background image

4

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
Before performing service or maintenance, be sure indoor unit

main power switch is turned OFF and indoor blower has

stopped.

Power Wiring

Unit is factory wired for voltage shown on nameplate. Provide

adequate, fused disconnect switch within sight from unit, readily

accessible, but out of reach of children. Provision for locking the

switch open (off) is advisable to prevent power from being turned

on while unit is being serviced.
Disconnect switch, fuses, and field wiring must comply with the

NEC and local code requirements. Use copper wire only between

the disconnect switch and unit. Use minimum 75 C wire for the

field power connection.
Route power wires through the opening in unit side panel and

connect in the unit control box as shown on the unit label diagram

and Fig. 4. Unit must be grounded.

LEGEND

NEC

National Electrical Code

TB

Terminal Board

TB Connections
Field Wiring
Factory Wiring

A07428

Fig. 4

 - 

Line Power Connections

Control Circuit Wiring

Control voltage is 24 v (40 va minimum). See Fig. 5 and unit label

diagram for field

supplied wiring details. Route control wire

through opening in unit side panel to connection in unit control

box.

A07398

Fig. 5

 - 

24AHA4 Typical Control Circuit Connections

NOTE

:  Use No. 18 AWG color

coded, insulated (35

_

C

minimum) wire. If thermostat is located more than 100 ft. (30.5 m)

from unit, as measured along the control voltage wires, use No. 16

AWG color

coded wire to avoid excessive voltage drop.

NOTE

:  All wiring must conform to NEC and local codes.

NOTE

:  Operating unit on improper line voltage constitutes abuse

and could affect warranty. See Product Data. 

Do not

 install unit in

a system where voltage may fluctuate above or below permissible

limits.
Refer to the Product Data for recommended fuse sizes. When

making electrical connections, provide clearance at the unit for

refrigerant piping connections.

NOTE

:  The 24AHA4 units use the control transformer supplied

with the matched indoor unit.

START

UP

PRELIMINARY CHECKS

1. Check that all internal wiring connections are tight and that

all barriers, covers, and panels are in place.

2. Field electrical power source must agree with unit name-

plate rating.

3. All service valves must be open.
4. Belly

band crankcase heater must be tight on compressor

crankcase for those units with belly

band heaters.

EVACUATE AND DEHYDRATE

Field piping and fan coil must be evacuated and dehydrated.

CHARGE SYSTEM

Release charge into system by opening (back

seating) liquid and

suction line service valves. Outdoor unit is charged for 15 ft (4.6

m) of 3/8

in. liquid line.

TO START UNIT

Be sure that the field disconnect is closed. Set room thermostat

below ambient temperature. Operate unit for 15 minutes, then

check system refrigerant charge. See Refrigerant Charging section.

SERVICE

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

High

Pressure Relief Valve

The high

pressure relief valve is located in the compressor. The

relief valve opens at a pressure differential of approximately 550 to

625 

±

 50 psig between suction (low side) and discharge (high side)

to allow pressure equalization.

Internal Current and Temperature Sensitive Overload

The control resets automatically when internal compressor motor

temperature drops to a safe level (overloads may require up to 45

minutes to reset). When an internal overload is suspected of being

open, check by using an ohmmeter or continuity tester.

Pumpdown Procedure

The system may be pumped down in order to make repairs on the

low side without losing complete refrigerant charge.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never open system to atmosphere while it is under a vacuum.

When system must be opened for service, recover refrigerant, break

vacuum with dry nitrogen before opening system.

1. Attach pressure gage to suction service valve gage port.
2. Front

seat the liquid/mixed phase line valve.

Reviews: