Summary of Contents for 30GX080-176

Page 1: ...ully unloaded condition The accessory provides more precise control of leaving fluid temperature during light load conditions The 30GX and 30HX chillers have a dual circuit design Each minimum load co...

Page 2: ...t braze nipple on discharge line located between oil separator and con denser Remove plug from minimum load port on cooler shell See Fig 1 Using thread sealant install Swagelok fitting in minimum load...

Page 3: ...bottoms out tighten the compression nut finger tight while holding the fitting body Use backup wrench to hold fitting body and tighten compression nut another 11 4 turns IMPORTANT Do NOT overtighten t...

Page 4: ...ncluded with this kit in the position shown on the 30GX chiller in Fig 3 Route the waterproof conduit included with this kit between the accessory junction box and the factory installed junction box S...

Page 5: ...30GX080 176 30HX076 271 LEGEND MLC Minimum Load Control TB Terminal Block NOTE See Fig 3 for locations of junction boxes on unit Fig 4 Minimum Load Control Wiring 5...

Page 6: ...electrical connec tions for proper location and tightness For 30HX units re place and secure the access panels for the unit control box For 30GX units secure the junction box covers to the junc tion...