Fig. 13—Service Label

A99233

SERVICE

G

R

Y

W

Com

HUM

TES

T

LE
D

LED CODE

STATUS

24V

11

12

13

14
21

22

23

24

31

33

34

*

9

8

6

5

32

1

4

7

COMPONENT TEST

NO PREVIOUS CODE - Stored status codes are erased when power
(115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.
BLOWER ON AFTER POWER UP  (115VAC or 24 VAC)  -  Blower runs for 90
seconds, if unit is powered up during a call for heat (R-W closed).
LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will auto reset after
three hours. Reset switch or replace fuse link.  Refer to #33.
IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve          -Defective control (Valve relay)
ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared.
Check for:    - Leaky gas valve              - Stuck-open gas valve
PRESSURE SWITCH DID NOT OPEN - Check for:
- Obstructed pressure tubing.           - Pressure switch stuck closed.
SECONDARY VOLTAGE FUSE IS OPEN
Check for:      - Short circuit in secondary voltage (24VAC) wiring.
PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED
VENT SWITCH
 (when used) DID NOT CLOSE OR REOPENED
(DOWNFLOW ONLY*)
  If open longer than five minutes, inducer shuts off for 15
minutes before retry.      Check for:

- Proper vent sizing

- Low inducer voltage (115VAC)

- Defective inducer motor

- Defective Blower motor or capacitor

- Restricted vent

- Defective pressure switch

- Excessive wind

- Inadequate combustion air supply
- Disconnected or obstructed pressure tubing
If it opens after trial for ignition period, blower will come on for 90 second
recycle delay.
LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes, code changes to #13. Flame roll-out switch requires manual reset.
Check for:           - Defective blower motor or capacitor.
- Dirty filter or restricted duct system.
- Loose blower wheel.
- Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch or fuse link open).
- Open Flame Roll-out Switch, or fuse link. Manual reset or replace.
IGNITION PROVING FAILURE - Control will try three more times before
lockout #14 occurs. If flame signal lost after trial for ignition period, blower
will come on for 90 second recycle delay. Check for:
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
- Gas valve defective or gas valve turned off.
- Defective Hot Surface Ignitor

- Manual valve shut-off.

- Low inlet gas pressure.

- Control ground continuity

- Green wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
- Flame sensor must be ungrounded.

To initiate the component test sequence, shut OFF the room thermostat or
disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "Com
24V" terminal. Status LED will flash code and then turn ON the inducer motor.
The inducer motor will run for the entire component test. The hot surface ignitor,
blower motor-heat speed, and blower motor-cool speed will be turned ON for
10-15 seconds each. Gas Valve and Humidifier will not be turned on.

If status code recall is needed, do not remove power or blower door. Briefly remove and then
reconnect one main limit wire to display stored status code.

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and

SEC-2.

CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING -  Line voltage (115VAC) polarity reversed. If twinned, refer

to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY
THE NUMBER OF LONG FLASHES.

320615-102 REV. K (LIT)

10

Summary of Contents for 170 Series

Page 1: ... safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 NFPA 90B In Canada refer to the CAN CGA B149 1 and 2 M95 National Standard of Canada Natural Gas and Propane Installation Codes NSCNGPIC Wear safety glasses and work gloves Have fire extinguisher available during start up and adjustment procedures and service calls Recognize safety information This is the safety ...

Page 2: ...l sources may also be used to prevent ESD damage CARE AND MAINTENANCE For continuing high performance and to minimize possible equip ment failure it is essential that periodic maintenance be performed on this equipment Consult your local dealer as to the proper frequency of maintenance and the availability of a maintenance contract Never store anything on near or in contact with the furnace such a...

Page 3: ...and let dry Oiling or coating of filter is not recommended or required g Reinstall filter s h Replace blower and control access doors i Restore electrical power to furnace BLOWER MOTOR AND WHEEL The following steps should be performed by a qualified service technician To ensure long life economy and high efficiency clean accumu lated dirt and grease from blower wheel and motor annually The inducer...

Page 4: ...efer to Table 3 for motor speed lead relocation if leads were not identified before disconnection Heating air speed selection MUST be adjusted to provide proper air temperature rise as specified on the rating plate Failure to adjust the heating speed may shorten heat ex changer life 14 Downflow furnaces only Reinstall internal vent pipe and enclosure by reversing items 3a through 3d NOTE A releasi...

Page 5: ...ature switch es e Gas valve f Hot surface igniter g Flame sensing electrode h Flame rollout switch es if applicable 7 Remove complete inducer assembly and relief box from furnace 8 Remove 8 screws that secure flue collector box to center panel Be careful not to damage collector box 9 Remove burner assembly and cell inlet plates IMPORTANT Replace screws in center panel and cells before cleaning NOT...

Page 6: ...2 Replace control access door on upflow furnace 23 On downflow horizontal furnaces remove blower access door replace control access door first then replace blower access door and secure with screws in front of door ELECTRICAL CONTROLS AND WIRING There may be more than 1 electrical supply to the unit Check accessories and cooling unit for additional electrical supplies The electrical ground and pol...

Page 7: ...to follow this warning could result in personal injury or death d BRIEFLY short jumper TEST 3 16 in quick connect terminal on control adjacent to LED diagnostic light and COM 24V terminal on furnace thermostat connection block See Fig 11 NOTE If TEST to COM 24V terminals are jumpered longer than 2 sec LED will flash rapidly and test request will be ignored e Component Test will function as describ...

Page 8: ...ANSFORMER SEC 2 SPARE 1 SPARE 2 EAC 1 EAC ELECTRONIC AIR CLEANER TERMINALS 115 VAC 1 0 AMP MAX EAC 2 115 VAC L2 NEUTRAL CONNECTION 24 V THERMOSTAT TERMINALS BLOWER SPEED SELECTION TERMINALS INDUCER MOTOR CONNECTOR 115 VAC L1 POWER SUPPLY HOT SURFACE IGNITOR CONNECTOR HEAT SEC 1 C OM 24V HUM G R Y W TEST TWIN COOL 3 AMP FUSE 8 ...

Page 9: ...VAC CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 COM HSIR EAC 1 START OL COM HI MED HI MED LO LO BLWM SCHEMATIC DIAGRAM NATURAL GAS PROPANE EAC 2 1 1 HSI 2 PL5 2 PL2 3 PL3 PR2 115VAC PR1 TRAN 24VAC 1 2 IDR TEST TWIN FU1 NOTE 6 CAP L2 PL1 8 FSE...

Page 10: ...lame roll out switch requires manual reset Check for Defective blower motor or capacitor Dirty filter or restricted duct system Loose blower wheel Defective switch or connections Inadequate combustion air supply Flame Roll out Switch or fuse link open Open Flame Roll out Switch or fuse link Manual reset or replace IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs ...

Page 11: ...11 ...

Page 12: ...un for the entire component test The HSI blower motor heat speed and blower motor cool speed will run for 10 15 sec each Determine status code The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes Was there a previous fault code other than No 11 Does control respond to W Y or G 24 vac thermostat signals...

Page 13: ...e gas valve was de energized Inducer will run until fault is cleared Check for Stuck open gas valve solenoid or leak Defective control center 23 PRESSURE SWITCH WILL NOT OPEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 LOW VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwork or furnace cabinet Disconnect th...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ... Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 2000 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58pr15sm Manufacturer reserves the right t...

Reviews: