COMPLETE REFRIGERANT PIPING CONNECTIONS

Outdoor units may be connected to indoor units using

field

supplied tubing of refrigerant grade and condition. See

Product Data for correct line sizes. Do not use less than 10 ft (3.05

m) of interconnecting tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4

mm) vertical rise to the valve connections on the outdoor

unit. If more than the recommended length is buried,

refrigerant may migrate to cooler, buried section during

extended periods of system shutdown. This causes refrigerant

slugging and could possibly damage the compressor at

start

up.

When more than 80 ft (24.4 m) of interconnecting tubing and more

than 20 ft (6.1 m) of vertical lift is used, consult the residential

Long Line Application Guide for required accessories. If either

refrigerant tubing or indoor coil is exposed to the atmosphere, the

system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary

turns and bends. Suspend refrigerant tubes so they do not damage

insulation on vapor tube and do not transmit vibration to structure.

Also, when passing refrigerant tubes through a wall, seal the

opening so that vibration is not transmitted to structure. Leave

some slack in refrigerant tubes between structure and outdoor unit

to absorb vibration. Refer to separate indoor unit installation

instructions for additional information.

Filter Drier

Refer to Fig. 3 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from

step 1.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3

 - 

Filter Drier Components

The filter drier must be replaced whenever the refrigeration system

is exposed to the atmosphere.
Only use factory specified liquid

line filter driers with rated

working pressures less than 600 psig.

NOTE

:  Do not install a suction

line filter drier in liquid line.

Make Piping Sweat Connections

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors.  Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

Remove plastic caps from liquid and suction service valves. Use

refrigerant grade tubing. Service valves are closed from the factory

and are ready for brazing. After wrapping the service valve with a

wet cloth, the tubing set can be brazed to the service valve using

either silver bearing or non

silver bearing brazing material.

Consult local code requirements. Refrigerant tubing and the indoor

coil are now ready for leak testing.

NOTE

:  Unit is shipped with Puron (R

410A) refrigerant factory

charge indicated on nameplate.
Pass nitrogen or other inert gas through piping while brazing to

prevent formation of copper oxide.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to unit or service valves observe the

following:

S

  Use a brazing shield.

S

  Wrap service valves with wet cloth or use a heat sink 

material.

MAKE ELECTRICAL CONNECTIONS

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Unit failure as a result of operation on improper line voltage

or excessive phase imbalance constitutes abuse and may

cause damage to electrical components. Such operation

would void any applicable warranty.