Step 3
−
Mount Mounting Bracket on Wall
1. Decide how refrigerant will be piped. If necessary, knock
out the appropriate pre-punched holes (Fig. 4) on unit for
piping and electrical connections.
2. Remove bracket from fan coil unit by pulling it down
from fan coil unit bottom as shown in Fig. 6.
3. Using a carpenter’s level, fasten mounting brackets
into
the studs in the wall
at least 10 in. away from the ceiling
with the 8 screws provided. Always be sure to insert screws
into the top 2 holes indicated in Fig. 6. Make sure the
attached bracket will support a 200 lb vertical load. For
a masonry wall, anchor shields can be used to attach bracket
to the wall.
4. Temporarily hang unit on bracket to check location and
level.
*A clearance of 4
9
is the absolute minimum. A clearance of 10
9
is
recommended.
NOTE: Remove unit front cover for control box access.
Fig. 3 — Minimum Required Clearances
Fig. 4 — Refrigerant Piping
*38HDC, 38BK/38HDS systems.
Fig. 5 — Maximum Line Lengths