background image

5

Outdoor units may be connected to indoor section using
accessory tubing package or field--supplied refrigerant grade

tubing of correct size and condition. For tubing requirements
beyond 80 ft, substantial capacity and performance losses can

occur. Following the recommendations in the Application

Guideline and Service Manual--Residential Split--System Air
Conditioners and Heat Pumps will reduce these losses. Refer to

Table 1 for accessory requirements. Refer to Table 2 for field
tubing diameters.
There are no buried--line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY
APPROVED INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for

operation with approved ARI rated indoor unit when connected
by 15 ft of field--supplied or factory--accessory tubing, and

factory supplied filter drier. Check refrigerant charge for
maximum efficiency.

Refrigerant Tubing and Sweat Connections

Connect vapor tube to fitting on outdoor unit vapor service

valves (see Table 2). Connect liquid tubing to adapter tube on
liquid service valve. Use refrigerant grade tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat--sinking

material such as a wet cloth while brazing.

Remove plastic retainer holding outdoor piston in liquid service
valve, leaving the piston and piston retainer inside the valve.

Connect sweat/flare adapter provided, to valve. (See Fig. 6.)
Connect refrigerant tubing to fittings on outdoor unit vapor and

liquid service valves. Service valves are closed from factory and
ready for brazing. After wrapping service valve with a wet cloth,

tubing set can be brazed to service valve using either silver

bearing or non--silver bearing brazing material. Do not use soft
solder (materials which melt below 800

°

F). Consult local code

requirements. Refrigerant tubing and indoor coil are now ready
for leak testing. This check should include all field and factory

joints.

PISTON BODY

PISTON

PISTON
RETAINER

SWEAT/FLARE ADAPTER

A05226

Fig. 6

---

Liquid Service Valve

25H

B

R

Summary of Contents for 25HBR

Page 1: ...LLATION RECOMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Chec...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...ve roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating...

Page 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Page 5: ...ciency Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on liquid service valve Use refrige...

Page 6: ...ing Set lengths between 80 and 200 ft horizontal or 20 ft vertical differential 250 ft Total Equivalent Length refer to the Longline Guideline Air Conditioners and Heat Pumps using R 22 IMPORTANT Chec...

Page 7: ...t must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance...

Page 8: ...Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury Wear safety glasses protective clothing and gloves when handling refrigerant and observe the following S...

Page 9: ...to complete circuit and bring on second bank of supplemental electric heat When thermostat is satisfied its contacts open de energizing contactor and relay All heaters and motors should stop Defrost T...

Page 10: ...an indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on ou...

Page 11: ...11...

Page 12: ...10 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HBR 2SI Replaces 25HBR 1SI P...

Reviews: