21
For the high pressure single and dual-pump motors for 30RQM/30RQP 160-520 units (options 116R and 116V)
No.
(2)
Description
(3)
Units
30RQM/30RQP
160 180 210 230 240 270
310
330
380
430
470
520
1
Nominal efficiency at full load and nominal voltage
%
87.5 87.5 89.6 89.6 89.6 89.7 89.7 89.7 89.7 90.8 90.8
90.8
1
Nominal efficiency at 75% full load and nominal voltage
%
88.2 88.2 90.4 90.4 90.4 90.0 90.0 90.0 90.0 90.8 90.8
90.8
1
Nominal efficiency at 50% full load and nominal voltage
%
87.5 87.5 89.9 89.9 89.9 89.0 89.0 89.0 89.0 89.6 89.6
89.6
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4
Manufacturer’s name or trademark, commercial registration
number and registered address
-
Same as above
5
Product’s model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V) kW
3
3
4
4
4
5.5
5.5
5.5
5.5
7.5
7.5
7.5
7-2
Maximum input power (400 V)
(5)
kW
3.81 3.81 4.96 4.96 4.96 6.80 6.80 6.80 6.80 9.16 9.16
9.16
8
Nominal input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
3 x 400
9-2
Maximum current drawn (400 V)
(6)
A
6.81 6.81 8.27 8.27 8.27 11.30 11.30 11.30 11.30 15.30 15.30 15.30
10
Nominal speed
r/s - r/min 48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(4)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw.
For the high pressure single- and dual-pump motors for 30RQM/30RQP 160-520 units (options 116S and 116W)
No.
(2)
Description
(3)
Units
30RQM/30RQP
160
180
210
230
240
270
310
330
380
430
470
520
1
Nominal efficiency at full load and nominal voltage
%
87.5 87.5 89.6 89.6 89.6 89.7 89.7 89.7 90.8 90.8 90.8
90.8
1
Nominal efficiency at 75% full load and nominal voltage
%
88.2 88.2 90.4 90.4 90.4 90.0 90.0 90.0 90.8 90.8 90.8
90.8
1
Nominal efficiency at 50% full load and nominal voltage
%
87.5 87.5 89.9 89.9 89.9 89.0 89.0 89.0 89.6 89.6 89.6
89.6
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4
Manufacturer’s name or trademark, commercial registration
number and registered address
-
Same as above
5
Product’s model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage
(400 V)
kW
3
3
4
4
4
5.5
5.5
5.5
5.5
7.5
7.5
7.5
7-2
Maximum input power (400 V)
(5)
kW
3.81 3.81 4.96 4.96 4.96 6.80 6.80 6.80 6.80 9.16 9.16
9.16
8
Nominal input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
3 x 400
9-2
Maximum current drawn (400 V)
(6)
A
6.81 6.81 8.27 8.27 8.27 11.30 11.30 11.30 11.30 15.30 15.30 15.30
10
Nominal speed
r/s - r/min 48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(4)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific conditions
in the Carrier selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw.