PUMPCONF – Pump configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 4
0
-
Cooler Pumps Sequence
Evaporator pumps sequence
2
0 = No Pump
0 = No pump
3
1 = One Pump Only
1 = One pump only
4
2 = Two Pumps Auto
2 = Two pumps automatic control
5
3 = Pump#1 Manual
3 = Pump 1 manual
6
4 = Pump#2 Manual
4 = Pump 2 manual
7
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump automatic rotation delay
8
no/yes
no
-
Pump Sticking Protection
Pump sticking protection
9
no/yes
no
-
Stop Pump During Standby
Pump stop when the unit is in standby
10
no/yes
yes
-
Flow Checked If Pump Off
Flow check when the pump is off
11
no/yes
no
-
Cooler Pump Off In Heat
Evaporator pump off in Heating
12
no/yes
no
-
Cond Pump Off In Cool
Condenser pump off in Cooling
13
1 to 3
1
-
VSPump regulation config
Variable speed pump configuration
*Depends on the selected language (English by default).
USERCONF – User configuration
No.
Status
Default
Unit
Displayed text*
Description
1
1 to 9999
11
-
User Password
User password
2
0 to 1
0
-
Language List
Selected language list
3
0 = eng/spa/fre/ger/dut
Languages available when “language list” is set to “0”
4
chi/ita/por/rus/und
5
1 = eng/spa/fre/ger/dut
Languages available when “language list” is set to “1”
6
tur/ita/por/rus/gre
*Depends on the selected language (English by default).
RESETCFG – Reset configuration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 4
0
-
Cooling Reset Select
Cooling reset selection
2
0 to 4
0
-
Heating Reset Select
Heating reset selection
3
0=None, 1=OAT
0 = None
1 = OAT
4
2=Delta T, 4=Space Temp
2 = Delta T
4 = Space temperature
5
3=4-20mA control
3 = 4-20 mA control
6
Cooling
Cooling
7
-10 to 51.7
-10
°C
OAT No Reset Value
OAT, no reset value
14 to 125
14
°F
8
-10 to 51.7
-10
°C
OAT Full Reset Value
OAT, max. reset value
14 to 125
14
°F
9
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset value
0 to 25
0
^F
10
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset value
0 to 25
0
^F
11
0 to 20
0
mA
Current No Reset Value
Current, no reset value
12
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
13
-10 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset value
14 to 125
14
°F
14
-10 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset value
14 to 125
14
°F
15
-16.7 to 16.7
0
^C
Cooling Reset Deg. Value
Maximum cooling reset value
-30 to 30
0
^F
16
Heating
Heating
17
-10 to 51.7
-10
°C
OAT No Reset Value
OAT, no reset value
14 to 125
14
°F
18
-10 to 51.7
-10
°C
OAT Full Reset Value
OAT, max. reset value
14 to 125
14
°F
19
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset value
0 to 25
0
^F
20
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset value
0 to 25
0
^F
21
0 to 20
0
mA
Current No Reset Value
Current, no reset value
22
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
23
-10 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset value
14 to 125
14
°F
24
-10 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset value
14 to 125
14
°F
25
-16.7 to 16.7
0
^C
Heating Reset Deg. Value
Maximum heating reset value
-30 to 30
0
^F
*Depends on the selected language (English by default).