5.3 - Alarms menu
Icon
Displayed text*
Description
Reset Alarms
Alarm reset
Current Alarms
Current alarms
Alarm History
Alarm history
Major Alarm History
Major alarm history
*Depends on the selected language (English by default).
5.4 - Configuration menu
Icon
Displayed text*
Description
Associated table
General Configuration
General configuration
GEN_CONF
Pump Configuration
Pump configuration
PUMPCONF
User Configuration
User configuration
USERCONF
Reset Configuration
Reset configuration
RESETCFG
Schedule Menu
Schedule menu
SCHEDULE
Holiday Menu
Holiday menu
HOLIDAY
Broadcast Menu
Broadcast menu
BROCASTS
Date/Time Configuration
Date/time configuration
DATETIME
Control Identification
Control identification
CTRL_ID
*Depends on the selected language (English by default).
NOTE: Since specific units may not include certain options, some tables may contain parameters that cannot be
configured for a given unit.
GEN_CONF – General configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 2
0
-
Cir Priority Sequence
Circuit priority
2
0=Auto
1=A Prio
0 = Automatic circuit selection
1 = Circuit A priority
3
2=B Prio
2 = Circuit B priority
4
0 to 1
0
-
Staged Loading Sequence
Staged loading sequence
5
no/yes
0
-
Ramp Loading Select
Ramp loading selection
6
1 to 15
1
min
Unit Off to On Delay
Unit Off to On delay
7
0 to 2
0
-
Demand Limit Type Select
Demand limit selection
8
0 = None
0 = None
9
1 = Switch Control
1 = Switch control
10
2 = 4-20mA Control
2 = 4-20 mA control
11
-
-
-
Night Mode Start Hour
Night mode start hour
12
-
-
-
Night Mode End Hour
Night mode end hour
13
0 to 100
100
%
Night Capacity Limit
Night capacity limit
14
0 to 1
0
-
Power Limit select
Power limit selection
15
0 to 1
0
-
Ice Mode Enable
Ice mode enabled
16
0 to 2000
2000
kW
Maximum Power Limit
Maximum power limit
17
0 to 1
0
-
short cycle management
Short cycle management
*Depends on the selected language (English by default).