No.
Status
Unit
Displayed text*
Description
25
-
hour
Circuit B Fan #3 Hours
Operating hours, fan B3
26
-
hour
Circuit B Fan #4 Hours
Operating hours, fan B4
27
-
hour
Circuit B Fan #5 Hours
Operating hours, fan B5
28
-
hour
Circuit B Fan #6 Hours
Operating hours, fan B6
29
-
hour
Circuit B Fan #7 Hours
Operating hours, fan B7
30
-
hour
Circuit B Fan #8 Hours
Operating hours, fan B8
31
-
hour
Circuit B Fan #9 Hours
Operating hours, fan B9
32
-
hour
Circuit B Fan #10 Hours
Operating hours, fan B10
33
-
hour
Circuit B Fan #11 Hours
Operating hours, fan B11
34
-
hour
Circuit B Fan #12 Hours
Operating hours, fan B12
35
-
hour
Circuit B Fan #13 Hours
Operating hours, fan B13
36
-
hour
Circuit B Fan #14 Hours
Operating hours, fan B14
* Depends on the selected language (English by default).
NOTE: The displayed run times are updated every hour.
MODES – Modes
No.
Status
Unit
Displayed text*
Description
1
no/yes
-
Start Up Delay In Eff ect
Start-up delay in eff ect
2
no/yes
-
Second Setpoint In Use
Second setpoint in use
3
no/yes
-
Reset In Eff ect
Setpoint reset active
4
no/yes
-
Demand limit active
Demand limit active
5
no/yes
-
Cooler Pump Rotation
Evaporator pump rotation
6
no/yes
-
Pump Periodic Start
Pump periodic start
7
no/yes
-
Night Low Noise Active
Night low noise active
8
no/yes
-
Master Slave Active
Master/slave mode active
9
no/yes
-
Auto Changeover Active
Automatic changeover active
10
no/yes
-
Condenser Pump Rotation
Condenser pump rotation
11
no/yes
-
Cond Pump Periodic Start
Condenser pump periodic start
12
no/yes
-
Ice Mode In Eff ect
Ice mode active
* Depends on the selected language (English by default).
SETPOINT – Setpoint table
No.
Status
Default
Unit
Displayed text*
Description
1
-28.9 to 26
6.7
°C
Cooling Setpoint 1
Cooling setpoint 1
-20.0 to 78.8
44.0
°F
2
-28.9 to 26
6.7
°C
Cooling Setpoint 2
Cooling setpoint 2
-20.0 to 78.8
44.0
°F
3
-28.9 to 26
6.7
°C
Cooling Ice Setpoint
Ice storage setpoint
-20.0 to 78.8
44.0
°F
4
0.1 to 11.1
0.6
^C
Cooling Ramp Loading
Cooling ramp loading setpoint
0.2 to 20.0
1.0
^F
5
26.7 to 63
37.8
°C
Heating Setpoint 1
Heating setpoint 1
80.0 to 145.4
100.0
°F
6
26.7 to 63
37.8
°C
Heating Setpoint 2
Heating setpoint 2
80.0 to 145.4
100.0
°F
7
0.1 to 11.1
0.6
^C
Heating Ramp Loading
Heating ramp loading setpoint
0.2 to 20.0
1.0
^F
8
3.9 to 50
23.9
°C
Cool Changeover Setpt
Cooling changeover setpoint
39.0 to 122.0
75.0
°F
9
0 to 46.1
17.8
°C
Heat Changeover Setpt
Heating changeover setpoint
32.0 to 115.0
64.0
°F
10
1 to 20
5
^C
Varipump Delta Temp Stp
Variable speed pump, delta temperature setpoint
1.8 to 36
9.0
^F
11
50 to 344.8
200
kPa
Varipump Delta Press Stp
Variable speed pump, delta temperature setpoint
7.25 to 50
29.0
PSI
12
0 to 100
100
%
Switch Limit Setpoint 1
Switch limit setpoint 1
13
0 to 100
100
%
Switch Limit Setpoint 2
Switch limit setpoint 2
14
0 to 100
100
%
Switch Limit Setpoint 3
Switch limit setpoint 3
*Depends on the selected language (English by default).
NOTE: Since specifi c units may not include certain options, some tables provided in the document contain parameters
that cannot be confi gured for a given unit. Some confi guration or setpoint limits may also be clamped to lower / higher
values depending on option selection.