
NOTE:
Leave blower access panel installed to maintain power to
control to view current LED status.
c. Remove control access door.
d. BRIEFLY remove either wire from the main limit switch
until LED goes out, then reconnect it.
NOTE:
If wire to main limit is disconnected longer than 4 sec,
main blower starts, and retrieval request is ignored.
2. When above items have been completed, the following will
occur:
a. LED flashes a status code 4 times. Record this status code
for further troubleshooting.
b. Inducer motor starts and continues to run the entire
component test.
c. Hot surface igniter is energized for 15 sec, then de-
energized.
d. Main blower operates at cooling speed for 10 sec, then
turns off.
e. Main blower operates at heating speed for 10 sec, then
turns off.
f. Inducer motor stops.
Items a through e above will assist in furnace troubleshooting
since all components are functionally operated except the gas
valve. This procedure is also referred to as "Component Test."
3. Operate furnace through 1 heat cycle to test for proper
operation and check LED status.
4. If furnace is operating properly and LED indicates proper
operation, replace control access door.
5. Component Test can also be initiated by performing the
following:
a. Remove control access door.
b. Remove blower access door.
c. Manually close blower access door switch.
Blower access door switch opens 115-v power to control. No
component operation can occur. Caution must be taken when
manually closing this switch for service purposes. Failure to
follow this warning could result in personal injury or death.
d. BRIEFLY short (jumper) TEST, 3/16-in. quick-connect
terminal on control (adjacent to LED diagnostic light), and
C
OM
-24V terminal on furnace thermostat connection block.
(See Fig. 11.)
NOTE:
If TEST to C
OM
-24V terminals are jumpered longer than
2 sec, LED will flash rapidly, and test request will be ignored.
e. Component Test will function as described in item 2 above.
f. Check LED status.
g. If LED status indicates proper operation, RELEASE
BLOWER ACCESS DOOR SWITCH, replace blower
access door, and replace control access door.
TROUBLESHOOTING
Refer to the service label. (See Fig. 13.) Pages 10 and 11 contain
a troubleshooting guide. This guide can be a useful tool in isolating
furnace operation problems. Beginning with the word "Start,"
answer each question and follow the appropriate arrow to the next
item.
The guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
Fig. 10—Heating and Cooling Application Wiring Diagram
A98521
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
C
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
7