To Clean Outdoor Coil (Outdoor Unit)

Some metal parts and sharp fins of outdoor unit coil can
cause personal injury during cleaning. Clean coil
carefully.

To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that

collects between coil fins inhibits heat transfer — direct
the water spray between coil fins to flush out debris.

Cleaning Condensate Drains —

Clean all drains and

drain pans at the start of each cooling season. Check the flow
by pouring water into the drain.

SERVICE

When servicing unit, turn off all electric power to unit
to avoid shock hazard or injury from rotating parts.

Do not vent refrigerant to atmosphere when servicing
unit. Reclaim refrigerant during system repair or unit

removal.

Diagnostic Codes —

This unit is equipped with a mi-

croprocessor control which continuously monitors the op-
eration of the unit. If an operational fault is detected, a fault
is indicated by the flashing of the green ‘‘UNIT ON’’ light
on the front of the fan coil unit. A red LED (light-emitting

diode) indicator light, located on the control board in the
control box of the indoor unit, will emit a flash code which

can be used to troubleshoot a system problem. The control
will continue to monitor the unit and, if the conditions which

cause the fault are cleared, the unit will return to normal
operation. If the fault code is present for 5 cycles of the unit,

the unit will be locked out and the alarm is indicated by the
flashing of the green ‘‘UNIT ON’’ light on the front of the

fan coil unit.

To access the LED indicator light, remove the front cover

of the unit by removing the 3 screws holding it in place.

If the LED indicator light continuously flashes on for one

second, then off for one second, the control is functioning
properly and no fault is present. A fast flashing LED indi-
cates that a fault has been detected. Table 7 lists the number
of quick flashes and the associated fault. If the system does
not operate, and the LED indicator does not flash, either the

power to the control board is off, or the control board has
failed.

System Tests —

System tests listed below are per-

formed continuously by the microprocessor. If a fault is
indicated, then the system allows only limited operation un-
til the problem is resolved. If the problem resolves itself,
then the code is cleared and operation resumes.

THERMISTOR TESTS — Each thermistor is tested for high
limit out of range (shorted condition) and low limit out of

range (open condition). If the thermistor is out of range, the
fault status indicator comes on and the LED flashes the ap-
propriate fault code.

Table 7 — System Fault Codes

NO. OF QUICK
LED FLASHES

SYSTEM FAULT

2

Room Air Thermistor

3

Indoor Coil Thermistor

4

Outdoor Coil Thermistor*

5

Compressor Malfunction

6

Reversing Valve Malfunction*

7

Outdoor Air Thermistor*

8

Indoor Fan Failure

9

Discharge Air Thermistor

LED —

Light-Emitting Diode

*Heat pump systems only.

NOTE: If the LED light continuously flashes on for one second, then
off for one second, the control is functioning properly and no fault is
present.

PRESS

SET TIME

PRESS

TA

TA

Fig. 22 — Setting The Current Time

REMOVE FILTER

VACUUM CLEAN

RINSE WITH WATER

Fig. 23 — Air Filter Maintenance

14

Summary of Contents for 38BK-018

Page 1: ...S Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install or service air conditioning equipment Untrained personnel can perform basic maintenance such as cleaning and replacing filters All other operations should be performed by trained service personnel When working on air co...

Page 2: ...ting screws taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for damage incurred in transit Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 115 F DB 67 F DB 55 F DB 71 F WB 57 F WB 0 F DB HEA...

Page 3: ...cuRater device in the fan coil unit on 38HDC and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clearances are absolute minimums Clearances of 109 are recommended Fig 2 40QN Dimensional Drawing UNIT WEIGHT 40QN018 39 Lb 17 5 Kg 40QN024 43 Lb 19 5 Kg 3 ...

Page 4: ... 10 in away from the ceiling with the 8 screws provided Always be sure to insert screws into the top 2 holes indicated in Fig 6 Make sure the attached bracket will support a 200 lb vertical load For a masonry wall anchor shields can be used to attach bracket to the wall 4 Temporarily hang unit on bracket to check location and level A clearance of 49 is the absolute minimum A clearance of 109 is re...

Page 5: ...t be a 6 in vertical rise to the valve connections on the outdoor unit If more than the rec ommended length is buried refrigerant may migrate to the cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up Use the following instructions to connect piping 1 Install insulation Insulateall refrigerant lines on heat pumps a...

Page 6: ... 39 43 REFRIGERANT R 22 with AccuRaterT Control or TXV FAN Rpm 1120 1470 Nominal Cfm High Speed 540 550 COIL Rows 2 3 Face Area sq ft 2 56 2 56 Fins in 15 9 18 1 Number of Circuits 2 3 CONNECTIONS MPT Suction in Flare 5 8 Liquid in Flare 3 8 Condensate Drain 5 8 LINE SIZES Suction in 5 8 Liquid in 3 8 Condensate Drain 5 8 TXV Thermostatic Expansion Valve 38HDS only Table 4 Required Piston Sizes fo...

Page 7: ...tch and unit NOTE Install branch circuit disconnect per NEC of ad equate size to handle unit starting current Locate disconnect within sight from and readily accessible from unit per Section 440 14 of NEC Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked check local code before installing in this manner To make electrical connections 1 Remove the screws...

Page 8: ...ocked Rotor Amps MCA Minimum Circuit Amps per NEC Section 430 24 NEC National Electrical Code Permissible limits of the voltage range at which unit will operate satisfactorily Fig 12 Drainage System Rear Piping Shown NOTE This shows item locations only Front cover of fan coil unit must be removed to access terminal boards Fig 13 Fan Coil Unit Wiring Preparation FAN COIL UNITS LEGEND CONN Connectio...

Page 9: ...R O and O and G and G Step 8 Install Fan Coil Unit Onto Mounting Bracket 1 Hook the fan coil unit onto the top of the mounting bracket See Fig 16 2 Snap the fan coil unit onto the mounting bracket as shown in Fig 16 IMPORTANT An audible snapping sound will be heard as the hook on the unit is secured into the hole on the mounting bracket Be sure unit is cor rectly mounted START UP Complete the foll...

Page 10: ...stem after it has been out of use for the winter season perform the following steps BEFORE starting the system 1 Inspect and clean the outdoor unit particularly the coil 2 Clean or replace the air filters in the indoor unit 3 Clean the indoor unit drain pan and drain pipe and re move any obstructions 4 Turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours befor...

Page 11: ... the following occurs 1 If the room temperature is above or equal to the selected temperature the unit will operate for 16 minutes and the compressor and outdoor fan will operate The indoor fan will operate as in the cooling mode After 16 minutes of operation or when the room reaches 2 F below set point the unit switches to normal dehumidification operation 2 If the room temperature is below the s...

Page 12: ...ency mode manually move the slide switch on the fan coil unit to the EMER position Fig 20 The unit is automatically operated in cooling or heating BK units only mode according to room tempera ture Emergency operation settings are as follows 1 Operation mode AUTO 2 Fan Speed AUTO 3 Cooling set point 77 F 4 Timer Mode Continuous NOTE The unit cannot be controlled by the remote con troller until the ...

Page 13: ... is flashing Note that a m and p m are also indicated as the times are scrolled through TA 3 Press again The flashing will stop and the current time will be reset to the new setting To Remove and Clean or Replace Air Filters Operating your system with dirty air filters may damage the indoor unit and can also cause reduced cooling per formance intermittent system operation frost build up on the ind...

Page 14: ...reen UNIT ON light on the front of the fan coil unit To access the LED indicator light remove the front cover of the unit by removing the 3 screws holding it in place If the LED indicator light continuously flashes on for one second then off for one second the control is functioning properly and no fault is present A fast flashing LED indi cates that a fault has been detected Table 7 lists the num...

Page 15: ...s less than or equal to 32 F for 10 minutes after the compressor has started then the compressor and outdoor fan are turned off The indoor fan continues to run at the user selected speed until the indoor coil reaches 44 F At that time the compressor and outdoor fan will restart INDOOR COIL HIGH TEMPERATURE PROTECTION Heat Pump Systems Only If indoor coil temperature is greater than or equal to 135...

Page 16: ...mistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay STM Step Motor TB Terminal Block TRAN Transformer U Unloader Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring 1 If any of the original wire furnished must be replaced it must be replaced with type 90 C wi...

Page 17: ...ling Only System 38HDC Shown RELAY CHART COMPRESSOR K13 THERMISTOR EQUIVALENCE TEMPERATURE RESISTANCE F C V 95 35 6 500 72 22 11 400 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER 17 ...

Page 18: ...00 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3e 2f PC 111 Catalog No 534 078 Printed in U S A Form 40QN 1SI Pg 18 4 96 Replaces New ...

Page 19: ...ORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOOR UNIT RUN AND CONNECTED PROPERLY HAS CONDENSATE DRAIN BEEN RUN AND SLOPED PROPERLY IS AIR FILTER S IN PLACE IS UNIT MOUNTED LEVEL IS COOLING PISTON INSTALLED THE CORRECT SIZE AND IN THE CORRECT DI...

Page 20: ... MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and wi...