3.4 - Installation of multiple heat pumps
It is recommended to install multiple heat pumps in a single row, arranged as shown in the example below, to avoid recycling of
air from one unit to another.
If the floor space does not allow this arrangement, contact your Carrier distributor to assess the various installation options.
3.5 - Distance to the wall
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your Carrier distributor to assess the various installation options.
Anti-vibration