background image

Step 5 — Connect Condensate Drain Line —

Observe all local sanitary codes when installing condensate

drains.
1. Connect drain line by inserting a

5

8

-in. rigid PVC pipe

over the drain connection. Refer to Fig. 11.

The drain tube extension must be securely fastened
to the condensate drain. Failure to do so can result
in condensate water dripping onto the floor.

2. To ensure regular flow of condensate water, the drain pipe

should be pitched toward an open drain or sump at a down-
ward slope of at least

1

4

-in. per foot. Refer to Fig. 12.

IMPORTANT: Be sure the drain piping has no slack

which might form a trap. Do not insert a trap in the
drain line; the drain is internally trapped.

3. Insulate condensate drain line(s). Insulate the condensate

drain lines that are located in or above an occupied area

with a condensate proof material such as polyurethane or
neoprene.

Step 6 — Make Electrical Connections —

Be sure

field wiring complies with local building codes and NEC,
and unit voltage is within limits shown in Table 5.

Contact local power company for correction of improper

line voltage.

To avoid personal injury or damage to unit, do not make
electrical connections until all power sources are shut
down, locked out, and tagged off. Failure to do so could
result in personal injury or unit damage.

Operation of unit on improper line voltage constitutes

abuse and could affect warranty. Refer to Table 5 for

permissible operating limits. Do not install unit in sys-
tem where voltage may fluctuate above or below per-

missible limits.

NOTE: Use type NM power cable only (per NEC; provided
for fan coil units only) between disconnect switch and unit.

NOTE: Install branch circuit disconnect per NEC of ad-
equate size to handle unit starting current. Locate disconnect

within sight from and readily accessible from unit, per
Section 440-14 of NEC. Some codes allow indoor unit to
share disconnect with outdoor unit if disconnect can be locked;

check local code before installing in this manner. To make

electrical connections:
1. Remove the screws holding the front cover of the fan coil

unit, and remove front cover. Save screws and screw

covers for reinstallation.

2. Remove control box strain relief clamp (see Fig. 13).
3. Remove any factory test leads still connected to the power

terminal box. These leads (if applicable) are for factory

testing only and cannot be used for power connections.

4. Route the factory-supplied ground and power wires from

terminal block 1 (TB1) to the field-supplied disconnect

switch.

According to NEC and most local codes, the unit

must have an uninterrupted, unbroken ground to mini-
mize personal injury if an electrical fault should oc-
cur. The ground may consist of electrical wire or
metal conduit when installed in accordance with ex-
isting electrical codes. Failure to follow this warn-
ing could result in an electric shock, fire, or death.

5. Route factory-supplied line power leads (see Fig. 14) from

field-supplied, indoor unit disconnect to the fan coil unit
TB1 (see Fig. 14 and 15). Run wire through the strain
relief on the control box (see Fig. 13). When routing wire
in the fan coil unit, keep the wire away from refrigerant
and condensate piping and any sharp edges on the unit.

Do not short circuit the 40QN transformer

it is

fused. The transformer can be short circuited by con-
necting the wrong wires or by touching a live wire
to the side of a grounded control box.

Fig. 11 — Drain Connection (Right Side Shown When

Facing Fan Coil Unit)

7

Summary of Contents for 38BK-018

Page 1: ...S Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install or service air conditioning equipment Untrained personnel can perform basic maintenance such as cleaning and replacing filters All other operations should be performed by trained service personnel When working on air co...

Page 2: ...ting screws taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for damage incurred in transit Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 115 F DB 67 F DB 55 F DB 71 F WB 57 F WB 0 F DB HEA...

Page 3: ...cuRater device in the fan coil unit on 38HDC and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clearances are absolute minimums Clearances of 109 are recommended Fig 2 40QN Dimensional Drawing UNIT WEIGHT 40QN018 39 Lb 17 5 Kg 40QN024 43 Lb 19 5 Kg 3 ...

Page 4: ... 10 in away from the ceiling with the 8 screws provided Always be sure to insert screws into the top 2 holes indicated in Fig 6 Make sure the attached bracket will support a 200 lb vertical load For a masonry wall anchor shields can be used to attach bracket to the wall 4 Temporarily hang unit on bracket to check location and level A clearance of 49 is the absolute minimum A clearance of 109 is re...

Page 5: ...t be a 6 in vertical rise to the valve connections on the outdoor unit If more than the rec ommended length is buried refrigerant may migrate to the cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up Use the following instructions to connect piping 1 Install insulation Insulateall refrigerant lines on heat pumps a...

Page 6: ... 39 43 REFRIGERANT R 22 with AccuRaterT Control or TXV FAN Rpm 1120 1470 Nominal Cfm High Speed 540 550 COIL Rows 2 3 Face Area sq ft 2 56 2 56 Fins in 15 9 18 1 Number of Circuits 2 3 CONNECTIONS MPT Suction in Flare 5 8 Liquid in Flare 3 8 Condensate Drain 5 8 LINE SIZES Suction in 5 8 Liquid in 3 8 Condensate Drain 5 8 TXV Thermostatic Expansion Valve 38HDS only Table 4 Required Piston Sizes fo...

Page 7: ...tch and unit NOTE Install branch circuit disconnect per NEC of ad equate size to handle unit starting current Locate disconnect within sight from and readily accessible from unit per Section 440 14 of NEC Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked check local code before installing in this manner To make electrical connections 1 Remove the screws...

Page 8: ...ocked Rotor Amps MCA Minimum Circuit Amps per NEC Section 430 24 NEC National Electrical Code Permissible limits of the voltage range at which unit will operate satisfactorily Fig 12 Drainage System Rear Piping Shown NOTE This shows item locations only Front cover of fan coil unit must be removed to access terminal boards Fig 13 Fan Coil Unit Wiring Preparation FAN COIL UNITS LEGEND CONN Connectio...

Page 9: ...R O and O and G and G Step 8 Install Fan Coil Unit Onto Mounting Bracket 1 Hook the fan coil unit onto the top of the mounting bracket See Fig 16 2 Snap the fan coil unit onto the mounting bracket as shown in Fig 16 IMPORTANT An audible snapping sound will be heard as the hook on the unit is secured into the hole on the mounting bracket Be sure unit is cor rectly mounted START UP Complete the foll...

Page 10: ...stem after it has been out of use for the winter season perform the following steps BEFORE starting the system 1 Inspect and clean the outdoor unit particularly the coil 2 Clean or replace the air filters in the indoor unit 3 Clean the indoor unit drain pan and drain pipe and re move any obstructions 4 Turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours befor...

Page 11: ... the following occurs 1 If the room temperature is above or equal to the selected temperature the unit will operate for 16 minutes and the compressor and outdoor fan will operate The indoor fan will operate as in the cooling mode After 16 minutes of operation or when the room reaches 2 F below set point the unit switches to normal dehumidification operation 2 If the room temperature is below the s...

Page 12: ...ency mode manually move the slide switch on the fan coil unit to the EMER position Fig 20 The unit is automatically operated in cooling or heating BK units only mode according to room tempera ture Emergency operation settings are as follows 1 Operation mode AUTO 2 Fan Speed AUTO 3 Cooling set point 77 F 4 Timer Mode Continuous NOTE The unit cannot be controlled by the remote con troller until the ...

Page 13: ... is flashing Note that a m and p m are also indicated as the times are scrolled through TA 3 Press again The flashing will stop and the current time will be reset to the new setting To Remove and Clean or Replace Air Filters Operating your system with dirty air filters may damage the indoor unit and can also cause reduced cooling per formance intermittent system operation frost build up on the ind...

Page 14: ...reen UNIT ON light on the front of the fan coil unit To access the LED indicator light remove the front cover of the unit by removing the 3 screws holding it in place If the LED indicator light continuously flashes on for one second then off for one second the control is functioning properly and no fault is present A fast flashing LED indi cates that a fault has been detected Table 7 lists the num...

Page 15: ...s less than or equal to 32 F for 10 minutes after the compressor has started then the compressor and outdoor fan are turned off The indoor fan continues to run at the user selected speed until the indoor coil reaches 44 F At that time the compressor and outdoor fan will restart INDOOR COIL HIGH TEMPERATURE PROTECTION Heat Pump Systems Only If indoor coil temperature is greater than or equal to 135...

Page 16: ...mistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay STM Step Motor TB Terminal Block TRAN Transformer U Unloader Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring 1 If any of the original wire furnished must be replaced it must be replaced with type 90 C wi...

Page 17: ...ling Only System 38HDC Shown RELAY CHART COMPRESSOR K13 THERMISTOR EQUIVALENCE TEMPERATURE RESISTANCE F C V 95 35 6 500 72 22 11 400 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER 17 ...

Page 18: ...00 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3e 2f PC 111 Catalog No 534 078 Printed in U S A Form 40QN 1SI Pg 18 4 96 Replaces New ...

Page 19: ...ORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOOR UNIT RUN AND CONNECTED PROPERLY HAS CONDENSATE DRAIN BEEN RUN AND SLOPED PROPERLY IS AIR FILTER S IN PLACE IS UNIT MOUNTED LEVEL IS COOLING PISTON INSTALLED THE CORRECT SIZE AND IN THE CORRECT DI...

Page 20: ... MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and wi...

Reviews: