background image

19

9 - WATER CONNECTIONS

For size and position of the unit water inlet and outlet connec-
tions refer to the certified dimensional drawings supplied with
the unit. The water pipes must not transmit any radial or axial
force to the heat exchangers nor any vibration.

The water supply must be analysed and appropriate filtering,
treatment, control devices, shutoff and bleed valves and circuits
built in, to prevent corrosion (example: damage to the protection
of the tube surface if the fluid is polluted), fouling and deter-
ioration of the pump fittings.

Before any start-up verify that the heat exchange fluid is
compatible with the materials and the water circuit coating.

In case additives or other fluids than those recommended by
Carrier s.a are used, ensure that the fluids are not considered as
a gas, and that they belong to class 2, as defined in directive
97/23/EC.

Carrier s.a. recommendations on heat exchange fluids:
1.

No NH

4+

 ammonium ions in the water, they are very

detrimental for copper. This is one of the most important
factors for the operating life of copper piping. A content
of several tenths of mg/l will badly corrode the copper
over time.

2.

Cl

-

 Chloride ions are detrimental for copper with a risk of

perforations by corrosion by puncture. If possible keep
below 10 mg/l.

3.

SO

4

2-

 sulphate ions can cause perforating corrosion, if

their content is above 30 mg/l.

4.

No fluoride ions (<0.1 mg/l).

5.

No Fe

2+

 and Fe

3+

 ions with non negligible levels of

dissolved oxygen must be present. Dissolved iron < 5 mg/
l with dissolved oxygen < 5 mg/l.

6.

Dissolved silicon: silicon is an acid element of water and
can also lead to corrosion risks. Content < 1mg/l.

7.

Water hardness: TH >2.8 K. Values between 10 and 25
can be recommended. This will facilitate scale deposit that
can limit corrosion of copper. TH values that are too high
can cause piping blockage over time. A total alkalimetric
titre (TAC) below 100 is desirable.

8.

Dissolved oxygen: Any sudden change in water oxygen-
ation conditions must be avoided. It is as detrimental to
deoxygenate the water by mixing it with inert gas as it is
to over-oxygenate it by mixing it with pure oxygen. The
disturbance of the oxygenation conditions encourages
destabilisation of copper hydroxides and enlargement of
particles.

9.

Specific resistance – electric conductivity: the higher the
specific resistance, the slower the corrosion tendency.
Values above 3000 Ohm/cm are desirable. A neutral
environment  favours maximum specific resistance values.
For electric conductivity values in the order of 200-6000
S/cm can be recommended.

10. pH: Ideal case pH neutral at 20-25°C (7 < pH < 8).

ATTENTION: Charging, adding or draining fluid from the
water circuit must be done by qualified personnel, using air
vents and materials suitable for the products. The water
circuit charging devices are field-supplied.

Charging and removing heat exchange fluids should be done
with devices that must be included on the water circuit by the
installer. Never use the unit heat exchangers to add heat
exchange fluid.

9.1 - Operating precautions and recommendations

The water circuit should be designed to have the least number
of elbows and horizontal pipe runs at different levels. Below
the main points to be checked for the connection:

Comply with the water inlet and outlet connections shown
on the unit.

Install manual or automatic air purge valves at all high
points in the circuit.

Use an expansion device to maintain pressure in the
system and install a safety valve as well as an expansion
tank.
Units with a hydronic module include the safety valve and
the expansion tank.

Install thermometers in both the entering and leaving
water connections.

Install drain connections at all low points to allow the
whole circuit to be drained.

Install stop valves, close to the entering and leaving water
connections.

Use flexible connections to reduce the transmission of
vibrations.

Insulate all pipework, after testing for leaks, both to
reduce thermal leaks and to prevent condensation.

If the external unit water pipes are in an area, where the
ambient temperature is likely to fall below 0°C, insulate the
piping and add an electric heater. The internal unit piping
is protected down to -20°C.

NOTE: For units not equipped with a hydronic module a
screen filter must be installed as close to the heat exchanger
as possible, in a position that is easily accessible for removal
and cleaning. Units with hydronic module are equipped with
this type of filter.

The mesh size of the filter must be 1.2 mm.

The plate heat exchanger can foul up quickly at the initial
unit start-up, as it complements the filter function, and the
unit operation will be impaired (reduced water flow rate due
to increased pressure drop).

Before the system start-up verify that the water circuits are
connected to the appropriate heat exchangers (e.g. no
reversal between evaporator and condenser).

Do not introduce any significant static or dynamic pressure
into the heat exchange circuit (with regard to the design
operating pressures).

The products that may be added for thermal insulation of the
containers during the water piping connection procedure
must be chemically neutral in relation to the materials and
coatings to which they are applied. This is also the case for
the products originally supplied by Carrier s.a.

Summary of Contents for 30RA040B

Page 1: ...Hz Installation operation and maintenance instructions AQUASNAP For the operation of the control please refer to the Pro Dialog Control manual for the 30RA RH RY RYH B series Carrier is participating...

Page 2: ...2 The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract...

Page 3: ...Control box 16 7 2 Power supply 17 7 3 Voltage phase imbalance 17 8 RECOMMENDEDWIRESECTIONS 18 8 1 Field control wiring 18 9 WATERCONNECTIONS 19 9 1 Operating precautions and recommendations 19 9 2 H...

Page 4: ...the unit In certain cases the globe stops are installed on ball valves These valves are factory supplied lead sealed in the open position This system permits isolating and removing the globe stop for...

Page 5: ...ntact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrigerant type used must be within easy r...

Page 6: ...ut by a qualified and authorised engineer These procedures must be carried out with the unit shut down NOTE The unit must never be left shut down with the liquid line valve closed as liquid refrigeran...

Page 7: ...ld always be protected against crushing while a unit is being moved Use struts or spreader bars to spread the slings above the unit Do not tilt a unit more than 15 WARNING Never push or lever on any o...

Page 8: ...s and arrangements are in place and comply with the current European standard Verify that all document for pressure containers certificates name plates files instruction manuals that are required docu...

Page 9: ...9 30RA 090 160 3 DIMENSIONS CLEARANCES 30RA 040 080 1081 1329 2071 1000 1000 1 2 1 2 1000 1000 2071 2278 1329 1000 1000 1000 1000 2 1 1 1 1 2...

Page 10: ...ct Power cable entry NOTE A Non certifieddrawings Refer to the certified dimensional drawings supplied with the unit or available on request when designing an installation For the location of fixing p...

Page 11: ...le 040 050 060 070 080 090 100 120 140 160 200 240 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit supply The control circuit is supplied via the unit mount...

Page 12: ...vely please order the special version from the factory by contacting your local Carrier dealer For unit sizes 200 and 240 the installation requires drilling a hole into the control box changing of the...

Page 13: ...l 30RA units are protected to IP44CW and fulfil this protectioncondition Electrical data notes 30RA 30RA 040 240 units have a single power connection point located at the main switch The control box i...

Page 14: ...recirculation of the evaporator water flow may take place leading to the risk of excessive fouling 6 4 Maximum evaporator water flow rate This is limited by the permitted evaporator pressure drop Also...

Page 15: ...outside air temperature Operating range with required anti freeze solution and special Pro Dialog controlconfiguration 6 6 Unit operating range at full and part load 6 7 Pressure drop in the plate hea...

Page 16: ...1 Main disconnect switch PE Earth connection S Power supply cable section see table Recommended wire sections X Disconnect switch position referred to the unit side Y Control box position referred to...

Page 17: ...ch position referred to the unit side Y Control box position referred to the unit base X mm Y mm 30RA 040 080 190 762 30RA 090 160 1415 762 30RA 200 240 1161 1107 NOTES The 30RA 040 240 units have onl...

Page 18: ...oltage drop to 5 length L in metres see table below IMPORTANT Before connection of the main power cables L1 L2 L3 on the terminal block it is imperative to check the correct order of the 3 phases befo...

Page 19: ...be recommended 10 pH Ideal case pH neutral at 20 25 C 7 pH 8 ATTENTION Charging adding or draining fluid from the water circuit must be done by qualified personnel using air vents and materials suitab...

Page 20: ...a bypass must be included as shown below Winter position Legend A Unit B Water network C Closed O Open A B O F F IMPORTANT Depending on the atmospheric conditions in your area you must do the followi...

Page 21: ...tion are equipped with a flow switch and an internal piping heater Legend Components of the unit and hydronic module 1 Victaulic screen filter 2 Expansion tank 3 Safety valve 4 Available pressure pump...

Page 22: ...ble for the installation to get it These characteristics can be obtained from the technical literature using the unit performance tables for a T of 5 K at the evaporator or with the Electronic Catalog...

Page 23: ...system has an excessive pressure drop in relation to the available static pressure provided by the pump the resulting water flow rate will de reduced and the difference between entering and leaving wa...

Page 24: ...RA080 100 3 30RA120 160 4 30RA200 240 Dual pumps 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 12 14 16 18 20 22 24 26 1 2 3 4 50 75 100 125 150 175 200 225 250 275 300 325 0 2 4 6 8 10 1...

Page 25: ...7 30RA 120 8 30RA 140 9 30RA 160 10 30RA 200 11 30RA 240 Dual pumps Legend 1 30RA 040 2 30RA 050 3 30RA 060 4 30RA 070 5 30RA 080 6 30RA 090 7 30RA 100 8 30RA 120 9 30RA 140 10 30RA 160 11 30RA 200 12...

Page 26: ...Ensure that all safety devices are satisfied especially the high pressure switches 11 3 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and...

Page 27: ...Data table To verify the correct system charge prodeed as follows Ensure that no bubbles appear in the sight glass when operat ing the unit at full load for a while at a saturated condensing temperatu...

Page 28: ...rant R407C Depending on whether the leak occurs in the liquid or in the vapour phase the proportion of the different components in the remaining liquid is not the same NOTE Regularly carry out leak ch...

Page 29: ...4 51 04 28 75 63 67 67 64 10 22 12 27 77 19 5 46 77 51 55 29 64 07 68 02 10 25 22 94 28 56 19 75 47 29 52 05 29 25 64 47 68 39 12 4 Condenser coil We recommend that finned coils are inspected regularl...

Page 30: ...operations please refer to the paragraph on diagnostics and breakdowns of the 30RA RH 30RY RYH B Pro Dialog Plus controls manual IMPORTANT Before each equipment maintenance operation please ensure tha...

Page 31: ...ssors fans and pumps Check the compressor fan and pump winding status Mechanical checks Check the tightening of the fan tower fan compressor and control box fixing bolts Check that no water has penetr...

Page 32: ...Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has been sized and installed properly Unit ground wire h...

Page 33: ...050 to 240 3 50 litres nominal kW capacity for air conditioning 30RA 040 Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if req...

Page 34: ...this machine Once all checks have been made start the unit in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a whil...

Page 35: ...35...

Page 36: ...persedes order No 13435 76 04 2002 Manufactured by Carrier SA Montluel France Manufacturer reserves the right to change any product specificatiuons without notice Printed in the Netherlands Printed on...

Reviews: