background image

9

24 VAC HOT

R

C

W2

Y

G

R

C

RVS COOLING

C

W2

HP THERMOSTAT

 TYPICAL

FAN COIL

HEAT 

PUMP

G

O

E

W2

E

W3

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT

STAGE 1

INDOOR FAN

EMERGENCY

HEAT

O

*
*
*

 IF AVAILABLE

*

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

A02325 / A97413

Fig. 10

---

Generic Wiring Diagrams

(See Thermostat Installation Instructions for specific unit

combinations)

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is
energized.

Cooling

On a call for cooling, thermostat makes circuits R--O and R--Y,

and R--G. Circuit R--O energizes reversing valve, switching it to
cooling position. Circuit R--Y energizes contactor, starting

outdoor fan motor and compressor circuit. R--G energizes indoor
unit blower relay, starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de--energizing

contactor and blower relay. Compressor and motors should stop.

NOTE

: If indoor unit is equipped with a time--delay relay

circuit, the indoor blower will run an additional 90 seconds to
increase system efficiency.

Heating

On a call for heating, thermostat makes circuits R--Y and R--G.

Circuit R--Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R--G energizes indoor blower relay, starting

blower motor on high speed.
Should temperature continue to fall, R--W2 is made through

second--stage room thermostat. Circuit R--W2 energizes a relay,

bringing on first bank of supplemental electric heat and providing
electrical potential to second heater relay (if used). If outdoor

temperature falls below setting of outdoor thermostat (field
installed option), contacts close to complete circuit and bring on

second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de--energizing
contactor and relay. All heaters and motors should stop.

Defrost

The defrost control is a time/temperature control which includes a

field selectable (quick--connects located at board edge) time
period between defrost cycles (30, 60, or 90 minutes), factory set

to 90 minutes.
The electronic defrost timer sequence is enabled when the T1

input on the board is energized. The timer starts only when the

defrost thermostat is closed and the contactor is energized.
Defrost mode is identical to cooling mode except that outdoor fan

motor stops and second--stage heat is turned on to continue
warming conditioned spaces.
To initiate defrost, the defrost thermostat must be closed. This can

be accomplished as follows:

1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control

board, see Fig. 11. Tape lead to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate

on outdoor coil.

4. After a few minutes in heating mode, liquid line

temperature should drop below closing point of defrost
thermostat (approximately 30

°

F).

5. Short between speedup terminals with a flat--blade

screwdriver. This reduces the timing sequence to 1/256th
of original time. (See Table 4.)

6. When you hear reversing valve change position, remove

screwdriver immediately; otherwise, control will terminate
normal 10--minute defrost cycle in approximately 2

seconds.

NOTE

: Length of defrost cycle is dependent upon length of time

it takes to remove screwdriver from test pins after reversing valve
has shifted.

7. Unit will remain in defrost for remainder of defrost cycle

time or until defrost thermostat reopens at approximately
65

°

F coil temperature of liquid line.

8. Turn off power to outdoor unit and reconnect fan motor

lead to OF2 on control board.

25H

B

R

Summary of Contents for 25HBR

Page 1: ...LLATION RECOMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Chec...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...ve roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating...

Page 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Page 5: ...ciency Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on liquid service valve Use refrige...

Page 6: ...ing Set lengths between 80 and 200 ft horizontal or 20 ft vertical differential 250 ft Total Equivalent Length refer to the Longline Guideline Air Conditioners and Heat Pumps using R 22 IMPORTANT Chec...

Page 7: ...t must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance...

Page 8: ...Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury Wear safety glasses protective clothing and gloves when handling refrigerant and observe the following S...

Page 9: ...to complete circuit and bring on second bank of supplemental electric heat When thermostat is satisfied its contacts open de energizing contactor and relay All heaters and motors should stop Defrost T...

Page 10: ...an indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on ou...

Page 11: ...11...

Page 12: ...10 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HBR 2SI Replaces 25HBR 1SI P...

Reviews: