9 2 34 32 8 18 3 2 57 30 9 17 7 2 82 28 9...

Page 15: ...8 25 8 4 57 63 36 1 29 6 2 78 34 1 28 8 3 08 32 1 27 9 3 41 29 9 27 0 3 76 27 5 25 9 4 14 24 9 24 5 4 55 62 36 3 36 3 2 78 34 6 34 6 3 08 32 9 32 9 3 41 31 0 31 0 3 77 28 9 28 9 4 16 26 5 26 5 4 57 5...

Page 16: ...1575 72 49 7 26 3 3 24 47 1 25 5 3 60 44 5 24 6 4 00 41 7 23 6 4 44 38 6 22 6 4 93 35 0 21 5 5 44 67 45 6 34 7 3 21 43 3 33 8 3 57 40 9 32 9 3 97 38 3 31 8 4 41 35 4 30 7 4 89 32 2 29 4 5 40 63 42 6...

Page 17: ...50 40 4 40 4 4 99 37 9 37 9 5 54 35 0 35 0 6 13 1800 72 55 9 30 2 3 85 52 9 29 2 4 24 49 9 28 2 4 68 46 6 27 1 5 17 43 1 26 0 5 70 39 1 24 7 6 28 67 51 3 40 1 3 80 48 6 39 0 4 19 45 8 38 0 4 63 42 9...

Page 18: ...8 39 0 6 97 45 4 37 3 7 68 63 59 1 43 2 4 62 56 2 41 9 5 12 53 2 40 6 5 66 50 0 39 2 6 27 46 5 37 7 6 93 42 5 36 0 7 63 62 58 2 53 8 4 61 55 4 52 4 5 11 52 5 51 0 5 65 49 4 49 3 6 26 46 5 46 5 6 93 4...

Page 19: ...2 2 37 950 10 8 9 97 2 06 13 1 12 0 2 05 15 6 14 2 2 07 18 4 16 3 2 11 21 7 19 7 2 16 25 4 25 4 2 23 26 5 26 5 2 31 27 6 27 6 2 32 75 700 10 5 9 64 2 07 12 6 11 6 2 10 15 0 13 7 2 16 17 7 15 7 2 23 20...

Page 20: ...0 2 58 33 1 33 1 2 56 35 4 35 4 2 61 1200 13 2 12 2 2 37 15 9 14 6 2 38 19 0 17 3 2 40 22 4 19 9 2 45 26 2 23 8 2 51 30 4 30 4 2 58 33 6 33 6 2 54 35 5 35 5 2 55 75 900 13 1 12 1 2 35 15 3 14 1 2 40 1...

Page 21: ...4 0 3 04 31 5 28 7 3 16 36 5 36 5 3 29 35 8 35 8 3 21 34 3 34 3 3 10 1500 16 5 15 2 2 90 19 7 18 1 2 94 23 4 21 3 3 01 27 5 24 5 3 09 32 1 29 2 3 19 37 2 37 2 3 30 36 5 36 5 3 21 35 0 35 0 3 09 Indoor...

Page 22: ...19 4 17 8 3 46 23 0 21 1 3 43 26 9 24 6 3 40 31 1 27 6 3 37 35 7 32 5 3 35 40 8 40 8 3 32 44 5 44 5 4 05 42 3 42 3 3 87 1400 19 9 18 3 3 53 23 3 21 4 3 47 27 3 24 9 3 42 31 6 28 0 3 37 36 3 33 0 3 33...

Page 23: ...7 4 11 57 3 57 3 4 23 75 1400 20 4 18 8 3 46 24 3 22 3 3 53 28 8 26 2 3 64 33 7 29 9 3 78 39 3 35 8 3 94 45 6 45 6 4 13 50 2 50 2 4 35 54 2 54 2 4 51 1600 20 7 19 1 3 55 24 7 22 7 3 59 29 2 26 6 3 68...

Page 24: ...60 8 5 01 58 8 58 8 5 02 58 6 58 6 4 95 2000 26 6 24 5 4 22 32 6 29 9 4 37 38 7 35 2 4 48 45 4 40 4 4 62 53 1 48 3 4 79 61 7 61 7 4 98 59 8 59 8 4 97 59 6 59 6 4 88 2250 27 0 24 8 4 29 33 0 30 3 4 48...

Page 25: ...onnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Residential Split System Application Guideline and Servic...

Page 26: ...26...

Page 27: ...27...

Page 28: ...art up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Co...

Reviews: