Compressor Operation on 24ANA1 Models

The basic scroll design has been modified with the addition of an

internal unloading mechanism that opens a by--pass port in the first
compression pocket, effectively reducing the displacement of the

scroll. The opening and closing of the by--pass port is controlled
by an internal electrically operated solenoid. The modulated scroll

uses a single step of unloading to go from full capacity to
approximately 67% capacity.
A single speed, high efficiency motor continues to run while the

scroll modulates between the two capacity steps. Modulation is
achieved by venting a portion of the gas in the first suction pocket

back to the low side of the compressor, thereby reducing the
effective displacement of the compressor.
Full capacity is achieved by blocking these vents, thus increasing

the displacement to 100%. A DC solenoid in the compressor
controlled by a rectified 24 volt AC signal in the external solenoid

plug moves the slider ring that covers and uncovers these vents.
The vent covers are arranged in such a manner that the compressor

operates at approximately 67% capacity when the solenoid is not
energized and 100% capacity when the solenoid is energized. The

loading and unloading of the two step scroll is done ”on the fly”

without shutting off the motor between steps.

NOTE

: 67% compressor capacity translates to approximately

75% cooling capacity at the indoor coil.
The compressor will always start unloaded and stay unloaded for

five seconds even when the thermostat is calling for high--stage
capacity.

Crankcase Heater Operation

The crankcase heater is energized during unit off cycle regardless

of OAT temperature on 24ANA7 models.
The crankcase heater is energized during off cycle below
65

_

F/18.33

_

C on 24ANA1 models.

Outdoor Fan Motor Operation

The outdoor unit control energizes the outdoor fan any time the

compressor is operating except for low--ambient cooling operation.

The outdoor fan remains energized if a pressure switch or
compressor overload should open. Outdoor fan motor will

continue to operate for one minute after the compressor shuts off
when the outdoor ambient is greater than or equal to

100

_

F/37.78

_

C to allow for easier starting during next cooling

cycle.
On 24ANA7 models, the outdoor fan remains energized during the

1--minute compressor staging time delay.
On 24ANA7 models, the outdoor fan motor is a PSC type. A fan

relay on the control board turns the fan off and on by opening and
closing a high voltage circuit to the motor. It does not change

speeds between low-- and high--stage operation.
On 24ANA1 models, the outdoor fan is an ECM type. The motor
control is continuously powered with high voltage. The motor

speed is determined by electrical pulses provided by the PWM
outputs on the control board. The ECM motor RPM adjusts to

outdoor conditions as described in Table 3. The PWM output can

be measured between the PWM1 and PWM2 terminals on the
circuit board with a volt meter set to DC volts.

Table 3 – Outdoor Fan Motor PWM

Outdoor Temp (DC volts, Tol/-- 2%)

MODEL

LOW---STAGE

(OAT

104

_

F/40

_

C)

HIGH---STAGE

(OAT

104

_

F/40

_

C)

LOW--- & HIGH---

STAGE

(OAT

>

104

_

F/40

_

C)

24ANA124

9.57

10.88

11.90

24ANA136

9.06

10.23

11.90

24ANA148

9.91

11.04

11.90

24ANA160

10.83

11.70

11.90

NOTE

:

For 24ANA1 models in low---ambient cooling, the PWM output for both

high--- and low---stage equals the value for low---stage operation below 55

_

F

(12.8

_

C).

In low ambient cooling (below 55

_

F/12.78

_

C) on 24ANA7 and

24ANA1 models, the control board cycles the fan off and on.

Time Delays

The unit time delays include:

S

Five minute time delay to start cooling or heating operation

when there is a call from the thermostat or user interface. To

bypass this feature, momentarily short and release Forced

Defrost pins.

S

Five minute compressor re--cycle delay on return from a

brown--out condition.

S

Two minute time delay to return to standby operation from last

valid communication (with Infinity only).

S

One minute time delay of outdoor fan at termination of cooling

mode when outdoor ambient is greater than or equal to

100

_

F/37.78

_

C.

S

On 24ANA7 models there is a 1 minute time delay between

staging from low to high and from high to low capacity. On

24ANA1 models there is no delay; the compressor will change

from low to high and from high to low capacity on the fly to

meet the demand.

Low Ambient Cooling

If this unit will be required to operate below 55

_

F/12.78

_

C

outdoor temperature, provisions must be made for low ambient

operation.

Infinity Controlled low ambient cooling:

This unit is capable of low ambient cooling

down to

0

_

F/--17.78

_

C without a kit ONLY when using Infinity control. A

low ambient kit is not required, and the outdoor fan motor does not

need to be replaced for Infinity controlled low ambient operation.
The Infinity Control provides an automatic evaporator coil freeze

protection algorithm that eliminates the need for an evaporator

freeze thermostat. Low ambient cooling must be enabled in the
User Interface set up. Fan may not begin to cycle until about

40

_

F/4.4

_

C OAT. Fan will cycle based on coil and outdoor air

temperature.
Infinity controlled low ambient mode operates as follows:

S

Fan is OFF when outdoor coil temp is < (outdoor air tempe
3

_

F/1.67

_

C) or outdoor fan has been ON for 30 minutes. (Fan is

turned off to allow refrigerant system to stabilize.)

S

Fan is ON when outdoor coil temp > (outdoor air tempe
25

_

F/13.89

_

C) or outdoor coil temp > 80

_

F/26.67

_

C or if outdoor

fan has been OFF for 30 minutes. (Fan is turned on to allow
refrigerant system to stabilize.)

S

Low pressure switch is ignored for first 3 minutes during low
ambient start up. After 3 minutes, if LPS trips, then outdoor fan
motor is turned off for 10 minutes, with the compressor running. If
LPS closes within 10 minutes then cooling continues with the
outdoor fan cycling per the coil temperature routine listed above
for the remainder of the cooling cycle. If the LPS does not close
within 10 minutes, then the normal LPS trip response (shut down
cooling operation and generate LPS trip error) will occur.

For 24ANA1 models, the PWM output for both high-- and

low--stage equals the value for low--stage operation below 55

_

F

(12.8

_

C).

24AN

A

Summary of Contents for 24ANA1 Infinity

Page 1: ...cognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazard...

Page 2: ...llation Specifications for this unit in residential new construction market require the outdoor unit indoor unit refrigerant tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Application Guideline and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for ...

Page 3: ...d tubing diameters Refer to Table 2 for accessory requirements There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for op...

Page 4: ...r CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Installation of filter drier in liquid line is required Refer to Fig 3 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor co...

Page 5: ...m unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if ...

Page 6: ... board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections This fan coil has an adjustable blower off delay factory set at 90 sec for high and low stage blower operation For other combinations of equipment consult the Product Data Sheet START UP CAUTION UNIT OPERATION AND SAFETY HAZARD Failure to follow...

Page 7: ...ht on the outdoor board see Fig 6 indicates successful communication with the other system products The green LED will remain OFF until communications is established Once a valid command is received the green LED will turn ON continuously If no communication is received within 2 minutes the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light i...

Page 8: ...s Table 3 Outdoor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 24ANA124 9 57 10 88 11 90 24ANA136 9 06 10 23 11 90 24ANA148 9 91 11 04 11 90 24ANA160 10 83 11 70 11 90 NOTE For 24ANA1 models in low ambient cooling the PWM output for both high and low stage equals the value for low stage operation below 55_F 1...

Page 9: ...r the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriate fault code temporarily Table 4 Model Plug Information MODEL NUMBER MODEL PLUG NUMBER PIN RESISTANCE K ohms Pins 1 4 Pins 2 3 24ANA724 HK70EZ00...

Page 10: ... Contactor Open 24ANA7 models No 230V at Compressor 24ANA1 models If the compressor voltage is not sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 24ANA7 Models Only Compressor Start Detection In low stage if the specified start voltage a...

Page 11: ...rload attached to motor windings Compressor Control Contactors The contactor s have a 24 volt coil The electronic control board controls the operation of the appropriate contactors TEMPERATURE THERMISTORS Thermistors are electronic devices which sense temperature As the temperature increases the resistance decreases Thermistors are used to sense outdoor ambient OAT and coil temperature OCT Refer t...

Page 12: ... that all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Users Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing h...

Page 13: ...nd exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed high stage Ther mal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage s...

Page 14: ...M 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Return SRTN SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor THERMIDISTAT VARIABLE SPEED FURNACE TWO STAGE AIR CONDITIONER A09338 Thermidistat Model TP PRH 01 or TP NRH 01 w VS Furnace 2 Stage Air Conditioner Variable Speed Furnace Thermidistat 2 Stage Air Conditioner Heat Stage 2 O B W2 W2 Heat...

Page 15: ...le with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plas...