17
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
4.1 - Physical data 30RQM 160-520
30RQM
160
180
210
230
240
270
310
330
380
430
470
520
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Standard unit + option 15
(3)
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Unit length with water buffer tank module opt
mm
3604
4798
5991
Operating weight
(4)
Standard unit
kg
1426 1505 1633 1656
2068
2216 2341 2572 3040
3289
3302 3342
Standard unit + option 15
kg
1509 1588
1741 1764 2176 2342 2467 2716 3202 3470
3482
3522
Standard unit + option 15 + option 116W
(3)
kg
1649 1728 1893 1915
2337 2551
2685 2920
3407 3715 3764
3803
Unit + option 15 + option 116W + Water buffer tank module
kg
2608 2687 2852 2874 3296
3510 3644
3879
4366 4674 4723 4762
Compressors
Hermetic Scroll 48.3 r/s
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(4)
R-410A
Circuit A charge
kg
14,5 22,0 23,0 24,0 27,0 27,0 30,0 33,0 42,0 53,0 54,0 56,0
tCO
2
e
30,3 45,9 48,0 50,1 56,4 56,4 62,6 68,9 87,7 110,7 112,8 116,9
Circuit B charge
kg
23,0 23,0 23,0 24,0 35,0 36,0 48,5 53,0 53,0 53,0 54,0 56,0
tCO
2
e
48,0 48,0 48,0 50,1 73,1 75,2 101,3 110,7 110,7 110,7 112,8 116,9
Control
Touch Pilot Control
Minimum capacity
%
33% 33% 25% 25% 25% 20% 20% 17% 14% 13% 13% 13%
Air heat exchanger
Grooved copper tubes and aluminum fins
Fans
Axial Flying Bird 4 with rotating shroud
Quantity
3
4
4
4
5
5
6
6
7
8
8
8
Maximum total air flow
l/s
13542
18056 18056 18056 22569 22569 27083 27083 31597
36111 36111 36111
Maximum rotation speed
rps
16
16
16
16
16
16
16
16
16
16
16
16
Water heat exchanger
Dual-circuit plate heat exchanger
Water volume
l
15
15
15
19
27
27
35
44
44
44
47
53
Max. water-side operating pressure without hydraulic module
kPa
3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve, pressure sensors,
expansion tank (option)
Pump
Centrifugal pump, monocell, 48.3 rps, low- or high-pressure (as required), single or dual
(as required)
Expansion vessel volume
l
50
50
50
50
80
80
80
80
80
80
80
80
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic type
Connections
inch
3
3
3
3
4
4
4
4
4
4
4
4
External diameter
mm
88.9 88.9 88.9 88.9 114.3 114.3 114.3 114.3 114.3 114.3 114.3 114.3
Chassis paintwork
Colour code: RAL 7035
(1)
In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1
and certified by Eurovent at nominal conditions EN14511 - cooling mode.
(2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound
power Lw(A).
(3) Options: 15 = low noise level, 116W = Variable speed high pressure dual-pump hydraulic module.
(4) Values are guidelines only. Refer to the unit nameplate.
Eurovent certified values