Step 4 — Install Control Wiring

Be sure all power to the unit is off before proceeding.
Lock out and safety-tag all disconnects.

Wires between field-installed components and unit control

box must be enclosed in field-supplied conduit. Follow all
local codes and NEC (National Electrical Code, U.S.A.). Wire
size must be no. 16 AWG (American Wire Gage) (1.5 mm

2

)

minimum. See Fig. 4 for field wiring.

30HX UNITS — Remove the screws holding the right-side
access panel to the unit control box. Remove the right-side
access panel and store in a safe area.

Route wires through field-supplied conduit and attach the

conduit to the unit control box, using a suitable conduit fit-
ting and one of the available

7

8

-in. knockout openings. At-

tach the other end of the conduit to the solenoid valve, using
a suitable fitting. Repeat for the other circuit.

30GX UNITS — Install the accessory junction box included
with this kit in the position shown on the 30GX chiller in
Fig. 3. Route the waterproof conduit included with this kit
between the accessory junction box and the factory-installed
junction box. See Fig. 3 and 4. Route field-supplied conduits
from the solenoid valves to the accessory junction box.

ALL UNITS — Using good wiring practice, connect a white
wire from the solenoid valve on circuit A to a white wire
from the solenoid valve on circuit B. Connect both wires to
the white wire in the factory-installed junction box (30GX),
or unit wiring harness labelled ‘‘MLC-A & B’’ (30HXA, HXC).

Connect a pink wire from the solenoid valve on circuit A

to the pink wire in the factory-installed junction box (30GX),
or unit wiring harness labelled MLC-A (30HXA, HXC).

Connect a gray wire from the solenoid valve on circuit B

to the gray wire in the factory-installed junction box (30GX),
or unit wiring harness labelled MLC-B (30HXA, HXC).

Figure 4 shows the correct wiring for the minimum load

control and the location of the wiring connection points on
the chiller.

Fig. 3 — Installing Valves, 30GX

4

Summary of Contents for 30GX080-176

Page 1: ...ully unloaded condition The accessory provides more precise control of leaving fluid temperature during light load conditions The 30GX and 30HX chillers have a dual circuit design Each minimum load co...

Page 2: ...t braze nipple on discharge line located between oil separator and con denser Remove plug from minimum load port on cooler shell See Fig 1 Using thread sealant install Swagelok fitting in minimum load...

Page 3: ...bottoms out tighten the compression nut finger tight while holding the fitting body Use backup wrench to hold fitting body and tighten compression nut another 11 4 turns IMPORTANT Do NOT overtighten t...

Page 4: ...ncluded with this kit in the position shown on the 30GX chiller in Fig 3 Route the waterproof conduit included with this kit between the accessory junction box and the factory installed junction box S...

Page 5: ...30GX080 176 30HX076 271 LEGEND MLC Minimum Load Control TB Terminal Block NOTE See Fig 3 for locations of junction boxes on unit Fig 4 Minimum Load Control Wiring 5...

Page 6: ...electrical connec tions for proper location and tightness For 30HX units re place and secure the access panels for the unit control box For 30GX units secure the junction box covers to the junc tion...

Page 7: ......

Page 8: ...ufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 Tab 5c PC 903 Catalog No 563 056 Printed in U S A Fo...

Reviews: