OUTPUTS – Outputs status
No.
Status
Unit
Displayed text*
Description
1
off/on
-
Compressor A
Compressor A status
2
off/on
-
Oil Solenoid Output A
Oil solenoid output, circuit A
3
off/on
-
Slide Valve 1 Output A
Slide valve 1 output, circuit A
4
off/on
-
Slide Valve 2 Output A
Slide valve 2 output, circuit A
5
-
V
Capacity Signal Cir A
0-10 V capacity signal, circuit A
6
0 to 100
%
VariFan Speed A
Variable speed fan, circuit A
7
off/on
-
Ref Iso Valve Close A
Refrigerant isolation valve closed, circuit A
8
off/on
-
Ref Iso Valve Open A
Refrigerant isolation valve open, circuit A
9
close/open
-
Ref Iso Valve pos. A
Refrigerant isolation valve position, circuit A
10
off/on
-
Oil Heater Output A
Oil heater output, circuit A
11
off/on
-
Compressor B
Compressor B status
12
off/on
-
Oil Solenoid Output B
Oil solenoid output, circuit B
13
off/on
-
Slide Valve 1 Output B
Slide valve 1 output, circuit B
14
off/on
-
Slide Valve 2 Output B
Slide valve 2 output, circuit B
15
-
V
Capacity Signal Cir B
0-10 V capacity signal, circuit B
16
0 to 100
%
VariFan Speed B
Variable speed fan, circuit B
17
off/on
-
Ref Iso Valve Close B
Refrigerant isolation valve closed, circuit B
18
off/on
-
Ref Iso Valve Open B
Refrigerant isolation valve open, circuit B
19
close/open
-
Ref Iso Valve pos. B
Refrigerant isolation valve position, circuit B
20
off/on
-
Oil Heater Output B
Oil heater output, circuit B
21
-
V
Chiller Capacity signal
Chiller capacity signal
22
off/on
-
Alarm Relay Status
Alarm status
23
off/on
-
Running Relay Status
Run status
24
off/on
-
Alert Relay State
Alert status
25
off/on
-
Shutdown Indicator State
Shutdown status
26
off/on
-
Cooler Heater Output
Evaporator heater output
27
off/on
-
Electrical box fan
Electrical box fan
*Depends on the selected language (English by default).
PUMPSTAT – Pump status
No.
Status
Unit
Displayed text*
Description
1
no/yes
-
Cooler Flow Setpoint Out
Evaporator flow setpoint output
2
0 to 1
-
Cooler Pump #1 Command
Evaporator pump 1 control
3
0 to 1
-
Cooler Pump #2 Command
Evaporator pump 2 control
4
0 to 1
-
Rotate Cooler Pumps ?
Evaporator pumps rotation
5
open/close
-
Cooler Flow Switch
Evaporator flow switch
6
0 to 100
%
Variable speed pump cmd
Variable speed pump command
7
-
l/s
GPS
Cooler flow (kit hydro)
Evaporator flow (hydronic kit)
*Depends on the selected language (English by default).
RUNTIME – Run times
No.
Status
Unit
Displayed text*
Description
1
-
hour
Machine Operating Hours
Unit operating hours
2
-
-
Machine Starts Number
Number of unit starts
3
-
hour
Compressor A Hours
Operating hours, compressor A
4
-
-
Compressor A Starts
Number of starts, compressor A
5
-
hour
Compressor B Hours
Operating hours, compressor B
6
-
-
Compressor B Starts
Number of starts, compressor B
7
-
hour
Cooler Pump #1 Hours
Operating hours, evaporator pump 1
8
-
hour
Cooler Pump #2 Hours
Operating hours, evaporator pump 2
9
-
hour
Circuit A Fan #1 Hours
Operating hours, fan A1
10
-
hour
Circuit A Fan #2 Hours
Operating hours, fan A2
11
-
hour
Circuit A Fan #3 Hours
Operating hours, fan A3
12
-
hour
Circuit A Fan #4 Hours
Operating hours, fan A4
13
-
hour
Circuit A Fan #5 Hours
Operating hours, fan A5
14
-
hour
Circuit A Fan #6 Hours
Operating hours, fan A6
15
-
hour
Circuit A Fan #7 Hours
Operating hours, fan A7
16
-
hour
Circuit A Fan #8 Hours
Operating hours, fan A8
17
-
hour
Circuit A Fan #9 Hours
Operating hours, fan A9
18
-
hour
Circuit A Fan #10 Hours
Operating hours, fan A10
19
-
hour
Circuit A Fan #11 Hours
Operating hours, fan A11
20
-
hour
Circuit A Fan #12 Hours
Operating hours, fan A12
21
-
hour
Circuit A Fan #13 Hours
Operating hours, fan A13
22
-
hour
Circuit A Fan #14 Hours
Operating hours, fan A14
23
-
hour
Circuit B Fan #1 Hours
Operating hours, fan B1
24
-
hour
Circuit B Fan #2 Hours
Operating hours, fan B2