background image

9

Check Charge

All 24ANA units must be charged in high stage only.

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be
favorable for subcooling charging. Favorable conditions exist

when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15 ft (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line
above or below 15 ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft /24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to
drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) only. Charge level should then

be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor
and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than

20 ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

TROUBLESHOOTING

Systems Communication Failure

If communication with the Infinity Control is lost with the user
interface, the control will flash the appropriate fault code. (See

Table 6) Check the wiring to the User Interface, indoor and

outdoor units.

Model Plug

Each control board contains a model plug. The correct model plug

must be installed for or the system to operate properly. (See Table

4.)
The model plug is used to identify the type and size of unit to the

control. On 24ANA7 models, the model plug is also used to
determine the start sequence timing for each individual model.
On new units, the model and serial numbers are input into the

board’s memory at the factory. If a model plug is lost or missing at
initial installation, the unit will operate according to the

information input at the factory and the appropriate error code will
flash temporarily. An RCD replacement board contains no model

and serial information. If the factory control board fails, the model
plug must be transferred from the original board to the replacement

board for the unit to operate.

NOTE

:

The model plug takes priority over factory model

information input at the factory. If the model plug is removed after
initial power up, the unit will operate according to the last valid
model plug installed, and flash the appropriate fault code
temporarily.

Table 4 – Model Plug Information

MODEL

NUMBER

MODEL PLUG

NUMBER

PIN RESISTANCE

(K---ohms)

Pins 1---4

Pins 2---3

24ANA724

HK70EZ001

5.1

11

24ANA736

HK70EZ003

5.1

24

24ANA748

HK70EZ005

5.1

39

24ANA760

HK70EZ007

5.1

62

24ANA124

HK70EZ009

5.1

91

24ANA136

HK70EZ011

5.1

150

24ANA148

HK70EZ013

5.1

220

24ANA160

HK70EZ015

5.1

360

Pressure Switch Protection

The outdoor unit is equipped with high-- and low--pressure

switches. If the control senses the opening of a high or low
pressure switch, it will respond as follows:

1. De--energize the appropriate compressor contactor,
2. Keep the outdoor fan operating for 15 minutes,
3. Display the appropriate fault code (see Table 6).
4. After a 15 minute delay, if there is still a call for cooling and

the LPS or HPS is reset, the appropriate compressor contac-
tor is energized.

5. If LPS or HPS has not closed after a 15 minute delay, the

outdoor fan is turned off. If the open switch closes anytime
after the 15--minute delay, then resume operation with a call

for cooling.

6. If LPS or HPS trips 3 consecutive cycles, the unit operation

is locked out for 4 hours.

7. In the event of a high pressure switch trip or high pressure

lockout, check the refrigerant charge outdoor fan operation

and outdoor coil for airflow restrictions.

8. In the event of a low pressure switch trip or low pressure

lockout, check the refrigerant charge and indoor airflow.

Control Fault

If the outdoor unit control board has failed, the control will flash

the appropriate fault code. (See Table 6) The control board should
be replaced.

Brown Out Protection

If the line voltage is less than 187v for at least 4 seconds, the

appropriate compressor contactor and fan relay are de--energized.
Compressor and fan operation are not allowed until voltage is a

minimum of 190v. The control will flash the appropriate fault

code (see Table 6).

230v Brown--Out Protection Defeated

The brownout feature can be defeated if needed for severe noisy

power conditions. This defeat should always be a last resort to
solving the problem. Defeat is available on the User Interface

setup screen (available with SYSTXCCUID01--C UI) or can be

initiated through the forced defrost pins for non--communicating
systems as follows:
The brownout toggle is accomplished by shorting the defrost pins
from power up with the OAT and OCT sensor connector removed.

After 3 seconds, the status of the force defrost short and the

OAT/OCT as open will be checked. If correct, then the brownout
will be toggled.

S

Status code 6 shows the brownout is disabled.

S

Status code 5 shows the brownout is active.

After the brownout defeat is set, power down and reinstall the
OAT/OCT sensor and remove the short from the forced defrost

pins. As long as the short on the forced defrost remains, the OAT
and OCT faults will not be cleared. The code will continue to be

flashed.

24AN

A

Summary of Contents for 24ANA1 Infinity

Page 1: ...cognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazard...

Page 2: ...llation Specifications for this unit in residential new construction market require the outdoor unit indoor unit refrigerant tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Application Guideline and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for ...

Page 3: ...d tubing diameters Refer to Table 2 for accessory requirements There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for op...

Page 4: ...r CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Installation of filter drier in liquid line is required Refer to Fig 3 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor co...

Page 5: ...m unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if ...

Page 6: ... board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections This fan coil has an adjustable blower off delay factory set at 90 sec for high and low stage blower operation For other combinations of equipment consult the Product Data Sheet START UP CAUTION UNIT OPERATION AND SAFETY HAZARD Failure to follow...

Page 7: ...ht on the outdoor board see Fig 6 indicates successful communication with the other system products The green LED will remain OFF until communications is established Once a valid command is received the green LED will turn ON continuously If no communication is received within 2 minutes the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light i...

Page 8: ...s Table 3 Outdoor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 24ANA124 9 57 10 88 11 90 24ANA136 9 06 10 23 11 90 24ANA148 9 91 11 04 11 90 24ANA160 10 83 11 70 11 90 NOTE For 24ANA1 models in low ambient cooling the PWM output for both high and low stage equals the value for low stage operation below 55_F 1...

Page 9: ...r the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriate fault code temporarily Table 4 Model Plug Information MODEL NUMBER MODEL PLUG NUMBER PIN RESISTANCE K ohms Pins 1 4 Pins 2 3 24ANA724 HK70EZ00...

Page 10: ... Contactor Open 24ANA7 models No 230V at Compressor 24ANA1 models If the compressor voltage is not sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 24ANA7 Models Only Compressor Start Detection In low stage if the specified start voltage a...

Page 11: ...rload attached to motor windings Compressor Control Contactors The contactor s have a 24 volt coil The electronic control board controls the operation of the appropriate contactors TEMPERATURE THERMISTORS Thermistors are electronic devices which sense temperature As the temperature increases the resistance decreases Thermistors are used to sense outdoor ambient OAT and coil temperature OCT Refer t...

Page 12: ... that all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Users Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing h...

Page 13: ...nd exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed high stage Ther mal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage s...

Page 14: ...M 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Return SRTN SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor THERMIDISTAT VARIABLE SPEED FURNACE TWO STAGE AIR CONDITIONER A09338 Thermidistat Model TP PRH 01 or TP NRH 01 w VS Furnace 2 Stage Air Conditioner Variable Speed Furnace Thermidistat 2 Stage Air Conditioner Heat Stage 2 O B W2 W2 Heat...

Page 15: ...le with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plas...

Page 16: ... W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANA 6SI Replaces 24ANA 5SI 24ANA ...

Reviews: