1 - INTRODUCTION

Prior to the initial start-up of the 30RA units, the people
involved in the on-site installation, start-up, operation, and
maintenance of this unit should be thoroughly familiar with
these instructions and the specific project data for the
installation site.

The 30RA liquid chillers are designed to provide a very high
level of safety during installation, start-up, operation and
maintenance. They will provide safe and reliable service when
operated within their application range.

This manual provides the necessary information to familiarize
yourself with the control system before performing start-up
procedures. The procedures in this manual are arranged in the
sequence required for machine installation, start-up, operation
and maintenance.

Be sure you understand and follow the procedures and safety
precautions contained in the instructions supplied with the
machine, as well as those listed in this guide.

Earthquake resistance has not been verified for these units.

1.1 - Installation safety considerations

This machine must be installed in a location that is not accessible
to the public and protected against access by non-authorised
people.

After the unit has been received, when it is ready to be installed
or reinstalled, and before it is started up, it must be inspected
for damage. Check that the refrigerant circuit(s) is (are) intact.
Ensure especially that no components or pipes have shifted
(e.g. following a shock). If in doubt, carry out a leak tightness
check and verify with the manufacturer that the circuit integrity
has not been impaired. If damage is detected upon receipt,
immediately file a claim with the shipping company.

Do not remove the skid or the packaging until the unit is in its
final position. These units can be moved with a fork lift truck,
as long as the forks are positioned in the right place and
direction on the unit.

The units can also be lifted with slings, using only the desig-
nated lifting points marked at the four corners at the unit base.

These units are not designed to be lifted from above. Use
slings with the correct capacity, and always follow the lifting
instructions on the certified drawings supplied with the unit.

Safety is only guaranteed, if these instructions are carefully
followed. If this is not the case, there is a risk of material
deterioration and injuries to personnel.

Never cover any safety devices.

This applies to the globe valve in the water circuit and the
globe valve(s) in the refrigerant circuit(s).

Ensure that the valves are correctly installed, before operating
the unit.

In certain cases the globe stops are installed on ball valves.
These valves are factory-supplied lead-sealed in the open
position. This system permits isolating and removing the
globe stop for checking and replacing. The globe stops are
designed and installed to ensure protection against fire risk.
Removing the globe stops is only permitted if the fire risk is
fully controlled and the responsibility of the user.

All factory-installed globe valves are lead-sealed to prevent
any calibration change. If the globe valves are installed on a
reversing valve (change-over), this is equipped with a globe
valve on each of the two outlets. Only one of the two glove
valves is in operation, the other one is isolated. Never leave
the reversing valve in the intermediate position, i.e. with both
ways open (locate the control element in the stop position). If
a globe stop is removed for checking or replacement please
ensure that there is always an active globe stop on each of the
reversing valves installed in the unit.

Provide a drain in the discharge circuit, close to each valve,
to avoid an accumulation of condensate or rain water.

The safety valves must be connected to discharge pipes. These
pipes must be installed in a way that ensures that people and
property are not exposed to refrigerant leaks. These fluids
may be diffused in the air, but far away from any building air
intake, or they must be discharged in a quantity that is
appropriate for a suitably absorbing environment.

Periodic check of the globe valves: See paragraph
“Maintenance safety considerations”.

Accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation or explosions.

Inhalation of high concentrations of vapour is harmful and
may cause heart irregularities, unconsciousness, or death.
Vapour is heavier than air and reduces the amount of oxygen
available for breathing. These products cause eye and skin
irritation. Decomposition products are hazardous.

1.2 - Equipment and components under pressure

These products incorporate equipment or components under
pressure, manufactured by Carrier or other manufacturers. We
recommend that you consult your appropriate national trade
association or the owner of the equipment or components under
pressure (declaration, re-qualification, retesting, etc.). The
characteristics of this equipment/these components are given
on the nameplate or in the required documentation, supplied
with the products.

Do not introduce high static and dynamic pressure compared
with the existing operating pressures - either service or test
pressures in the refrigerant circuit or in the heat transfer circuit,
especially:
-

limiting the elevation of the condensers or evaporators

-

taking the circulating pumps into consideration.

Summary of Contents for 30RA040B

Page 1: ...Hz Installation operation and maintenance instructions AQUASNAP For the operation of the control please refer to the Pro Dialog Control manual for the 30RA RH RY RYH B series Carrier is participating...

Page 2: ...2 The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract...

Page 3: ...Control box 16 7 2 Power supply 17 7 3 Voltage phase imbalance 17 8 RECOMMENDEDWIRESECTIONS 18 8 1 Field control wiring 18 9 WATERCONNECTIONS 19 9 1 Operating precautions and recommendations 19 9 2 H...

Page 4: ...the unit In certain cases the globe stops are installed on ball valves These valves are factory supplied lead sealed in the open position This system permits isolating and removing the globe stop for...

Page 5: ...ntact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrigerant type used must be within easy r...

Page 6: ...ut by a qualified and authorised engineer These procedures must be carried out with the unit shut down NOTE The unit must never be left shut down with the liquid line valve closed as liquid refrigeran...

Page 7: ...ld always be protected against crushing while a unit is being moved Use struts or spreader bars to spread the slings above the unit Do not tilt a unit more than 15 WARNING Never push or lever on any o...

Page 8: ...s and arrangements are in place and comply with the current European standard Verify that all document for pressure containers certificates name plates files instruction manuals that are required docu...

Page 9: ...9 30RA 090 160 3 DIMENSIONS CLEARANCES 30RA 040 080 1081 1329 2071 1000 1000 1 2 1 2 1000 1000 2071 2278 1329 1000 1000 1000 1000 2 1 1 1 1 2...

Page 10: ...ct Power cable entry NOTE A Non certifieddrawings Refer to the certified dimensional drawings supplied with the unit or available on request when designing an installation For the location of fixing p...

Page 11: ...le 040 050 060 070 080 090 100 120 140 160 200 240 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit supply The control circuit is supplied via the unit mount...

Page 12: ...vely please order the special version from the factory by contacting your local Carrier dealer For unit sizes 200 and 240 the installation requires drilling a hole into the control box changing of the...

Page 13: ...l 30RA units are protected to IP44CW and fulfil this protectioncondition Electrical data notes 30RA 30RA 040 240 units have a single power connection point located at the main switch The control box i...

Page 14: ...recirculation of the evaporator water flow may take place leading to the risk of excessive fouling 6 4 Maximum evaporator water flow rate This is limited by the permitted evaporator pressure drop Also...

Page 15: ...outside air temperature Operating range with required anti freeze solution and special Pro Dialog controlconfiguration 6 6 Unit operating range at full and part load 6 7 Pressure drop in the plate hea...

Page 16: ...1 Main disconnect switch PE Earth connection S Power supply cable section see table Recommended wire sections X Disconnect switch position referred to the unit side Y Control box position referred to...

Page 17: ...ch position referred to the unit side Y Control box position referred to the unit base X mm Y mm 30RA 040 080 190 762 30RA 090 160 1415 762 30RA 200 240 1161 1107 NOTES The 30RA 040 240 units have onl...

Page 18: ...oltage drop to 5 length L in metres see table below IMPORTANT Before connection of the main power cables L1 L2 L3 on the terminal block it is imperative to check the correct order of the 3 phases befo...

Page 19: ...be recommended 10 pH Ideal case pH neutral at 20 25 C 7 pH 8 ATTENTION Charging adding or draining fluid from the water circuit must be done by qualified personnel using air vents and materials suitab...

Page 20: ...a bypass must be included as shown below Winter position Legend A Unit B Water network C Closed O Open A B O F F IMPORTANT Depending on the atmospheric conditions in your area you must do the followi...

Page 21: ...tion are equipped with a flow switch and an internal piping heater Legend Components of the unit and hydronic module 1 Victaulic screen filter 2 Expansion tank 3 Safety valve 4 Available pressure pump...

Page 22: ...ble for the installation to get it These characteristics can be obtained from the technical literature using the unit performance tables for a T of 5 K at the evaporator or with the Electronic Catalog...

Page 23: ...system has an excessive pressure drop in relation to the available static pressure provided by the pump the resulting water flow rate will de reduced and the difference between entering and leaving wa...

Page 24: ...RA080 100 3 30RA120 160 4 30RA200 240 Dual pumps 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 12 14 16 18 20 22 24 26 1 2 3 4 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 1...

Page 25: ...7 30RA 120 8 30RA 140 9 30RA 160 10 30RA 200 11 30RA 240 Dual pumps Legend 1 30RA 040 2 30RA 050 3 30RA 060 4 30RA 070 5 30RA 080 6 30RA 090 7 30RA 100 8 30RA 120 9 30RA 140 10 30RA 160 11 30RA 200 12...

Page 26: ...Ensure that all safety devices are satisfied especially the high pressure switches 11 3 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and...

Page 27: ...Data table To verify the correct system charge prodeed as follows Ensure that no bubbles appear in the sight glass when operat ing the unit at full load for a while at a saturated condensing temperatu...

Page 28: ...rant R407C Depending on whether the leak occurs in the liquid or in the vapour phase the proportion of the different components in the remaining liquid is not the same NOTE Regularly carry out leak ch...

Page 29: ...4 51 04 28 75 63 67 67 64 10 22 12 27 77 19 5 46 77 51 55 29 64 07 68 02 10 25 22 94 28 56 19 75 47 29 52 05 29 25 64 47 68 39 12 4 Condenser coil We recommend that finned coils are inspected regularl...

Page 30: ...operations please refer to the paragraph on diagnostics and breakdowns of the 30RA RH 30RY RYH B Pro Dialog Plus controls manual IMPORTANT Before each equipment maintenance operation please ensure tha...

Page 31: ...ssors fans and pumps Check the compressor fan and pump winding status Mechanical checks Check the tightening of the fan tower fan compressor and control box fixing bolts Check that no water has penetr...

Page 32: ...Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has been sized and installed properly Unit ground wire h...

Page 33: ...050 to 240 3 50 litres nominal kW capacity for air conditioning 30RA 040 Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if req...

Page 34: ...this machine Once all checks have been made start the unit in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a whil...

Page 35: ...35...

Page 36: ...persedes order No 13435 76 04 2002 Manufactured by Carrier SA Montluel France Manufacturer reserves the right to change any product specificatiuons without notice Printed in the Netherlands Printed on...

Reviews: