System Functions And Sequence Of Operation

The outdoor unit control system has special functions. The
following is an overview of the 2--stage control functions:

Cooling Operation

24ANA7 and 24ANA1 (containing circuit board HK38EA015 or

newer) models utilize either a 2--stage cooling indoor thermostat or
an Infinity communicating User Interface. With a call for first

stage cooling, the outdoor fan and low--stage compressor are
energized. If low--stage cannot satisfy cooling demand, high--stage

is energized by the second stage of indoor thermostat or User

Interface. After second stage is satisfied, the unit returns to
low--stage operation until first stage is satisfied or until second

stage is required again. When both first stage and second stage
cooling are satisfied, the compressor will shut off.

NOTE

: On 24ANA7 models, if unit has not operated within the

past 12 hrs, or following a unit power--up, upon the next
thermostat high-- or low--stage demand, unit operates for a
minimum of 5 minutes in high--stage.

NOTE

: With non--communicating (non--Infinity) systems, with

first stage of cooling, (Y1) is powered on; and with second stage of
cooling, (Y1 and Y2) are on.

NOTE

: When 2--stage unit is operating at low--stage, system

vapor (suction) pressure will be higher than a standard
single--stage system or high--stage operation.

NOTE

: Outdoor fan motor will continue to operate for one

minute after compressor shuts off, when outdoor ambient is greater
than or equal to 100

_

F (37.78

_

C).

This reduces pressure

differential for easier starting on the next cycle.

Communication and Status Function Lights

For Infinity Control Only, Green communications (COMM)

Light

A green LED

(COMM light)

on the outdoor board (see Fig. 6)

indicates successful communication with the other system

products. The green LED will remain OFF until communications is
established. Once a valid command is received, the green LED will

turn ON continuously. If no communication is received within 2
minutes, the LED will be turned OFF until the next valid

communication.

Amber Status Light

An amber colored

STATUS light

is used to display the operation

mode and fault codes as specified in the troubleshooting section.
See Table 6 for codes and definitions.

NOTE

: Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority).

Utility Interface

With Infinity Control

The utility curtailment relay should be wired between R and Y2

connections on the control board for Infinity Communicating

Systems only (see Fig. 6.) This input allows a power utility device
to interrupt compressor operation during peak load periods. When

the utility sends a signal to shut the system down, the User
Interface will display, “Curtailment Active”.

One Minute Stage Change Time Delay on 24ANA7

Models

When compressor changes stages from high to low or low to high,

there is a 1--minute time delay before compressor restarts. The

outdoor fan motor remains running.

Compressor Operation on 24ANA7 Models

When the compressor operates in high--stage operation, the motor

rotates clockwise. Both the lower and upper pistons are eccentric
with the rotating crankshaft and both compress refrigerant.
When the compressor operates in low--stage operation the motor

reverses direction (rotates counterclockwise). The lower piston
becomes idle and the upper piston compresses refrigerant.

The

start and run windings are reversed.

UTILITY RELAY  

*

UTILITY SIGNAL

OPEN RELAY

*

 SUPPLIED BY UTILITY PROVIDER

LLS

Liquid Line Solenoid

MODEL 
PLUG

A06526

Fig. 6 -- 2--Stage Control Board

24AN

A

Summary of Contents for 24ANA1 Infinity

Page 1: ...cognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazard...

Page 2: ...llation Specifications for this unit in residential new construction market require the outdoor unit indoor unit refrigerant tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Application Guideline and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for ...

Page 3: ...d tubing diameters Refer to Table 2 for accessory requirements There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for op...

Page 4: ...r CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Installation of filter drier in liquid line is required Refer to Fig 3 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor co...

Page 5: ...m unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if ...

Page 6: ... board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections This fan coil has an adjustable blower off delay factory set at 90 sec for high and low stage blower operation For other combinations of equipment consult the Product Data Sheet START UP CAUTION UNIT OPERATION AND SAFETY HAZARD Failure to follow...

Page 7: ...ht on the outdoor board see Fig 6 indicates successful communication with the other system products The green LED will remain OFF until communications is established Once a valid command is received the green LED will turn ON continuously If no communication is received within 2 minutes the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light i...

Page 8: ...s Table 3 Outdoor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 24ANA124 9 57 10 88 11 90 24ANA136 9 06 10 23 11 90 24ANA148 9 91 11 04 11 90 24ANA160 10 83 11 70 11 90 NOTE For 24ANA1 models in low ambient cooling the PWM output for both high and low stage equals the value for low stage operation below 55_F 1...

Page 9: ...r the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriate fault code temporarily Table 4 Model Plug Information MODEL NUMBER MODEL PLUG NUMBER PIN RESISTANCE K ohms Pins 1 4 Pins 2 3 24ANA724 HK70EZ00...

Page 10: ... Contactor Open 24ANA7 models No 230V at Compressor 24ANA1 models If the compressor voltage is not sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 24ANA7 Models Only Compressor Start Detection In low stage if the specified start voltage a...

Page 11: ...rload attached to motor windings Compressor Control Contactors The contactor s have a 24 volt coil The electronic control board controls the operation of the appropriate contactors TEMPERATURE THERMISTORS Thermistors are electronic devices which sense temperature As the temperature increases the resistance decreases Thermistors are used to sense outdoor ambient OAT and coil temperature OCT Refer t...

Page 12: ... that all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Users Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing h...

Page 13: ...nd exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed high stage Ther mal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage s...

Page 14: ...M 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Return SRTN SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor THERMIDISTAT VARIABLE SPEED FURNACE TWO STAGE AIR CONDITIONER A09338 Thermidistat Model TP PRH 01 or TP NRH 01 w VS Furnace 2 Stage Air Conditioner Variable Speed Furnace Thermidistat 2 Stage Air Conditioner Heat Stage 2 O B W2 W2 Heat...

Page 15: ...le with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plas...

Page 16: ... W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANA 6SI Replaces 24ANA 5SI 24ANA ...

Reviews: