background image

5

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
The unit coils hold only the factorydesignated amount of

refrigerant. Additional refrigerant may cause units to relieve

pressure through the compressor internal pressure relief

valve (indicated by a sudden rise of suction pressure) before

suction pressure reaches 20 psig. If this occurs, shut off unit

immediately then front

seat the suction valve and remove

and recover excess refrigerant following accepted practices

3. Start unit and run until suction pressure reaches 20 psig.
4. Shut unit off and front

seat suction valve.

5. De

pressurize low side of unit and recover refrigerant fol-

lowing accepted practices.

Crankcase Heater

The crankcase heater prevents refrigerant migration and

compressor oil dilution during shutdown when compressor is not

operating. If the crankcase heater is de

energized for more than 6

hours, both compressor service valves must be closed.

NOTE

:  Addition of an accessory crankcase heater is required for

long line and low ambient colling applications.  Refer to the
Residential Long Line Guideline.
The crankcase heater is powered by the high

voltage power of the

unit. It is connected across the line side of the contactor and is

thermostatically controlled.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury

or death.
Use extreme caution when troubleshooting this device as

line voltage is continually present.

To troubleshoot:

1. Apply voltmeter across crankcase heater leads to see if heat-

er voltage is on. Do not touch heater. Carefully feel area

around crankcase heater; if warm, crankcase heater is func-

tioning.

2. With power off and heater leads disconnected, check across

leads with ohmmeter. Do not look for a specific resistance

reading. Check for resistance or an open circuit, and change

heater if an open circuit is detected.

Service Valves

The service valves in the outdoor unit come from the factory

front

seated. This means the refrigerant charge is isolated from the

line

set connection ports. To prevent damage to the valve, use a

wet cloth or other accepted heat sink material on the valve before

brazing.
The service valve cannot be field repaired, therefore, only a

complete valve or valve stem seal and service port caps are

available for replacement.

Refrigerant Charging

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Wear safety glasses and gloves when handling refrigerant.

Do not overcharge system 

 this can cause compressor

flooding.

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Service valves must be fully back

seated to close service

port. There is no Schrader valve at the service port, and

failure to back

seat the valve could result in loss of system

charge or personal injury.

NOTE

:  Do not vent or de

pressurize unit refrigerant to

atmosphere. Remove and recover refrigerant following accepted
practices.
All units are shipped with the refrigerant charge listed on the

nameplate.
Refer to Product Data and consider the following when working

with Puron (R

410A) refrigerant:

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400

psig, DOT (Department of Transportation) 4BA400 or

DOT BW400.

S

Puron systems should be charged with liquid refrigerant.

Use a commercial type metering device in the manifold

hose when charging into suction line with compressor op-

erating.

S

Manifold sets should be 700 psig high side and 180 psig

low side with 550 psig low

side retard.

S

Use hoses with 700 psig service pressure rating.

S

Puron refrigerant, as with other HFCs, is only compatible

with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Polyol Ester oils absorb moisture rapidly. Do not expose oil

to atmosphere.

S

Polyol Ester oils may cause damage to certain plastics and

roofing materials.

S

Wrap all filter driers and service valves with wet cloth when

brazing.

S

 factory approved, liquid

line filter drier is required on ev-

ery unit.

S

Do not use a TXV (thermostatic expansion valve) designed

for use with R

22 refrigerant. Refer to separate indoor unit

installation instructions for more details.

S

If using a suction line drier, do not leave in place for more
than 72 hours.

35 ft. (10.6 m) 

 25 ft. (7.6 m) = 10 ft. X 0.6 oz./ft. = 6 oz. of

additional charge.

Reviews: