background image

7

Once defrost termination conditions have been met, the following
sequence will occur: The compressor will be de--energized for

approximately 1 minute, then the reversing valve will be
de--energized. A few seconds later, the compressor will be

re--energized and the normal heating cycle starts.

Defrost

The defrost control is a time/temperature control which has field

selectable settings of 30, 60, 90, or 120 minutes, factory set to 90
minutes. These settings represent the amount of time that must pass

after closure of the defrost thermostat before the defrost sequence

begins.
The defrost thermostat senses coil temperature throughout the

heating cycle. When the coil temperature reaches the defrost
thermostat setting of approximately 32

_

F (0

_

C), it will close,

which energizes the DFT terminal and begins the defrost timing

sequence. When the DFT has been energized for the selected time,

the defrost cycle begins. Defrost cycle is terminated when defrost
thermostat opens, or automatically after 10 minutes.

Defrost Speedup

To initiate a forced defrost, speedup pins (J1) must be shorted with

a flat head screwdriver for 5 seconds and

RELEASED

. If the

defrost thermostat is open, a short defrost cycle will be observed
(actual length depends on Quiet Shift--2 switch position). When

Quiet Shift--2 is off, only a short 30 second defrost cycle is
observed. With Quiet Shift--2 ON, the speedup sequence is

approximately 3 minutes; 1 minute compressor off period followed

by 30 seconds of defrost with compressor operation. When
returning to heating mode, the compressor will turn off for an

additional 1 minute.
If the defrost thermostat is closed, a complete defrost cycle is

initiated. If the Quiet Shift--2 switch is turned on, the compressor

will be turned off for two 1 minute intervals as explained
previously.

OF2

OF1

ON

QUIET
SHIFT

120

30

60

60

30

90

INTERVAL  TIMER OFF

P3

DFT

O   R   W

2

   Y   C

T2 C  C  O

DFT

T1

Y

P1

J1

SPEEDUP

A05378

Fig. 11 – Defrost Control HK32EA008

A170130

Fig. 12 – Defrost Control HK32EA010

Table 4 – Defrost Control Speedup–Timing Sequence

PARAMETER

MINIMUM

(MINUTES)

MAXIMUM

(MINUTES)

SPEEDUP

(NOMINAL)

30–minute cycle

27

33

7 sec

50–minute cycle

45

55

12 sec

90–minute cycle

81

99

21 sec

10–minute cycle

9

11

2 sec

5 minutes

4.5

5.5

1 sec

Summary of Contents for 25HPB6

Page 1: ...suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing o...

Page 2: ...ications Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219...

Page 3: ...rements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuat...

Page 4: ...valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE...

Page 5: ...hrough power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The u...

Page 6: ...tem caps after system is opened to refrigerant flow back seated Replace caps finger tight and tighten with wrench an additional 1 12 turn 3 Close electrical disconnects to energize system 4 Set room t...

Page 7: ...up To initiate a forced defrost speedup pins J1 must be shorted with a flat head screwdriver for 5 seconds and RELEASED If the defrost thermostat is open a short defrost cycle will be observed actual...

Page 8: ...r temperature is below 70_F 21 11_C or the outdoor temperature is not in the favorable range adjust charge for line set length above or below 15ft 4 57 m only Charge level should then be appropriate f...

Page 9: ...MANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 005L 3 FX4DN B F 061L 3 FPMBN 024 FPMAN 030 FFM...

Page 10: ...psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatib...

Reviews: