14
A08060
A08057
Edge Thermidistat Models TP---PRH---01 & TP---NRH---01
w/ Fan Coil & 2---Stage Air Conditioner
Edge Thermidistat Models TP---PRH---01 & TP---NRH---01
w/ Furnace & 2---Stage Air Conditioner
RVS/Heat Stage 2
O/W2/B
Heat Stage 1
W/W1
Compressor Low
Y1
Compressor High
Y/Y2
Fan
G
24VAC Hot Heating
Rh
24VAC Hot Cooling
Rc
Dry Contact 1
D1
Dry Contact 2
D2
24VAC Common
C
Humidify
HUM
Outdoor Air Temp
OAT
Remote Room Sensor
RRS
OAT/RRS Return
SRTN
SRTN
Outdoor Sensor
Humidifier Solenoid
Valve
Remote Room
Sensor
O
Y1
W1
G
W2
C
Y2
R
Y1
Y/Y2
R
C
DH
REMOVE J2
JUMPER FOR
HEAT STAGING
REMOVE J1 FOR
DEHUMIDIFY
MODES
Two-Stage
Air Conditioner
Thermidistat
Variable Speed
Fan Coil
RVS/Heat Stage 2
O/W2/B
W2
Heat Stage 1
W/W1
W1
Compressor Low
Y1
Y1
Y1
Compressor High
Y/Y2
Y/Y2
Y2
Fan
G
G
24VAC Hot Heating
Rh
R
R
24VAC Hot Cooling
Rc
Dry Contact 1
D1
Dry Contact 2
D2
DHUM
24VAC Common
C
COM
C
Humidify
HUM
Outdoor Air Temp
OAT
Remote Room Sensor
RRS
OAT/RRS Return
SRTN
SRTN
Outdoor Sensor
Humidifier Solenoid
Valve
Remote Room
Sensor
THERMIDISTAT
VARIABLE SPEED
FURNACE
TWO-STAGE
AIR CONDITIONER
A09338
Thermidistat Model TP---PRH---01 or TP---NRH---01
w/ VS Furnace & 2---Stage Air Conditioner
Variable Speed
Furnace
Thermidistat
2-Stage
Air Conditioner
Heat Stage 2
O/B W2
W2
Heat Stage 1
W/W1
W1
Cool Stage 1
Y1 / W2
Y1
Cool Stage 2
Y/Y2
Y/Y2
Y/Y2
Fan
G
G
24VAC Hot Heating
Rh
R
R
24VAC Hot Cooling
Rc
Dry Contact 1
D1
Dry Contact 2
D2
DHUM
24VAC Common
C
COM
C
Humidify
HUM
Outdoor Air Temp
OAT
Remote Room Sensor
RRS
OAT/RRS Com
SRTN
Outdoor Sensor *
Humidifier Solenoid
Valve *
Remote Room
Sensor *
* Indicates connection may not be required / available.
LEGEND
24 VOLT FACTORY WIRING
24 VOLT FIELD WIRING
FIELD SPLICE CONNECTION
RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT
HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)
AIRFLOW SELECTOR
R1
H
AFS
A02005
Fig. 10 -- Thermidistat Wiring with 2--Stage Puron refrigerant Air Conditioner
24AN
A