Guide specifications

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system heat pump unit 

suitable for ground or rooftop installation. Unit consists of a 
hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil or 
coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of 

ARI Standard 240.

Unit will be certified for capacity and efficiency, and listed 

in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have C-UL 
approval.

Unit cabinet will be capable of withstanding Federal Test 

Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.

Air-cooled condenser coils will be leak tested at 217 psig 

and pressure tested at 450 psig.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled heat pump unit. 

Contained within the unit enclosure will be all factory wiring, 
piping, controls, compressor, refrigerant charge (Puron®), and 
special features required prior to field start-up.
Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.
Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type 

with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire 

safety guards.
Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 

bonded to copper tubes which are then cleaned, dehydrated, 
and sealed.
Refrigeration Components

Refrigeration circuit components will include liquid tube 

shutoff valve with sweat connections, suction tube shutoff 
valves with sweat connections, system charge of Puron® 
refrigerant, POE compressor oil, accumulator, and reversing 
valve.

Operating Characteristics

The capacity of the unit will meet or exceed 

 Btuh at a 

suction temperature of 

 °F. The power consumption at 

full load will not exceed 

 kW.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of 

 Btuh or greater 

at conditions of 

 CFM entering air temperature at the 

evaporator at 

 °F wet bulb and 

 °F dry bulb, and air 

entering the unit at 

 °F.

The system will have an SEER of 

 Btuh/watt or greater 

at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be 

 v,

 phase, 60 hz. The unit will be capable of satisfactory 

operation within voltage limits of 

 v to 

 v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and 

descriptions for specific features and available enhancements.

Air-Cooled, Split-System

Heat Pump

38BYC

1-1/2 to 5 Tons Nominal

Summary of Contents for 38BYC Series

Page 1: ...season All models are listed with UL U S and Canada CEC and ARI FEATURES BENEFITS Electrical Range All units are offered in single phase 208 230v Size Range 38BYC is available in 7 nominal sizes from 018 through 060 to meet the needs of residential and light commercial applications Compressor This unit features a scroll compressor which is significantly more efficient than conventional compressors...

Page 2: ...number Discharge Muffler Incorporated to minimize low frequency sound and pressure pulsation generated by compressor discharge gas Weather Protective Cabinet Steel is protected with a galvanized coating and treated with a layer of zinc phosphate A coat of modified polyester powder is then applied and baked on providing each unit with a hard smooth finish that will last for many years All screws on...

Page 3: ...TION VALVE In ID Sweat Liquid 5 8 3 4 3 4 3 4 7 8 7 8 7 8 Vapor 3 8 3 8 3 8 3 8 3 8 3 8 3 8 REFRIGERANT TUBES In OD Vapor 5 8 3 4 3 4 3 4 7 8 1 1 8 1 1 8 Liquid 3 8 3 8 3 8 3 8 3 8 3 8 3 8 UNIT SIZE SERIES OUTDOOR PISTON INDOOR TXV 018 33 34 42 KSATX0601HSO 024 35 36 52 KSATX0601HSO 030 34 35 55 KSATX0601HSO 036 34 35 63 KSATX0601HSO 042 33 34 65 KSATX0601HSO 048 33 34 73 KSATX0701HSO 060 33 34 78...

Page 4: ...High Pressure Switch All Sizes P504 8083S RCD Filter Drier Bi flow Sizes 018 036 P504 8163S RCD Filter Drier Bi flow Sizes 042 060 KHALS0401LLS Liquid Solenoid Valve LSV All Sizes KSACG1204CSM Inlet Grille Kit 4 Pack Size 018 KSACG1704CMD Inlet Grille Kit 4 Pack Size 024 KSACG1804CMD Inlet Grille Kit 4 Pack Size 042 KSACG2004CMD Inlet Grille Kit 4 Pack Sizes 030 036 048 KSACG2304CMD Inlet Grille K...

Page 5: ...nt controller has been added 6 Filter Drier Bi flow A device for removing contaminants from refrigerant circulating in a heat pump system 2 direction flow SUGGESTED USE Split system heat pumps 7 High Pressure Switch Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit Cycles compressor off if refrigerant pressure rises to about 425 psig Provides additional p...

Page 6: ...s with multiple stage supplemental heaters Used with KHAIC0101AAA Interface Control 14 Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second stage set point SUGGESTED USE Heat pump installations where 3 stage operation of supplemental heaters is desired 15 Sound Hood Wraparo...

Page 7: ...must be used from service disconnect to unit All motors compressors contain internal overload protection Sound power NOTE Tested in accordance with ARI Standard 270 95 Not listed with ARI UNIT SIZE SERIES V PH 60 Hz OPER VOLTS COMPRESSOR FAN FLA MCA MIN WIRE SIZE 60 C 75 C MAX LENGTH Ft 60 C 75 C MAX FUSE OR CKT BKR AMPS Max Min LRA RLA 018 33 34 024 35 36 030 34 35 036 34 35 042 33 34 048 33 34 0...

Page 8: ...f the unit model number 5 Center of gravity Dimensions DIMENSIONS IN UNIT SIZE SERIES A B C D E F G H J K L M N P MINIMUM MOUNTING PAD DIMENSIONS 018 33 34 22 1 2 33 15 16 3 3 16 5 8 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 10 3 4 11 14 1 4 22 1 2 x 22 1 2 024 35 36 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16 15 1 2 15 11 3 4 30 x 30 030 34 35 30 33 15 16 3 3 16 3...

Page 9: ...RATURE F 10 0 10 20 30 40 50 60 70 80 70 60 50 40 30 20 10 80 38BYC024 36 F A B 4ANF030 38BYC036 35 F A B 4AN F B 042 38BYC048 34 FK4CNF005 38BYC060 34 FK4CNB006 BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38BYC018 34 F A B 4ANF024 38BYC030 35 F A B 4ANF036 38BYC042 34 F A B 4AN F B 048 KW A02078 ...

Page 10: ... 400 NONE 11 70 10 75 23 600 3 40 14 200 2 26 7 30 CK3BA030 22 600 NONE 12 00 10 65 23 600 3 28 14 200 2 24 7 30 CK5A CK5BA024 22 400 NONE 11 70 10 75 23 600 3 40 14 200 2 26 7 30 CK5A CK5BA030 22 600 NONE 12 00 10 65 23 600 3 30 14 200 2 24 7 30 CK5A CK5BW024 22 400 NONE 11 70 10 75 23 600 3 40 14 200 2 26 7 30 CK5A CK5BW030 22 600 NONE 12 00 10 65 23 600 3 30 14 200 2 24 7 30 F A B 4 A B N F C 0...

Page 11: ... 22 800 2 46 7 70 CK5A CK5BT042 33 600 NONE 12 10 10 50 35 800 3 50 22 800 2 46 7 70 CK5A CK5BW036 33 600 NONE 12 10 10 50 35 800 3 50 22 800 2 46 7 70 F A B 4 A B N F C 036 33 000 TDR 11 70 10 20 36 000 3 38 23 000 2 38 7 60 FC4 B C NF036 33 000 TDR TXV 11 70 10 20 36 000 3 38 23 000 2 38 7 60 FC4 B C N F B 042 33 800 TDR TXV 12 10 10 45 35 800 3 46 23 000 2 44 8 00 FG3AAA036 33 000 None 12 00 10...

Page 12: ...8 00 CE3AA048 39 000 TDR 13 00 11 60 42 000 3 50 26 400 2 64 8 00 CK3BA048 39 000 TDR 13 00 11 65 42 000 3 54 26 400 2 66 8 00 CK5A CK5BA048 39 000 TDR 13 00 11 65 42 000 3 54 26 400 2 66 8 00 CK5A CK5BT048 39 000 TDR 13 00 11 65 42 000 3 54 26 400 2 66 8 00 CK5A CK5BW048 39 000 TDR 13 00 11 65 42 000 3 54 26 400 2 66 8 00 COILS 58CV A X 135 22 FURNACE CC5A CD5AC048 39 000 TDR 13 00 11 50 42 000 3...

Page 13: ... 80 CK5A CK5BT060 45 500 TDR 12 50 10 95 48 000 3 60 31 400 2 66 7 80 CK5A CK5BX060 47 000 TDR 13 00 11 15 48 000 3 62 31 400 2 68 7 80 060 33 34 40FK A B FK4 C D NB006 59 000 TDR TXV 12 00 10 30 60 000 3 40 39 000 2 46 8 00 CC5A CD5AA060 55 000 NONE 11 00 9 45 60 000 2 94 39 000 2 24 7 00 CC5A CD5AW060 57 000 NONE 11 40 9 75 60 000 3 08 38 500 2 30 7 40 CE3AA060 57 000 NONE 11 50 9 75 60 000 3 12...

Page 14: ...erature Heating Standard 70 F 21 C db indoor entering air temperature and 17 F 8 C db 15 F 11 C wb air entering outdoor unit Outdoor section indoor section combination tested in accordance with DOE test procedures for heat pumps Ratings for other combinations are determined under DOE computer simulation procedures Requires hard shutoff TXV based on computer simulation TDR is provided on most Carri...

Page 15: ... 18 0 17 5 1 53 17 2 17 1 1 71 16 5 16 5 1 92 15 8 15 8 2 14 15 0 15 0 2 37 57 17 8 17 8 1 53 17 2 17 2 1 72 16 5 16 5 1 91 15 8 15 8 2 12 15 0 15 0 2 38 72 21 6 11 7 1 58 20 7 11 4 1 78 19 7 11 1 1 98 18 7 10 7 2 19 17 7 10 4 2 45 67 19 8 15 5 1 58 18 9 15 1 1 75 18 0 14 8 1 97 17 1 14 4 2 18 16 1 14 1 2 41 750 63 18 4 15 0 1 58 17 6 14 6 1 75 16 7 14 2 1 95 15 8 13 9 2 17 14 9 13 5 2 41 62 18 5 ...

Page 16: ... 67 2 66 2 66 2 66 2 66 21 9 20 0 18 5 18 8 18 8 12 1 16 1 15 5 18 8 18 8 2 96 2 95 2 94 2 94 2 94 925 72 67 63 62 57 26 3 24 2 22 5 22 5 22 5 14 0 18 5 17 9 22 4 22 5 2 01 2 01 2 01 2 01 2 01 25 2 23 2 21 6 21 7 21 7 13 6 18 2 17 5 21 7 21 7 2 22 2 21 2 21 2 21 2 21 24 2 22 2 20 6 20 9 20 9 13 3 17 8 17 1 20 9 20 9 2 44 2 44 2 44 2 44 2 44 23 1 21 2 19 7 20 1 20 1 12 9 17 4 16 7 20 1 20 1 2 70 2 ...

Page 17: ... 9 24 9 3 02 23 8 23 8 3 35 22 7 22 7 3 71 1125 72 67 63 62 57 33 0 18 0 2 47 31 6 17 5 2 76 30 1 17 0 3 08 28 5 16 4 3 41 26 8 15 8 3 78 30 1 23 2 2 48 28 8 22 6 2 77 27 3 22 1 3 08 25 9 21 5 3 40 24 3 20 8 3 77 27 9 22 3 2 48 26 6 21 7 2 77 25 3 21 2 3 07 23 9 20 6 3 40 22 5 19 9 3 75 27 8 27 8 2 48 26 7 26 7 2 77 25 6 25 6 3 07 24 5 24 5 3 40 23 2 23 2 3 76 27 7 27 7 2 48 26 7 26 7 2 77 25 6 25...

Page 18: ... 29 0 25 0 4 34 33 2 26 7 2 99 31 7 26 1 3 28 30 2 25 4 3 59 28 5 24 6 3 93 26 9 23 9 4 31 33 1 33 1 2 99 31 8 31 8 3 28 30 5 30 5 3 60 29 2 29 2 3 94 27 8 27 8 4 32 33 1 33 1 2 99 31 8 31 8 3 28 30 6 30 6 3 60 29 2 29 2 3 94 27 8 27 8 4 32 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC...

Page 19: ... 36 9 36 9 4 25 4 20 4 16 4 18 4 18 39 6 36 5 34 0 35 2 35 2 23 2 31 6 30 4 35 2 35 2 4 64 4 59 4 54 4 57 4 57 37 4 34 5 32 1 33 6 33 6 22 5 30 8 29 5 33 6 33 6 5 07 5 01 4 96 4 99 4 99 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 0 98 0 98 CK5A CK5BT 048 0 98 0 91 CC5A CD...

Page 20: ...36 9 4 48 44 0 36 0 4 99 41 7 35 0 5 54 39 3 34 0 6 13 62 48 1 47 4 4 00 46 2 46 1 4 47 44 3 44 3 4 99 42 4 42 4 5 55 40 4 40 4 6 15 57 47 8 47 8 4 00 46 0 46 0 4 47 44 3 44 3 4 99 42 2 42 2 5 54 40 3 40 3 6 15 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 96 1 05 40FK A ...

Page 21: ...8 5 70 51 6 51 6 6 32 49 2 49 2 6 98 46 6 46 6 7 70 2000 72 67 8 35 6 5 39 64 7 34 5 5 96 61 5 33 4 6 59 58 1 32 2 7 26 54 4 31 0 7 99 67 62 6 46 3 5 31 59 7 45 2 5 87 56 6 44 0 6 49 53 4 42 7 7 15 50 0 41 4 7 87 63 59 0 45 2 5 26 56 3 44 1 5 82 53 4 42 8 6 44 50 4 41 6 7 09 47 3 40 2 7 80 62 58 2 56 6 5 24 55 7 55 1 5 80 53 1 53 1 6 42 50 5 50 5 7 09 47 9 47 9 7 81 57 57 8 57 8 5 24 55 5 55 5 5 8...

Page 22: ... 10 2 1 36 13 1 11 6 1 41 15 3 13 9 1 49 17 8 17 8 1 58 20 5 20 5 1 71 23 6 23 6 1 88 550 8 01 7 37 1 29 9 58 8 81 1 33 11 4 10 4 1 37 13 3 11 8 1 42 15 5 14 1 1 49 18 0 18 0 1 59 20 7 20 7 1 71 23 9 23 9 1 89 75 550 7 61 7 00 1 31 9 19 8 45 1 37 10 9 9 95 1 42 12 8 11 3 1 49 14 9 13 6 1 57 17 4 17 4 1 67 20 0 20 0 1 81 23 1 23 1 1 98 650 7 76 7 14 1 33 9 34 8 59 1 38 11 1 10 1 1 43 13 0 11 5 1 49...

Page 23: ...18 7 2 01 2 00 2 00 23 4 23 6 23 8 23 4 23 6 23 8 2 08 2 06 2 05 27 0 27 3 27 6 27 0 27 3 27 6 2 17 2 14 2 13 31 1 31 5 31 8 31 1 31 5 31 8 2 30 2 25 2 23 75 725 825 925 9 25 9 44 9 61 8 51 8 68 8 84 1 86 1 88 1 91 11 9 12 1 12 2 10 9 11 1 11 2 1 93 1 94 1 96 14 4 14 6 14 8 13 2 13 3 13 5 1 99 2 00 2 01 17 1 17 2 17 4 15 2 15 3 15 5 2 04 2 04 2 05 19 9 20 1 20 3 18 1 18 3 18 5 2 10 2 09 2 09 23 1 ...

Page 24: ... 2 13 9 2 20 18 3 16 7 2 27 21 9 19 4 2 37 25 7 23 4 2 49 29 9 29 9 2 64 34 4 34 4 2 78 38 1 38 1 2 92 75 875 1000 1125 11 6 10 7 2 16 14 5 13 3 2 26 17 6 16 0 2 35 21 0 18 7 2 47 24 8 22 6 2 61 28 9 28 9 2 79 33 7 33 7 3 02 38 7 38 7 3 23 11 8 10 9 2 19 14 7 13 5 2 27 17 8 16 2 2 35 21 3 18 9 2 46 25 1 22 9 2 59 29 3 29 3 2 76 34 1 34 1 2 98 38 6 38 6 3 12 12 0 11 0 2 22 14 9 13 7 2 30 18 0 16 5 ...

Page 25: ...58 14 6 13 4 2 48 18 1 16 6 2 58 21 8 19 9 2 68 25 9 23 0 2 81 30 4 27 6 2 97 35 4 35 4 3 16 40 8 40 8 3 32 45 1 45 1 3 48 14 8 13 7 2 52 18 4 16 9 2 61 22 1 20 2 2 71 26 2 23 3 2 83 30 7 27 9 2 97 35 7 35 7 3 16 40 6 40 6 3 28 43 6 43 6 3 39 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power ...

Page 26: ... 31 3 31 7 32 1 27 8 28 1 28 5 3 41 3 42 3 46 36 1 36 6 37 0 32 9 33 3 33 7 3 58 3 58 3 60 41 9 42 5 43 0 41 9 42 5 43 0 3 79 3 78 3 79 49 0 49 7 50 3 49 0 49 7 50 3 4 08 4 05 4 05 56 5 57 3 57 9 56 5 57 3 57 9 4 42 4 38 4 38 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 042 0 ...

Page 27: ... 1600 21 4 19 7 3 28 26 3 24 2 3 43 31 1 28 4 3 58 35 9 31 9 3 71 41 6 37 8 3 87 48 0 48 0 4 06 55 3 55 3 4 31 63 7 63 7 4 62 1800 21 7 20 0 3 30 26 6 24 4 3 44 31 4 28 6 3 57 36 2 32 1 3 69 41 9 38 1 3 84 48 4 48 4 4 01 55 8 55 8 4 24 64 3 64 3 4 55 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacit...

Page 28: ...2 0 47 3 5 25 60 0 60 0 5 57 69 3 69 3 5 97 79 7 79 7 6 41 2000 28 1 25 9 4 41 33 5 30 8 4 59 39 2 35 7 4 77 45 3 40 2 4 96 52 5 47 8 5 20 60 6 60 6 5 49 70 1 70 1 5 87 79 2 79 2 6 18 2250 28 5 26 2 4 45 33 8 31 1 4 61 39 5 36 0 4 78 45 7 40 6 4 95 52 9 48 2 5 18 61 1 61 1 5 45 70 4 70 4 5 77 78 5 78 5 6 05 75 1750 27 2 25 0 4 57 32 9 30 2 4 80 38 5 35 1 5 02 44 4 39 5 5 24 51 4 46 8 5 52 59 3 59 ...

Page 29: ...n unit should be level in all horizontal planes 7 Maximum elevation of indoor coil above or below base of outdoor unit is indoor coil above 50 ft indoor coil below 150 ft See items 8 and 9 following 8 For interconnecting refrigerant tube lengths greater than 50 ft consult Application Guideline and Service Manual Air Conditioners and Heat Pumps Using R 22 Refrigerant 9 For buried refrigerant tubing...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...ld start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamical...