background image

5

1.4 - Repair safety considerations

All installation parts must be maintained by the personnel in
charge, in order to avoid material deterioration and injuries to
people. Faults and leaks must be repaired immediately. The
authorized technician must have the responsibility to repair the
fault immediately. Each time repairs have been carried out to
the unit, the operation of the safety devices must be re-checked.

If a leak occurs or if the refrigerant becomes polluted (e.g. by a
short circuit in a motor) remove the complete charge using a
recovery unit and store the refrigerant in mobile containers
(careful in case the refrigerant decomposes due to high tempera-
ture increases, as the decomposition products are dangerous).

If a leak occurs, evacuate all refrigerant, repair the leak detected
and recharge the circuit with the total R407C charge, as
indicated on the unit name plate. Never top up the charge. Only
charge liquid refrigerant R407C at the liquid line.

The 30RA 040 to 240 units use R407C refrigerant. These
units are essentially sold in Europe, and their operating
range is limited to an outside air temperature of approxi-
mately 45°C.

Always ensure you are using the correct refrigerant type
before recharging the unit.

Charging any refrigerant other than the original charge type
(R407C) will impair machine operation and can even lead to
a destruction of the compressors. The compressors operating
with R407C are charged with a synthetic polyolester oil.

R407C units have a hermetic refrigerant circuit and the
original charge needs not be topped up, as R407C is a
zeotropic refrigerant.

Do not use oxygen to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease,
and other common substances.

Never exceed the specified maximum operating pressures.
Verify the allowable maximum high- and low-side test pres-
sures by checking the instructions in this manual and the
pressures given on the unit name plate.

Do not use air for leak testing. Use only refrigerant or dry
nitrogen.

Do not unweld or flamecut the refrigerant lines or any refri-
gerant circuit component until all refrigerant (liquid and
vapour) has been removed from chiller. Traces of vapour
should be displaced with dry air nitrogen. Refrigerant in
contact with an open flame produces toxic gases.

The necessary protection equipment must be available, and
appropriate fire extinguishers for the system and the
refrigerant type used must be within easy reach.

Do not siphon refrigerant.

1.3 - Maintenance safety considerations

Engineers working on the electric or refrigeration components
must be authorized and fully qualified to do so (electricians
trained and qualified in accordance with IEC 60364 Classi-
fication BA4).

All refrigerant circuit repairs must be carried out by a trained
person, fully qualified to work on these units. He must have
been trained and be familiar with the equipment and the
installation, and he must wear the necessary protective items
(gloves, glasses, protective clothes, safety shoes).

Soldering and welding: Component, piping and connection
soldering and welding operations must be carried out using the
correct procedures and by qualified operators. Pressurised
containers must not be subjected to shocks, nor to large
temperature variations during maintenance and repair operations.

Never work on a unit that is still energized.

Never work on any of the electrical components, until the
general power supply to the unit has been cut using the
disconnect switch in the control box.

If any maintenance operations are carried out on the unit,
lock the power supply circuit in the open position ahead of
the machine.

If the work is interrupted, always ensure that all circuits are
still deenergized before resuming the work.

ATTENTION: Even if the unit has been switched off, the
power circuit remains energized, unless the unit or circuit
disconnect switch is open. Refer to the wiring diagram for
further details. Attach appropriate safety labels.

Operating checks: During the life-time of the system,
inspection and tests must be carried out in accordance with
national regulations.

The information on operating inspections given in annex C of
standard EN378-2 can be used if no similar criteria exist in
the national regulations.

Safety device checks (annex C6 – EN378-2): The safety
devices must be checked on site once a year for safety devices
(high-pressure switches), and every five years for external
overpressure devices (safety globe valves).

Contact Carrier Service for a detailed explanation of the
high-pressure switch test method.

If the machine operates in a corrosive environment, inspect
the protection devices more frequently.

Regularly carry out leak tests and immediately repair any leaks.

Summary of Contents for 30RA040B

Page 1: ...Hz Installation operation and maintenance instructions AQUASNAP For the operation of the control please refer to the Pro Dialog Control manual for the 30RA RH RY RYH B series Carrier is participating...

Page 2: ...2 The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract...

Page 3: ...Control box 16 7 2 Power supply 17 7 3 Voltage phase imbalance 17 8 RECOMMENDEDWIRESECTIONS 18 8 1 Field control wiring 18 9 WATERCONNECTIONS 19 9 1 Operating precautions and recommendations 19 9 2 H...

Page 4: ...the unit In certain cases the globe stops are installed on ball valves These valves are factory supplied lead sealed in the open position This system permits isolating and removing the globe stop for...

Page 5: ...ntact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrigerant type used must be within easy r...

Page 6: ...ut by a qualified and authorised engineer These procedures must be carried out with the unit shut down NOTE The unit must never be left shut down with the liquid line valve closed as liquid refrigeran...

Page 7: ...ld always be protected against crushing while a unit is being moved Use struts or spreader bars to spread the slings above the unit Do not tilt a unit more than 15 WARNING Never push or lever on any o...

Page 8: ...s and arrangements are in place and comply with the current European standard Verify that all document for pressure containers certificates name plates files instruction manuals that are required docu...

Page 9: ...9 30RA 090 160 3 DIMENSIONS CLEARANCES 30RA 040 080 1081 1329 2071 1000 1000 1 2 1 2 1000 1000 2071 2278 1329 1000 1000 1000 1000 2 1 1 1 1 2...

Page 10: ...ct Power cable entry NOTE A Non certifieddrawings Refer to the certified dimensional drawings supplied with the unit or available on request when designing an installation For the location of fixing p...

Page 11: ...le 040 050 060 070 080 090 100 120 140 160 200 240 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit supply The control circuit is supplied via the unit mount...

Page 12: ...vely please order the special version from the factory by contacting your local Carrier dealer For unit sizes 200 and 240 the installation requires drilling a hole into the control box changing of the...

Page 13: ...l 30RA units are protected to IP44CW and fulfil this protectioncondition Electrical data notes 30RA 30RA 040 240 units have a single power connection point located at the main switch The control box i...

Page 14: ...recirculation of the evaporator water flow may take place leading to the risk of excessive fouling 6 4 Maximum evaporator water flow rate This is limited by the permitted evaporator pressure drop Also...

Page 15: ...outside air temperature Operating range with required anti freeze solution and special Pro Dialog controlconfiguration 6 6 Unit operating range at full and part load 6 7 Pressure drop in the plate hea...

Page 16: ...1 Main disconnect switch PE Earth connection S Power supply cable section see table Recommended wire sections X Disconnect switch position referred to the unit side Y Control box position referred to...

Page 17: ...ch position referred to the unit side Y Control box position referred to the unit base X mm Y mm 30RA 040 080 190 762 30RA 090 160 1415 762 30RA 200 240 1161 1107 NOTES The 30RA 040 240 units have onl...

Page 18: ...oltage drop to 5 length L in metres see table below IMPORTANT Before connection of the main power cables L1 L2 L3 on the terminal block it is imperative to check the correct order of the 3 phases befo...

Page 19: ...be recommended 10 pH Ideal case pH neutral at 20 25 C 7 pH 8 ATTENTION Charging adding or draining fluid from the water circuit must be done by qualified personnel using air vents and materials suitab...

Page 20: ...a bypass must be included as shown below Winter position Legend A Unit B Water network C Closed O Open A B O F F IMPORTANT Depending on the atmospheric conditions in your area you must do the followi...

Page 21: ...tion are equipped with a flow switch and an internal piping heater Legend Components of the unit and hydronic module 1 Victaulic screen filter 2 Expansion tank 3 Safety valve 4 Available pressure pump...

Page 22: ...ble for the installation to get it These characteristics can be obtained from the technical literature using the unit performance tables for a T of 5 K at the evaporator or with the Electronic Catalog...

Page 23: ...system has an excessive pressure drop in relation to the available static pressure provided by the pump the resulting water flow rate will de reduced and the difference between entering and leaving wa...

Page 24: ...RA080 100 3 30RA120 160 4 30RA200 240 Dual pumps 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 12 14 16 18 20 22 24 26 1 2 3 4 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 1...

Page 25: ...7 30RA 120 8 30RA 140 9 30RA 160 10 30RA 200 11 30RA 240 Dual pumps Legend 1 30RA 040 2 30RA 050 3 30RA 060 4 30RA 070 5 30RA 080 6 30RA 090 7 30RA 100 8 30RA 120 9 30RA 140 10 30RA 160 11 30RA 200 12...

Page 26: ...Ensure that all safety devices are satisfied especially the high pressure switches 11 3 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and...

Page 27: ...Data table To verify the correct system charge prodeed as follows Ensure that no bubbles appear in the sight glass when operat ing the unit at full load for a while at a saturated condensing temperatu...

Page 28: ...rant R407C Depending on whether the leak occurs in the liquid or in the vapour phase the proportion of the different components in the remaining liquid is not the same NOTE Regularly carry out leak ch...

Page 29: ...4 51 04 28 75 63 67 67 64 10 22 12 27 77 19 5 46 77 51 55 29 64 07 68 02 10 25 22 94 28 56 19 75 47 29 52 05 29 25 64 47 68 39 12 4 Condenser coil We recommend that finned coils are inspected regularl...

Page 30: ...operations please refer to the paragraph on diagnostics and breakdowns of the 30RA RH 30RY RYH B Pro Dialog Plus controls manual IMPORTANT Before each equipment maintenance operation please ensure tha...

Page 31: ...ssors fans and pumps Check the compressor fan and pump winding status Mechanical checks Check the tightening of the fan tower fan compressor and control box fixing bolts Check that no water has penetr...

Page 32: ...Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has been sized and installed properly Unit ground wire h...

Page 33: ...050 to 240 3 50 litres nominal kW capacity for air conditioning 30RA 040 Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if req...

Page 34: ...this machine Once all checks have been made start the unit in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a whil...

Page 35: ...35...

Page 36: ...persedes order No 13435 76 04 2002 Manufactured by Carrier SA Montluel France Manufacturer reserves the right to change any product specificatiuons without notice Printed in the Netherlands Printed on...

Reviews: