background image

Connect Rupture Disc Piping —

Vent rupture disc

to the outside of the building for safety. Model 16DF ma-
chines sometimes are factory equipped with a rupture disc
assembly on the generator-vapor transfer area.
1. Add a flexible connection and adequate support to pipe,

as required, to eliminate any piping stress on rupture disc.
Provide fittings so vent piping can be disconnected pe-
riodically for inspection of disc. Provide pipe plug on out-
let side of relief device for leak testing.

2. Cover outdoor vent with a rain cap to prevent excessive

moisture from entering the vent line.

3. Place a condensate drain at the low point in the piping to

prevent any water build-up on the atmospheric side of
the disc assembly.

Connect Fuel Piping —

Connect fuel lines to burner

fuel system and install separate fuel fittings using job data,
piping drawings, and general guidelines found in the burner
manual supplied by the burner manufacturer. Installation re-
quirements will vary for local building and insurance codes,
and for different application conditions.

Do not use Teflon Tape as an oil or gas pipe sealant.
Tape can cause valves to fail, creating a safety hazard.
Use a pipe joint compound.

1. Use a full size dirt pocket or trap in gas piping ahead of

the main manual shutoff.

2. Piping must be sized to provide the minimum specified

oil or gas pressure at the main manual shutoff when op-
erating at the maximum input.

3. A 2-pipe system with suction and return lines must be

used for oil burners, and the lines should be run in a trench
or under the floor when possible. Copper tubing with flare
fittings should be used for oil lines.

4. Hand valves must not be installed on discharge side of oil

pump or return line without a bypass relief installed to
the tank. An oil shut-off valve should be provided in the
suction line near the burner.

5. Oil suction lines should be pitched back slightly to the

tank and care should be taken to avoid any air traps in the
line.

6. The fuel system must be pressure tested with air or inert

gas and proven leak tight. Gas systems should be tested
for at least 3 times the gas pressure that will be used.

Connect Exhaust Duct —

Connect combustion ex-

haust ducting using job data and piping drawings. Systems
will vary for different application conditions.
1. Sharp bends and restrictions should be avoided to allow

smooth gas flow.

2. The outlet should be arranged to prevent rainwater entry

into the machine exhaust, and drains should be provided
to remove condensate or water.

3. Exhaust gas dampers and draft regulators must be in-

stalled correctly for proper operation.

INSULATION AND PAINT

Insulation (If Required) —

Apply insulation as in-

dicated in job data, after machine assembly and field piping
have been completed. If shipping vacuum or pressure test
indicate possible leakage, do not apply insulation until leak
has been corrected.

Most of the machine surfaces become hot during the heat-

ing cycle and those areas should be insulated with heat-
resistant material. High-temperature, fire resistant material
should be used in areas near the burner, refractory door, and
exhaust. All wiring should be external to the finished insu-
lation. The insulation should be applied so all flanged serv-
ice connections can be easily opened, and all valves, con-
trols, and sensor locations should be easily accessible.

Final Paint Coat (If Required) —

Paint machine as

indicated in job data, after installation assembly, leak test-
ing, and insulation have been completed. Use specified paint,
making sure only high-temperature paint is applied to areas
with hot surfaces.

ELECTRICAL CONNECTIONS

Field wiring must be installed in accordance with job and

machine/burner wiring diagrams, and all applicable electri-
cal codes.

Check Available Power Supply and Safety-
Interlocks —

Available power supply and safety inter-

locks must match the machine equipment. Job voltage, am-
perage, and values are stated on the machine and burner wiring
diagrams.

Machine Control Panel External Wiring —

All

machine sensors and controls are factory installed. External
field wiring connections to machine control panel wiring ter-
minals include:
• three-phase power supply
• control start/stop interlocks for chilled/hot water pump(s),

cooling water pump(s), and cooling tower fan(s)

• high-temperature generator sensors on machines shipped

in 2 pieces

• remote start/stop (when used)
• remote status indicators (when used)

Burner Control Panel Wiring —

Field wiring con-

nections between wiring terminals in the machine and burner
control panels include:
• three-phase blower motor and oil pump motor power sup-

ply

• burner control power supply and burner start/stop signal
• open/close signals for firing rate positioning motor
• burner alarm and firing rate limit position signals for machine/

burner vs chiller heater microprocessor controls

There are also field wiring connections between the high-

stage generator’s low-level probe and its relay contacts in
the burner control panel, and between the burner control panel
and the fuel line connector box.

INITIAL SOLUTION AND REFRIGERANT

CHARGING

Lithium bromide solution and refrigerant (water) will be

placed in the machine at initial start-up. Do not charge so-
lution into the machine until the unit is ready for operation.

Do not start any pump motors until the machine has been
charged with solution and refrigerant. The hermetic pumps
can be seriously damaged by dry operations.

Refer to 16DF Start-up, Operation, and Maintenance In-
structions for charging procedures.

Copyright 1992 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 2
Tab

5b

PC 211

Catalog No. 531-602

Printed in U.S.A.

Form 16DF-1SI

Pg 12

3-92

Replaces: New

Summary of Contents for 16DF013

Page 1: ...um or pressurized condition NEVER APPLY an open flame or live steam to a refrigerant cylinder Dangerous overpressure can result When necesary to heat a cylinder use only warm 110 F 43 C water DO NOT REUSE disposable nonreturnable cylinders or at tempt to refill them It is DANGEROUS AND ILLEGAL When cylinder is emptied bleed off remaining gas pressure loosen the collar and unscrew and discard the v...

Page 2: ...r model numbers and serial numbers are stamped on machine identification plates Check this information against shipping papers and job data Inspect Shipment Fig 1 Single piece machines are at a deep vacuum when shipped Do not open any valves until the vacuum has been noted Refer to Check Shipping Vacuum section below Machines shipped in 2 pieces are under nitrogen pressure Inspect for shipping dam...

Page 3: ... age the machine See Mounting the Burner section for burner rigging instructions Rigging 2 Piece Units PREPARATION Two piece units must be prepared for installation before they can be rigged 1 Open auxiliary evacuation valves to relieve pressure in absorber evaporator shell 2 Open shipping valve on generator assembly to relieve pressure 3 Remove all piping end plates by flamecutting the end plate ...

Page 4: ...Fig 2 16DF Views Typical V Lifting Holes Fig 3 Rigging One Piece Units Typical Top View 4 ...

Page 5: ...0 10 150 31 760 43 660 050 22 050 10 150 32 200 44 100 SI UNIT 16DF SHIPPING WEIGHT kg OPERATING WEIGHT kg Absorber Evaporator Low Temperature Generator Assembly High Temperature Generator Separator Assembly Total Weight 013 6 000 7 800 015 6 100 7 900 018 6 900 9 200 020 7 000 9 300 023 6 600 1800 8 400 11 300 025 6 700 1800 8 500 11 400 028 7 300 3900 11 200 14 800 032 7 500 3900 11 400 15 000 0...

Page 6: ...tor assembly first See Position and Level the Equipment section 3 Move the generator separator assembly into place beside the absorber evaporator assembly 4 Align connecting piping for generator separator and absorber evaporator assemblies Make sure serial numbers corre spond on both assemblies 5 See Mounting the Burner section for burner rigging instructions Position and Level the Equipment Isola...

Page 7: ...ak de tectors or equivalent If machine has acquired a leak in shipment or rigging all joints must be leak tested 6 After leak testing has been completed and leaks have been corrected release the machine pressure Machine Evacuation Removal of non condensables from the machine is required after machine has been opened To evacuate the machine proceed as follows 1 Connect auxiliary evacuation device F...

Page 8: ...high temperature insulating rope it must be wrapped around the flange circumference INSIDE of the mounting studs or bolt holes with overlapping ends to provide a complete gas tight seal Wrapping the rope around the outside of the studs or bolt holes could allow high temperature gas leakage through the holes in the attached plates Use either gasket cement or masking tape to hold the ropes in place ...

Page 9: ...iden tified with tags for suction supply and return lines The pip ing diagram with mounting dimensions and port sizes for your particular application is shown in the burner manual Oil supply and return connections are discussed under Con nect Fuel Piping in the Field Piping section of this manual FIELD PIPING Connect Water Piping Install piping using job data piping drawings and procedures outline...

Page 10: ... dam aged Fig 13 Mechanical Pressure Atomizing Light Oil Pump with External Regulating Relief Valve NOTES 1 Oil system schematic shown in high fire position 2 Supply pressure must not exceed 3 psi 20 kPa or pump seals may be dam aged Fig 14 Mechanical Pressure Atomizing Light Oil Pump with Integral Regulating Relief Valve 10 ...

Page 11: ...l thermometer wells and thermometers on the en tering and leaving chilled hot water pipes absorber en tering and leaving cooling water pipes and condenser leaving cooling water pipe Thermometer wells should extend into the pipe a minimum of 1 3 pipe diameter 9 Install pressure gage taps and pressure gages on the en tering and leaving chilled hot water pipes and cooling wa ter pipes Fusible Plug Dr...

Page 12: ...test indicate possible leakage do not apply insulation until leak has been corrected Most of the machine surfaces become hot during the heat ing cycle and those areas should be insulated with heat resistant material High temperature fire resistant material should be used in areas near the burner refractory door and exhaust All wiring should be external to the finished insu lation The insulation sh...

Reviews: