Superheat Charging Table (English) 
(Superheat Entering Suction Service Valve

 

INDOOR COIL ENTERING AIR (°F) WET-BULB 

ENT. 

WATER 

TEMP

F) 

50 52 54 56 58 60 62 64 66 68 70 72 74 76 

55 

9  12 14 17 20 23 26 29 32 35 37 40 42 45

60 

7  10 12 15 18 21 24 27 30 33 35 38 40 43

65 

-  6  10 13 16 19 21 24 27 30 33 36 38 41

70 

-  -  7  10 13 16 19 21 24 27 30 33 36 39

75 

-  -  -  6  9  12 15 18 21 24 28 31 34 37

80 

-  -  -  -  5  8  12 15 18 21 25 28 31 35

85 

- - - - - - 8 

11 

15 

19 

22 

26 

30 

33

90 

- - - - - - 5 9 

13 

16 

20 

24 

27 

31

95 

- - - - - - - 6 

10 

14 

18 

22 

25 

29

100  - - - - - - - - 8 

12 

15 

20 

23 

27

105  - - - - - - - - 5 9 

13 

17 

22 

26

110  - - - - - - - - - 6 

11 

15 

20 

25

115  - - - - - - - - - - 8 

14 

18 

23

 

Symbol dash (-) means: Do not attempt to charge system under these conditions 
or refrigerant slugging may occur. 

 
 
 
 
 

Required Suction Tube Temperature (English) 
(Entering Suction Service Valve) 

 

SUCTION PRESSURE AT SERVICE PORT (psig) 

SUPERHEAT 

TEMP (°F) 

61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7 

35 37 39 41 43 45 47 49 51 

37 39 41 43 45 47 49 51 53 

39 41 43 45 47 49 51 53 55 

41 43 45 47 49 51 53 55 57 

43 45 47 49 51 53 55 57 59 

10 

45 47 49 51 53 55 57 59 61 

12 

47 49 51 53 55 57 59 61 63 

14 

49 51 53 55 57 59 61 63 65 

16 

51 53 55 57 59 61 63 65 67 

18 

53 55 57 59 61 63 65 67 69 

20 

55 57 59 61 63 65 67 69 71 

22 

57 59 61 63 65 67 69 71 73 

24 

59 61 63 65 67 69 71 73 75 

26 

61 63 65 67 69 71 73 75 77 

28 

63 65 67 69 71 73 75 77 79 

30 

65 67 69 71 73 75 77 79 81 

32 

67 69 71 73 75 77 79 81 83 

34 

69 71 73 75 77 79 81 83 85 

36 

71 73 75 77 79 81 83 85 87 

38 

73 75 77 79 81 83 85 87 89 

40 

75 77 79 81 83 85 87 89 91 

 

 
 
 
 
 
 
 
 
 
 

 
Superheat Charging Table (Metric

(Superheat Entering Suction Service Valve)

 

 

INDOOR COIL ENTERING AIR (°C) WET-BULB 

ENT. 

WATER 

TEMP(°C) 

10  11.1 12.2 13.3 14.4 15.6 16.7 17.8 18.9  20  21.1 22.2 23.3 24.4 

12 

6.7  7.8  9.4  11.1 12.8 14.4 16.1 17.8 19.4 20.6 22.2 23.3

25 

15.5  3.9 5.6 6.7 8.3  10 11.7 

13.3 15 16.7 

18.3 19.4 21.1 22.2 23.9

18.3 

-  3.3 5.8 7.2 8.9 10.6 

11.7 

13.3 15 16.7 18.3

20 21.1 22.8

21.1 

7  5.6  7.2  8.9 10.6 11.7 13.3 15 16.7 18.3

20 21.7

23.9  - - - 

3.3 

6.7 

8.3 

10 

11.7 

13.3 15.6 17.2 18.9 20.6

26.7  - - - - 

2.8 

4.4 

6.7 

8.3 

10 

11.7 13.9 15.6 17.2 19.4

29.4  - - - - - - 

4.4 

6.1 

8.3 

10.6 12.2 14.4 16.7 18.3

32.2  - - - - - - 

2.8 

7.2 

8.9 

11.1 13.3

15 

17.2

36  - - - - - - - 

4.4 

5.6 

7.8 

10 

12.2 13.9 16.1

37.8  - - - - - - - - 

3.3 

6.7 

8.3 

11.1 12.8

15 

40.6  - - - - - - - - 

2.8 

7.2 

9.4 

12.2 14.4

43.3  - - - - - - - - - 

3.3 

6.1 

8.3 

11.1 13.9

46.1  - - - - - - - - - - 

4.4 

7.8 

10 

12.8

 

Symbol dash (-) means: Do not attempt to charge system under these conditions 
or refrigerant slugging may occur. 

 
 

 

 

 
 
Required Suction Tube Temperature (Metric) 
(Entering Suction Service Valve)

 

 

SUCTION PRESSURE AT SERVICE PORT (KPaG) 

SUPERHEAT 

TEMP (°K) 

424 443 463 483 503 524 546 568 591 

1.7 2.8 3.9  5  6.1 7.2 8.3 9.4 10.6 

1.1 

2.8 3.9  5  6.1 7.2 8.3 9.4 10.6 

11.7 

2.2 

3.9 5 6.1 7.2 8.3 9.4 

10.6 

11.7 

12.8 

3.3 

6.1  7.2  8.3  9.4  10.6 11.7 12.8 13.9 

4.4 

6.1  7.2  8.3  9.4  10.6 11.7 12.8 13.9  15 

5.6 

7.2  8.3  9.4  10.6 11.7 12.8 13.9  15  16.1 

6.7 

8.3  9.4  10.6 11.7 12.8 13.9  15  16.1 17.2 

7.8 

9.4  10.6 11.7 12.8 13.9  15  16.1 17.2 18.3 

8.9 

10.6 11.7 12.8 13.9  15  16.1 17.2 18.3 19.4 

10 

11.7 12.8 13.9  15  16.1 17.2 18.3 19.4 20.6 

11.1 

12.8 13.9  15  16.1 17.2 18.3 19.4 20.6 21.7 

12.2 

13.9  15  16.1 17.2 18.3 19.4 20.6 21.7 22.8 

13.3 

15  16.1 17.2 18.3 19.4 20.6 21.7 22.8 23.9 

14.4 

16.1 17.2 18.3 19.4 20.6 21.7 22.8 23.9  25 

15.6 

17.2 18.3 19.4 20.6 21.7 22.8 23.9  25  26.1 

16.7 

18.3 19.4 20.6 21.7 22.8 23.9  25  26.1 27.2 

17.8 

19.4 20.6 21.7 22.8 23.9  25  26.1 27.2 28.3 

18.9 

20.6 21.7 22.8 23.9  25  26.1 27.2 28.3 29.4 

20 

21.7 22.8 23.9  25  26.1 27.2 28.3 29.4 30.6 

21.2 

22.8 23.9  25  26.1 27.2 28.3 29.4 30.6 31.7 

22.2 

23.9  25  26.1 27.2 28.3 29.4 30.6 31.7 32.8 

 
 
 
 
 
 
 
 

TABLE 6 

TABLE 7 

Summary of Contents for 07KHP

Page 1: ...ny transmission of noise and vibration to the ceiling or walls Provide enough pipe flexibility before fixing unit to the structure Provide access panel in ceiling Make sure the panel is located near the unit for easy maintenance and servicing After the unit is installed and pipe work are completed be sure to insulate the unit s surroundings with acoustic treatment An acoustic type insulation can b...

Page 2: ...8 6 1 1 8 REFRIGERANT CONNECTIONS Liquid mm in Flare Type 6 35 6 35 9 52 3 8 9 52 3 8 9 52 3 8 S 15 8 5 8 High Press PSIG 426 7 320 20 CONTROL PRESSURESTAT SETTINGS Open Close pressure settings Low Press PSIG n a 27 4 67 7 POWER SOURCE V Ph Hz NOMINAL V 208 230 1 60 230 3 60 PERMISSIBLE MIN MAX VOLTAGE V 197 253 REFRIGERANT CONTROL DEVICE IN UNIT Capillary Tube Capillary Accurator RLA Rated Load A...

Page 3: ... supplied and field installed applicable for model 07KHP036 048 060 and 090 only Warranty will be voided if these models were not fitted with external filter drier in the field installation TUBING CONNECTIONS AND LEAK TEST Both suction and liquid are equipped with flare type connections except for Model 090 uses sweat connection Assemble flare joint by aligning tubing with machine surface of fitti...

Page 4: ...eak is detected the refrigerant should be recovered before repairing the leak This is in compliance with the Clean Air Act WATER PIPING Water inlet and outlet are equipped with 25 4mm or 1 FPT female pipe thread Make sure that internal water piping is clean Use correct size wrenches and proper sealing for water inlet and outlet connections Do not over tighten the connections Suspend or use vibrati...

Page 5: ...5 FIG 6 CEILING MOUNTED INSTALLATION FIG 7 FLOOR MOUNTED INSTALLATION ...

Page 6: ...balance is satisfactory as it is below the maximum allowable 2 Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components OPERATION AND START UP PRELIMINARY CHECKS Before operating the unit be sure the following are in order 1 All wiring connections are correct and tight 2 All barriers covers and panels are in place 3 Electrical ...

Page 7: ... maintenance LUBRICANT Compressor contains factory oil charge Replace oil when lost See table 3 for oil recharge and refer to Carrier Manual Chapter 1 page 1 21 for oil recharging procedure CLEANING HEAT EXCHANGER Use a tank with 5 phosphoric acid Pump the cleaning liquid through the plate heat exchanger at 1 5 times normal flow rate for optimum cleaning preferably in back flush mode Then rinse wi...

Page 8: ......

Page 9: ...1 1 22 2 23 3 24 4 12 5 6 7 7 8 9 4 11 1 12 8 14 4 16 1 17 8 19 4 20 6 22 2 23 3 25 15 5 3 9 5 6 6 7 8 3 10 11 7 13 3 15 16 7 18 3 19 4 21 1 22 2 23 9 18 3 3 3 5 8 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 1 22 8 21 1 7 5 6 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 7 23 9 3 3 5 6 7 8 3 10 11 7 13 3 15 6 17 2 18 9 20 6 26 7 2 8 4 4 6 7 8 3 10 11 7 13 9 15 6 17 2 19 4 29 4 4 4 6 1 8 3 10 6 12 2 14 4...

Page 10: ...10 FIG 8 WIRING DIAGRAM 07KHP012 FIG 9 WIRING DIAGRAM 07KHP018 024 ...

Page 11: ...11 FIG 10 WIRING DIAGRAM 07KHP040 050 FIG 11 WIRING DIAGRAM 07KHP060 ...

Page 12: ...12 FIG 12 WIRING DIAGRAM 07KHP090 FIG 13 RECOMMENDED SERVICE CLEARANCES ...

Page 13: ...H LOOSE LEADS AT COMPRESSOR COMPRESSOR STUCK COMPRESSOR POWER SUPPLY OPEN COMPRESSOR INTERNAL PROTECTION OPEN OVERCHARGED OR NONCONDENSABLES IN SYSTEM OPEN SHORTED OR GROUNDED COMPRESSOR MOTOR WINDING HIGH SUPERHEAT COMPRESSOR BEARINGS DEFECTIVE FAN CAPACITOR LINE VOLTAGE TOO HIGH OR LOW LOW REFRIGERANT CHARGED RESTRICTED DISCHARGE LINE INTERNAL PRESSURE RELIEF OPEN DEFECTIVE COMPRESSOR VALVES CON...

Page 14: ...inlupa City Tel No 63 2 850 1367 Fax No 63 2 809 9979 Website www carrier com ph Manufacturer reserve the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Form 07KHP 4IOM Replaces 07KHP 3IOM Concepcion Carrier Air conditioning Company ...

Reviews: