background image

Fuel System Installation —

See Fig. 12-14 for typi-

cal gas train and oil supply system arrangements. Refer to
burner manual supplied with the burner for installation in-
structions on the particular version of gas train and/or oil
supply system used with your application. These systems are
supplied pre-assembled, and with pre-installed interconnec-
tion fittings.

Do not use Teflon tape on any threaded connections as
a gas or oil pipe sealant. Loose tape pieces can cause
valve leakage and are a safety hazard. Use a pipe joint
compound.

GAS TRAIN — The high-gas pressure switch is mounted
on the gas train piping for convenience only, and does not
monitor the gas pressure at that location. A brass pipe tee
and a coil of 3/8-in. aluminum tubing with fittings are sup-
plied to connect the sensing line between the pressure switch
and the top of the burner manifold, as shown with dashed
lines on the gas train piping schematic.

Another coil of 3/8-in. aluminum tubing with compres-

sion fittings is provided for the pilot connection between the
pilot shutoff valve (mounted ahead of the main manual shut-
off valve) and the pilot gas pressure regulator (mounted on
the burner).

IMPORTANT: Do not use copper tubing for the gas
pilot supply.

Gas supply and vent connections are discussed under Con-
nect Fuel Piping in the Field Piping section of this manual.

OIL SUPPLY SYSTEM — This burner uses a separate motor-
driven oil pump which should be located close to the burner
and secured to the floor. The oil pump connections are iden-
tified with tags for suction (supply) and return lines. The pip-
ing diagram with mounting dimensions and port sizes for
your particular application is shown in the burner manual.
Oil supply and return connections are discussed under Con-
nect Fuel Piping in the Field Piping section of this
manual.

FIELD PIPING

Connect Water Piping —

Install piping using job data,

piping drawings, and procedures outlined below. A typical
piping installation is shown in Fig. 15.
1. Make sure all connections to water box covers allow open-

ing of covers for maintenance.

2. Installation and piping should allow sufficient access for

cleaning or replacing tubes.

3. Install pipe hangers where needed. Make sure no weight

or stress is placed on water box nozzles or flanges.

ITEM

DESCRIPTION

1

Pilot Shutoff Cock

2

Pilot Gas Pressure Regulator

3

Second Safety Shutoff

Pilot Valve (if used)

4

Safety Shutoff Pilot Valve

5

Gas Pressure Gage (if used)

6

Manual Leak Test Valve

7

Butterfly Gas Valve

8

High Gas Pressure Switch

9

Safety Shutoff Gas Valve

10

Second Safety Shutoff Gas Valve

11

Low Gas Pressure Switch

12

Gas Pressure Regulator

13

Manual Gas Shutoff Valve

NOTES:
1. Piping and fittings shown dashed to be supplied and installed by the burner

installation contractor.

2. For proper regulation and performance, regulators with internal control

require at least 5 pipe diameters of straight pipe on the outlet side un-
interrupted with fittings, elbows, etc.

3. The outlet screwed connections must conform with good piping prac-

tices, free of excess thread engagement.

4. The top cap at the spring must be in place or unstable operation can

occur.

5. For parts not identified, see burner manufacturer’s material list.

Fig. 12 — Gas Train, Typical

9

Summary of Contents for 16DF013

Page 1: ...um or pressurized condition NEVER APPLY an open flame or live steam to a refrigerant cylinder Dangerous overpressure can result When necesary to heat a cylinder use only warm 110 F 43 C water DO NOT REUSE disposable nonreturnable cylinders or at tempt to refill them It is DANGEROUS AND ILLEGAL When cylinder is emptied bleed off remaining gas pressure loosen the collar and unscrew and discard the v...

Page 2: ...r model numbers and serial numbers are stamped on machine identification plates Check this information against shipping papers and job data Inspect Shipment Fig 1 Single piece machines are at a deep vacuum when shipped Do not open any valves until the vacuum has been noted Refer to Check Shipping Vacuum section below Machines shipped in 2 pieces are under nitrogen pressure Inspect for shipping dam...

Page 3: ... age the machine See Mounting the Burner section for burner rigging instructions Rigging 2 Piece Units PREPARATION Two piece units must be prepared for installation before they can be rigged 1 Open auxiliary evacuation valves to relieve pressure in absorber evaporator shell 2 Open shipping valve on generator assembly to relieve pressure 3 Remove all piping end plates by flamecutting the end plate ...

Page 4: ...Fig 2 16DF Views Typical V Lifting Holes Fig 3 Rigging One Piece Units Typical Top View 4 ...

Page 5: ...0 10 150 31 760 43 660 050 22 050 10 150 32 200 44 100 SI UNIT 16DF SHIPPING WEIGHT kg OPERATING WEIGHT kg Absorber Evaporator Low Temperature Generator Assembly High Temperature Generator Separator Assembly Total Weight 013 6 000 7 800 015 6 100 7 900 018 6 900 9 200 020 7 000 9 300 023 6 600 1800 8 400 11 300 025 6 700 1800 8 500 11 400 028 7 300 3900 11 200 14 800 032 7 500 3900 11 400 15 000 0...

Page 6: ...tor assembly first See Position and Level the Equipment section 3 Move the generator separator assembly into place beside the absorber evaporator assembly 4 Align connecting piping for generator separator and absorber evaporator assemblies Make sure serial numbers corre spond on both assemblies 5 See Mounting the Burner section for burner rigging instructions Position and Level the Equipment Isola...

Page 7: ...ak de tectors or equivalent If machine has acquired a leak in shipment or rigging all joints must be leak tested 6 After leak testing has been completed and leaks have been corrected release the machine pressure Machine Evacuation Removal of non condensables from the machine is required after machine has been opened To evacuate the machine proceed as follows 1 Connect auxiliary evacuation device F...

Page 8: ...high temperature insulating rope it must be wrapped around the flange circumference INSIDE of the mounting studs or bolt holes with overlapping ends to provide a complete gas tight seal Wrapping the rope around the outside of the studs or bolt holes could allow high temperature gas leakage through the holes in the attached plates Use either gasket cement or masking tape to hold the ropes in place ...

Page 9: ...iden tified with tags for suction supply and return lines The pip ing diagram with mounting dimensions and port sizes for your particular application is shown in the burner manual Oil supply and return connections are discussed under Con nect Fuel Piping in the Field Piping section of this manual FIELD PIPING Connect Water Piping Install piping using job data piping drawings and procedures outline...

Page 10: ... dam aged Fig 13 Mechanical Pressure Atomizing Light Oil Pump with External Regulating Relief Valve NOTES 1 Oil system schematic shown in high fire position 2 Supply pressure must not exceed 3 psi 20 kPa or pump seals may be dam aged Fig 14 Mechanical Pressure Atomizing Light Oil Pump with Integral Regulating Relief Valve 10 ...

Page 11: ...l thermometer wells and thermometers on the en tering and leaving chilled hot water pipes absorber en tering and leaving cooling water pipes and condenser leaving cooling water pipe Thermometer wells should extend into the pipe a minimum of 1 3 pipe diameter 9 Install pressure gage taps and pressure gages on the en tering and leaving chilled hot water pipes and cooling wa ter pipes Fusible Plug Dr...

Page 12: ...test indicate possible leakage do not apply insulation until leak has been corrected Most of the machine surfaces become hot during the heat ing cycle and those areas should be insulated with heat resistant material High temperature fire resistant material should be used in areas near the burner refractory door and exhaust All wiring should be external to the finished insu lation The insulation sh...

Reviews: